Narsinha Engineering Works

TEST RESULTS OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS


ROUTINE TEST REPORT OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
Date Of Testing 15/07/2013
Dated 8/7/2013
PO No
Verbal
Costomer Name:
Sr
No

T/F Sr No

LV
HV Resistance in Resista HV IR LV IR

nce In losses Losses

Avg

1
2
3
4
5
6
7
8
9
10

NEWN-1
NEWN-2
NEWN-3
NEWN-4
NEWN-5
NEWN-6
NEWN-7
NEWN-8
NEWN-9
NEWN-10

Room Temp
30
Place
Nanded

19.45
19.75
20.12
19.76
19.38
20.11
19.78
19.81
19.42
19.32

Per Phase

28.68
28.65
28.64
28.32
28.52
28.63
28.45
28.75
28.62
28.12

Total
IR
Losses

No Load No Load
'I'
Losses
Measured Measured

Avg

Watt

Watt

Watt

Amps

Watt

0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011

804.5
818.2
831.1
810.5
815.4
806.4
817.5
811.4
813.7
825.3

257.1
269.4
271.9
266.0
269.0
271.9
266.8
269.5
269.8
270.8

1061.6
1087.6
1103.0
1076.5
1084.4
1078.3
1084.3
1080.9
1083.5
1096.1

1.55
1.42
1.45
1.41
1.42
1.34
1.38
1.43
1.39
1.40

242.50
238.00
240.20
237.70
238.00
235.00
236.40
238.40
236.70
237.00

Vector Group Confirmation ( R r Shorted) : Found OK


Magnetic Balance Test : FOUND OK
DVDF induced over voltage 3 Ph 866 V of 100 Hz : Withstand for 1 min
Seprate Source Test: HV 28 Kv & LV 3 Kv withstand for 1 Min.
BDV: Oil Tested at 2.5 mm gap withstood at 60 KV
Insualtion Resistance : Above 2000 M at Ambient Temprature.
Ratio Test: Found OK

Full
Full Load losses Load
measured
Loss @
5.248 A
Amps

5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25

Watt

Watt

1460.8
1480.6
1507.9
1510.5
1535.6
1498.5
1516.7
1542.5
1506.4
1490.5

1475.6
1497.1
1507.1
1512.7
1520.9
1505.4
1516.2
1542.6
1510.8
1508.4

Stray
Stray
Losses
Losses
@ room
@ 75 C
temp
Watt

Watt

Total
Total
% Imp
IR
losses @ @75
Losses
75 C
C
@ 75 C
Watt

85.42 79.93 1263.5


86.71 82.63 1294.7
90.85 88.45 1314.4
101.8 87.87 1280.7
110.5 100.87 1276.7
100.2 87.12 1277.9
108.45 92.45 1279.4
120.5 105.65 1289.7
104.44 90.41 1287.7
111.53 95.54 1289.4

Witnessed by,
For MSEDCL

Shri. V S Nirawar
Executive Engineer
Testing Divn , Nanded

Watt

1724.1
1718.4
1738.4
1718.6
1725.9
1713.6
1732.4
1709.8
1726.4
1723.4

Seal No

4.14
4.17
4.17
4.13
4.17
4.21
4.24
4.33
4.47
4.23

598051/52
598053/54
598055/56
598057/58
598059/60
598061/62
598063/64
598065/66
598067/68
598069/70

Tested By,
For Narsinha Engineering Works

Testing Engineer

Narsinha Engineering Works


TEST RESULTS OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
ROUTINE TEST REPORT OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
Date Of Testing 15/07/2013
Dated 8/7/2013
PO No
Verbal
Costomer Name:
Sr
No

T/F Sr No

LV
HV Resistance in Resista HV IR LV IR

nce In losses Losses

Avg

1
2
3
4
5
6
7
8
9
10

NEWN-11
NEWN-12
NEWN-13
NEWN-14
NEWN-15
NEWN-16
NEWN-17
NEWN-18
NEWN-19
NEWN-20

Room Temp
30
Place
Nanded

19.17
19.68
19.25
19.61
19.36
19.23
19.78
19.81
19.52
19.47

Per Phase

28.55
28.35
28.64
28.32
28.48
28.63
28.55
28.47
28.15
28.12

Total
IR
Losses

No Load No Load
'I'
Losses
Measured Measured

Avg

Watt

Watt

Watt

Amps

Watt

0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011

815.4
825.2
825.9
808.4
820.4
806.4
817.5
812.1
817.7
820.5

257.1
269.4
271.9
266.0
269.0
271.9
266.8
269.5
269.8
270.8

1072.6
1094.6
1097.8
1074.4
1089.4
1078.3
1084.3
1081.6
1087.4
1091.3

1.55
1.42
1.44
1.35
1.42
1.34
1.38
1.30
1.39
1.41

235.00
237.66
241.20
232.00
239.11
235.82
239.75
238.40
236.70
237.00

Vector Group Confirmation ( R r Shorted) : Found OK


Magnetic Balance Test : FOUND OK
DVDF induced over voltage 3 Ph 866 V of 100 Hz : Withstand for 1 min
Seprate Source Test: HV 28 Kv & LV 3 Kv withstand for 1 Min.
BDV: Oil Tested at 2.5 mm gap withstood at 60 KV
Insualtion Resistance : Above 2000 M at Ambient Temprature.
Ratio Test: Found OK

Full
Full Load losses Load
measured
Loss @
5.248 A
Amps

5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25

Watt

Watt

1510.1
1521.4
1504.6
1515.2
1535.6
1515.1
1516.7
1542.5
1520.1
1490.5

1520.4
1504.5
1511.5
1522.5
1540.5
1515.4
1516.2
1547.6
1504.1
1508.4

Stray
Stray
Losses
Losses
@ room
@ 75 C
temp
Watt

Watt

Total
Total
% Imp
IR
losses @ @75
Losses
75 C
C
@ 75 C
Watt

90.47
82.5 1279.9
102.5
95.4 1295.0
95.4 88.45 1310.1
101.8 97.45 1280.7
110.5 100.87 1276.7
100.2 92.41 1280.1
100.4 92.45 1279.4
95.77 89.01 1276.5
96.44 90.41 1290.7
88.78 80.79 1295.9

Witnessed by,
For MSEDCL

Shri. V S Nirawar
Executive Engineer
Testing Divn , Nanded

Watt

1720.1
1729.5
1718.0
1722.3
1728.4
1711.0
1735.1
1720.1
1717.1
1719.6

Seal No

4.14
4.17
4.24
4.13
4.35
4.21
4.24
4.35
4.47
4.17

598071/72
598073/74
598075/76
598077/78
598079/80
598081/82
598083/84
598085/86
598087/88
598089/90

Tested By,
For Narsinha Engineering Works

Testing Engineer

Narsinha Engineering Works


TEST RESULTS OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
ROUTINE TEST REPORT OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
Date Of Testing 20/07/2013
Dated 8/7/2013
PO No
Verbal
Costomer Name:
Sr
No

T/F Sr No

LV
HV Resistance in Resista HV IR LV IR

nce In losses Losses

Avg

1
2
3
4
5
6
7
8
9
10

NEWN-21
NEWN-22
NEWN-23
NEWN-24
NEWN-25
NEWN-26
NEWN-27
NEWN-28
NEWN-29
NEWN-30

Room Temp
30
Place
Nanded

19.23
19.78
19.17
19.61
19.36
19.23
19.78
19.17
19.61
19.36

Per Phase

28.23
28.55
28.35
28.32
28.40
28.41
28.62
28.39
28.21
28.18

Total
IR
Losses

No Load No Load
'I'
Losses
Measured Measured

Avg

Watt

Watt

Watt

Amps

Watt

0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011

806.2
809.4
818.2
803.3
801.6
805.3
803.3
809.4
799.7
810.6

257.2
268.7
271.2
265.1
272.0
274.1
265.4
262.6
263.3
268.7

1063.4
1078.0
1089.4
1068.4
1073.6
1079.4
1068.8
1072.0
1063.0
1079.3

1.48
1.42
1.52
1.35
1.36
1.39
1.43
1.36
1.39
1.42

243.54
238.55
233.00
236.51
239.41
237.65
239.75
240.44
242.11
233.55

Vector Group Confirmation ( R r Shorted) : Found OK


Magnetic Balance Test : FOUND OK
DVDF induced over voltage 3 Ph 866 V of 100 Hz : Withstand for 1 min
Seprate Source Test: HV 28 Kv & LV 3 Kv withstand for 1 Min.
BDV: Oil Tested at 2.5 mm gap withstood at 60 KV
Insualtion Resistance : Above 2000 M at Ambient Temprature.
Ratio Test: Found OK

Full
Full Load losses Load
measured
Loss @
5.248 A
Amps

5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25

Watt

Watt

1480.0
1483.0
1510.0
1497.0
1475.0
1481.0
1489.0
1496.0
1479.0
1505.0

1491.4
1497.6
1511.5
1510.1
1485.6
1482.4
1495.4
1496.5
1489.5
1508.4

Stray
Stray
Losses
Losses
@ room
@ 75 C
temp
Watt

90.47
95.52
92.44
100.4
97.5
89.55
91.44
93.55
92.14
101.2

Witnessed by,
For MSEDCL

Shri. V S Nirawar
Executive Engineer
Testing Divn , Nanded

Total
Total
% Imp
IR
losses @ @75
Losses
75 C
C
@ 75 C

Watt

Watt

82.50
90.10
88.45
95.45
91.55
87.55
88.90
90.50
89.41
95.66

1265.6
1285.9
1301.4
1291.3
1280.3
1275.7
1290.6
1274.6
1289.7
1279.3

Watt

1725.6
1720.3
1715.3
1718.0
1728.4
1721.6
1736.4
1740.3
1720.7
1716.3

Seal No

4.24
4.41
4.24
4.13
4.47
4.35
4.24
4.35
4.21
4.17

598091/92
598093/94
598095/96
598097/98
598099/100

600001/02
600003/04
600005/06
600007/08
600009/10

Tested By,
For Narsinha Engineering Works

Testing Engineer

Narsinha Engineering Works


TEST RESULTS OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
ROUTINE TEST REPORT OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
Room Temp
30
Place
Nanded

Date Of Testing 20/07/2013


PO No
Costomer Name:
Sr
No

1
2
3
4
5
6
7
8
9
10

T/F Sr No

NEWN-31
NEWN-32
NEWN-33
NEWN-34
NEWN-35
NEWN-36
NEWN-37
NEWN-38
NEWN-39
NEWN-40

LV
HV
HV Resistance in Resista
LV IR
IR

nce In
Losses
losses

Per
Avg
Avg
Watt
Watt
Phase

19.75
20.12
19.76
19.38
19.23
19.78
19.81
19.52
19.68
19.25

28.62
28.39
28.21
28.35
28.32
28.40
28.23
28.55
28.41
28.18

0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011

802.3
805.3
803.3
809.4
806.2
799.7
803.3
809.4
818.2
810.6

257.2
268.7
271.2
265.1
272.0
274.1
265.4
262.6
263.3
268.7

Total
IR
Losses

No Load
'I'
Measured

No Load
Losses
Measured

Watt

Amps

Watt

1063.4
1078.0
1089.4
1068.4
1074.3
1079.4
1068.8
1072.0
1063.0
1079.3

1.36
1.39
1.43
1.36
1.39
1.52
1.35
1.48
1.42
1.36

239.41
237.65
239.75
240.44
242.11
236.51
238.55
233.00
243.54
233.55

Vector Group Confirmation ( R r Shorted) : Found OK


Magnetic Balance Test : FOUND OK
DVDF induced over voltage 3 Ph 866 V of 100 Hz : Withstand for 1 min
Seprate Source Test: HV 28 Kv & LV 3 Kv withstand for 1 Min.
BDV: Oil Tested at 2.5 mm gap withstood at 60 KV
Insualtion Resistance : Above 2000 M at Ambient Temprature.
Ratio Test: Found OK

Full Load losses


measured
Amps

5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25

Full
Load
Loss @
5.248 A

Watt

Watt

1475.0
1481.0
1489.0
1496.0
1479.0
1480.0
1483.0
1510.0
1497.0
1499.0

1491.4
1497.6
1499.4
1507.9
1485.6
1482.4
1483.5
1515.4
1501.5
1508.4

Stray
Total
Stray
Total
Losses @
IR
Losses @
losses @
room
Losses
75 C
75 C
temp
@ 75 C
Watt

89.55
91.44
93.55
92.14
90.47
95.52
100.4
97.5
92.44
99.8

Witnessed by,
For MSEDCL

Shri. V S Nirawar
Executive Engineer
Testing Divn , Nanded

Watt

87.55
88.90
90.50
89.41
82.50
90.10
95.45
91.55
88.45
93.5

Watt

Watt

1291.3 1718.0
1280.3 1728.4
1275.7 1721.6
1290.6 1736.4
1286 1740.3
1301.4 1720.66
1265.6 1725.6
1289.7 1720.33
1279.3 1715.3
1274.6 1716.33

%
Imp
@75
C

Seal No

4.47
4.35
4.24
4.24
4.13
4.35
4.21
4.24
4.41
4.17

Tested By,
For Narsinha Engineering Works

Testing Engineer

Narsinha Engineering Works


TEST RESULTS OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
ROUTINE TEST REPORT OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
Room Temp
30
Place
Nanded

Date Of Testing 20.7.13


PO No
Costomer Name:
Sr
No

T/F Sr No

LV
HV
HV Resistance in Resista
IR

nce In
losses

Avg

1
2
3
4
5
6
7
8
9
10

NEWN-41
NEWN-42
NEWN-43
NEWN-44
NEWN-45
NEWN-46
NEWN-47
NEWN-48
NEWN-49
NEWN-50

19.50
19.75
19.70
19.41
19.35
19.80
19.78
19.62
19.65
19.38

Per
Phase

29.25
29.63
29.55
29.12
29.03
29.70
29.67
29.43
29.48
29.07

Avg

0.012
0.012
0.011
0.011
0.011
0.012
0.012
0.011
0.012
0.011

Watt

810
815
812
805
803
815
810
804
809
800

LV IR
Losses

Total
IR
Losses

No Load
'I'
Measured

No Load
Losses
Measured

Watt

Watt

Amps

Watt

257.2
268.7
271.2
265.1
272.0
274.1
265.4
262.6
263.3
268.7

1067.2
1083.7
1083.2
1070.1
1075.0
1089.1
1075.4
1066.6
1072.3
1068.7

0.947
0.925
0.892
1.00
0.998
0.908
0.980
0.948
1.035
0.982

242.80
244.80
238.70
241.50
243.60
244.80
242.60
238.60
240.80
242.50

Vector Group Confirmation ( R r Shorted) : Found OK


Magnetic Balance Test : FOUND OK
DVDF induced over voltage 3 Ph 866 V of 100 Hz : Withstand for 1 min
Seprate Source Test: HV 28 Kv & LV 3 Kv withstand for 1 Min.
BDV: Oil Tested at 2.5 mm gap withstood at 60 KV
Insualtion Resistance : Above 2000 M at Ambient Temprature.
Ratio Test: Found OK

Full Load losses


measured

Amps

5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25

Full
Load
Loss @
5.248 A

Stray
Total
Stray
Total
Losses @
IR
Losses @
losses @
room
Losses
75 C
75 C
temp
@ 75 C

Watt

Watt

Watt

1485.0
1490.0
1488.0
1475.0
1476.0
1480.0
1484.0
1482.0
1486.0
1489.0

1403
1385
1384
1346
1392
1362
1356
1384
1366
1370

90.15
95.12
94.26
93.35
92.6
91.78
95.42
96.35
94.12
97.62

Witnessed by,
For MSEDCL

Shri. V S Nirawar
Executive Engineer
Testing Divn , Nanded

Watt

88.15
93.12
92.26
91.35
90.60
89.78
93.42
94.30
92.12
95.62

Watt

1295
1285
1280
1293
1292
1305
1275
1285
1290
1285

%
Imp
@75
C

Watt

1722.6
1728.4
1726.1
1711.0
1712.2
1716.8
1721.4
1719.1
1723.8
1727.2

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

Seal No

600001-02
600003-04
600005-06
600007-08
600009-10
600011/12
600013/14
600015/16
600017/18
600019/20

Tested By,
For Narsinha Engineering Works

Testing Engineer

Narsinha Engineering Works


TEST RESULTS OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
ROUTINE TEST REPORT OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
Room Temp
30
Place
Nanded

Date Of Testing 20/7/13


PO No
Costomer Name:
Sr
No

T/F Sr No

LV
HV
HV Resistance in Resista
IR

nce In
losses

Avg

1
2
3
4
5
6
7
8
9
10

NEWN-51
NEWN-52
NEWN-53
NEWN-54
NEWN-55
NEWN-56
NEWN-57
NEWN-58
NEWN-59
NEWN-60

19.36
19.65
19.55
19.48
19.43
19.76
19.67
19.61
19.58
19.40

Per
Phase

29.04
29.48
29.33
29.22
29.15
29.64
29.51
29.42
29.37
29.10

LV IR
Losses

Total
IR
Losses

No Load
'I'
Measured

No Load
Losses
Measured

Avg

Watt

Watt

Watt

Amps

Watt

0.012
0.012
0.012
0.012
0.012
0.012
0.012
0.012
0.012
0.012

799.8
811.8
807.7
804.8
802.7
816.4
812.6
810.2
808.9
801.5

213.4
213.4
213.4
213.4
213.4
213.4
213.4
213.4
213.4
213.4

1013.2
1025.2
1021.0
1018.2
1016.1
1029.7
1026.0
1023.5
1022.3
1014.8

0.91
0.867
0.827
0.80
0.781
0.696
0.880
0.675
0.729
0.945

235.70
242.80
239.50
241.20
238.60
238.80
236.50
242.00
235.00
235.40

Vector Group Confirmation ( R r Shorted) : Found OK


Magnetic Balance Test : FOUND OK
DVDF induced over voltage 3 Ph 866 V of 100 Hz : Withstand for 1 min
Seprate Source Test: HV 28 Kv & LV 3 Kv withstand for 1 Min.
BDV: Oil Tested at 2.5 mm gap withstood at 60 KV
Insualtion Resistance : Above 2000 M at Ambient Temprature.
Ratio Test: Found OK

Full Load losses


measured

Amps

5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25

Full
Load
Loss @
5.248 A

Stray
Total
Stray
Total
Losses @
IR
Losses @
losses @
room
Losses
75 C
75 C
temp
@ 75 C

Watt

Watt

Watt

1490.0
1485.0
1469.0
1486.0
1487.0
1468.0
1479.0
1480.0
1472.0
1483.0

1455
1470
1450
1472
1471
1452
1463
1464
1455
1467

92.1
93.12
96.4
95.35
94.68
93.45
94.48
95.38
93.76
95.8

Witnessed by,
For MSEDCL

Shri. V S Nirawar
Executive Engineer
Testing Divn , Nanded

Watt

89.15
92.13
94.58
93.48
92.76
91.47
92.11
93.38
91.15
93.49

Watt

1175.3
1189.2
1184.4
1181.1
1178.7
1194.5
1190.2
1187.3
1185.8
1177.2

%
Imp
@75
C

Watt

1728.4
1722.6
1704.0
1723.8
1724.9
1702.9
1715.6
1716.8
1707.5
1720.3

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

Seal No

600021/22
600023/24
600025/26
600027/28
600029/30
600031-32
600033-34
600035-36
600037-38
600039-40

Tested By,
For Narsinha Engineering Works

Testing Engineer

Narsinha Engineering Works


TEST RESULTS OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
ROUTINE TEST REPORT OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
Date Of Testing 20/07/2013
PO No
Costomer Name:
Sr
No

T/F Sr No

LV
HV Resistance in Resista HV IR LV IR

nce In losses Losses

Avg

1
2
3
4
5
6
7
8
9
10

NEWN-61
NEWN-62
NEWN-63
NEWN-64
NEWN-65
NEWN-66
NEWN-67
NEWN-68
NEWN-69
NEWN-70

Room Temp
30
Place
Nanded

19.45
19.75
20.12
19.76
19.38
20.11
19.78
19.81
19.42
19.32

Per Phase

28.68
28.65
28.64
28.32
28.52
28.63
28.45
28.75
28.62
28.12

Total
IR
Losses

No Load No Load
'I'
Losses
Measured Measured

Avg

Watt

Watt

Watt

Amps

Watt

0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011
0.011

804.5
818.2
831.1
810.5
815.4
806.4
817.5
811.4
813.7
825.3

257.1
269.4
271.9
266.0
269.0
271.9
266.8
269.5
269.8
270.8

1061.6
1087.6
1103.0
1076.5
1084.4
1078.3
1084.3
1080.9
1083.5
1096.1

1.55
1.42
1.45
1.41
1.42
1.34
1.38
1.43
1.39
1.40

242.50
238.00
240.20
237.70
238.00
235.00
236.40
238.40
236.70
237.00

Vector Group Confirmation ( R r Shorted) : Found OK


Magnetic Balance Test : FOUND OK
DVDF induced over voltage 3 Ph 866 V of 100 Hz : Withstand for 1 min
Seprate Source Test: HV 28 Kv & LV 3 Kv withstand for 1 Min.
BDV: Oil Tested at 2.5 mm gap withstood at 60 KV
Insualtion Resistance : Above 2000 M at Ambient Temprature.
Ratio Test: Found OK

Full
Full Load losses Load
measured
Loss @
5.248 A
Amps

5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25

Watt

Watt

1460.8
1480.6
1507.9
1510.5
1535.6
1498.5
1516.7
1542.5
1506.4
1490.5

1475.6
1497.1
1507.1
1512.7
1520.9
1505.4
1516.2
1542.6
1510.8
1508.4

Stray
Stray
Losses
Losses
@ room
@ 75 C
temp
Watt

Watt

Total
Total
% Imp
IR
losses @ @75
Losses
75 C
C
@ 75 C
Watt

85.42 79.93 1263.5


86.71 82.63 1294.7
90.85 88.45 1314.4
101.8 87.87 1280.7
110.5 100.87 1276.7
100.2 87.12 1277.9
108.45 92.45 1279.4
120.5 105.65 1289.7
104.44 90.41 1287.7
111.53 95.54 1289.4

Witnessed by,
For MSEDCL

Shri. V S Nirawar
Executive Engineer
Testing Divn , Nanded

Watt

1724.1
1718.4
1738.4
1718.6
1725.9
1713.6
1732.4
1709.8
1726.4
1723.4

Seal No

4.14
4.17
4.17
4.13
4.17
4.21
4.24
4.33
4.47
4.23

600041-42
600043-44
600045-46
600047-48
600049-50
598651-52
598653-54
598655-56
598658-59
598660-61

Tested By,
For Narsinha Engineering Works

Testing Engineer

Narsinha Engineering Works


TEST RESULTS OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
ROUTINE TEST REPORT OF 100 KVA, 11/0.433 KV DISTRIBUTION CONVENTIONAL TRANSFORMERS
Room Temp
30
Place
Nanded

Date Of Testing 20/07/2013


PO No
Costomer Name:
Sr
No

1
2
3
4
5

T/F Sr No

NEWN-71
NEWN-72
NEWN-73
NEWN-74
NEWN-75

LV
HV
HV Resistance in Resista
LV IR
IR

nce In
Losses
losses

Per
Avg
Avg
Watt
Watt
Phase

19.75
20.12
19.76
19.38
19.23

28.62
28.39
28.21
28.35
28.32

0.011
0.011
0.011
0.011
0.011

802.3
805.3
803.3
809.4
806.2

257.2
268.7
271.2
265.1
272.0

Total
IR
Losses

No Load
'I'
Measured

No Load
Losses
Measured

Watt

Amps

Watt

1063.4
1065.5
1070.4
1072.6
1074.3

1.36
1.39
1.43
1.36
1.39

239.41
237.65
239.75
240.44
242.11

Vector Group Confirmation ( R r Shorted) : Found OK


Magnetic Balance Test : FOUND OK
DVDF induced over voltage 3 Ph 866 V of 100 Hz : Withstand for 1 min
Seprate Source Test: HV 28 Kv & LV 3 Kv withstand for 1 Min.
BDV: Oil Tested at 2.5 mm gap withstood at 60 KV
Insualtion Resistance : Above 2000 M at Ambient Temprature.
Ratio Test: Found OK

Full Load losses


measured
Amps

5.25
5.25
5.25
5.25
5.25

Full
Load
Loss @
5.248 A

Watt

Watt

1475.0
1481.0
1489.0
1496.0
1479.0

1491.4
1497.6
1499.4
1507.9
1485.6

Stray
Total
Stray
Total
Losses @
IR
Losses @
losses @
room
Losses
75 C
75 C
temp
@ 75 C
Watt

89.55
91.44
93.55
92.14
90.47

Witnessed by,
For MSEDCL

Shri. V S Nirawar
Executive Engineer
Testing Divn , Nanded

Watt

87.55
88.90
90.50
89.41
82.50

Watt

1291.3
1280.3
1275.7
1290.6
1286

%
Imp
@75
C

Watt

1718.0
1728.4
1721.6
1736.4
1740.3

4.47
4.35
4.24
4.24
4.13

Seal No

598662-63
598664-65
598666-67
598668-69
598670-71

Tested By,
For Narsinha Engineering Works

Testing Engineer