DOCWin 2.1
Curva Tempo-Corrente FFF 1E4s

Curva Energia specifica passante FFF 100MAs

1E3s

10MAs

100s

1MAs
10s

0.1MAs
1s

0.1s

1E-2MAs

1E-2s

1E-3MAs

0.1kA

1kA

10kA

0.1kA

1kA

10kA

ABB SACE - 1 01 - 11 - 21

Agenda

General features: what does DOCWin 2.1 calculate

Working with DOCWin 2.1: the ideal working sequence


ABB SACE - 2

Installation: system requirements and installation procedure Learning: instruments to learn DOCWin 2.1 Assistance: how to contact ABB SACE

General features

What does DOCWin 2.1 calculate

ABB SACE - 3

General features

Network without limitations

Unlimited number of nodes MV/LV networks Radial and meshed networks Several distribution systems

ABB SACE - 4

General features

Load-flow

Its possible to size all objects according to the the power of the transformer or (without flag) according to the load

ABB SACE - 5

General features

Configurations

You can create different configuration in one single projects Breakers can be set ON and OFF in each configuration.

Calculations can be done in actual configuration or in all...

ABB SACE - 6

General features

Configuration creation

Unlimited number of possible configurations Manual switch between configurations

ABB SACE - 7

General features

Load-flow

Its also possible to consider loads at constant current: a way much closer to designer habits

ABB SACE - 8

General features

Load-flow

Automatic phase balancing

In case of single phaseloads, DOC can select phase in order to optimize phase balancing
ABB SACE - 9

General features

Power factor correction

When sizing Utilities and busbars its possible to calculate the capacitor power

ABB SACE - 10

General features

Network calculations
voltage and load current in every point of the network

Load-flow:

Short circuit: maximum and minimum Ik in every point of the network

ABB SACE - 11

General features

Automatic dimensioning

Transformers Cables Busway trunking systems

Protection relation

Switchgear and protection devices


Circuit breakers Fuses Switch disconnectors

Co-ordination relations

ABB SACE - 12

Residual current circuit breakers

General features

User friendly

Checking and warning of the faulty situations


(to avoid to search for the problems already known by the program)

Electrical machines database


(to have all the parameters of generators, motors and trafos)

Prototypes and blocks saving


(to avoid to redo the same job)


ABB SACE - 13

Dimensioning / choice of one object only


(like the old DOC )

General features

Complete documentation

All the data are printable in DOCWin 2.1 native format


Single-line diagram with customized labels - customizables Report of each single object Curves diagrams and settings - customizables

All the data are exportable in the most common data exchange formats

ABB SACE - 14

Export of single-line diagram in DWG/DXF format Export of reports in RTF and PDFformat Export of curves in WMF format

Working with DOCWin 2.1

The ideal working sequence

ABB SACE - 15

Working with DOCWin 2.1

ABB solution for electrical plants

Project

CAD Program
Network drawing
Database ABB
Non competitors Database (Zucchini) User database

Network calculations ( SC, Load-Flow )


Sizing of cables, busways, transformers
ABB SACE - 16

Protective devices selection

Codes list

Working with DOCWin 2.1

Single-line diagrams drawing


Single-line diagram drawing

It is enough to select the object within the toolbar and position it in the diagram

ABB SACE - 17

Working with DOCWin 2.1

Power supply

Single-line diagram drawing

Supply Generator Two windings transformer Three windings transformer

ABB SACE - 18

Working with DOCWin 2.1

Objetcs

Single-line diagram drawing

Impedance Cable Busway

Busbar

ABB SACE - 19

Working with DOCWin 2.1

LV cable

Special window... Cable selection Method of installation

ABB SACE - 20

Working with DOCWin 2.1

LV cable (advanced settings)


Its possible to modify R and X when you know theyre different form the default ones Its possible to enalble only some selected cross sections

ABB SACE - 21

Working with DOCWin 2.1

Protection devices

Single-line diagram drawing

Circuit-breaker Residual current circuit - breaker Fuse

ABB SACE - 22

Working with DOCWin 2.1

Circuit breakers

Filtered or free selection Co-ordination Protection Pre-definition of:


Type Execution Release Idn

ABB SACE - 23

Working with DOCWin 2.1

Single-line diagrams drawing


Single-line diagram drawing

Switch disconnector Contactor

ABB SACE - 24

Working with DOCWin 2.1

Single-line diagrams drawing


Single-line diagram drawing

Generic load Motor Light load Multibranch cable Distribution busway Power factor correction group

ABB SACE - 25

-L1

Working with DOCWin 2.1

Generic load

All necessary informations are in the same window All possibilities: -by apparent power and pf -by active/reactive power -by current and pf -by active power and pf

ABB SACE - 26

Working with DOCWin 2.1

Motors

Single-line diagram drawing

Motor

ABB SACE - 27

Working with DOCWin 2.1

Motors

Single-line diagram drawing

Motor

ABB motors database

(from 0.18 to 710 kW )

ABB SACE - 28

Working with DOCWin 2.1

Motors

Single-line diagram drawing

Motor

Starter co-ordination and protection

ABB SACE - 29

Working with DOCWin 2.1

Motors

ABB SACE - 30

Different symbols for relevant type of protection

Working with DOCWin 2.1

Light load

You can define:


Lamp type/technology Power Number of lamps Distances

Doc sizes the cable

ABB SACE - 31

Working with DOCWin 2.1

Multimeter

All network calculations available in every point of the installation

ABB SACE - 32

Working with DOCWin 2.1

Single-line diagrams drawing


Single-line diagram drawing

Connection Line departure Line arrival

ABB SACE - 33

Working with DOCWin 2.1

Data input

Single-line diagram drawing

Data input

DOCWin 2.1 helps the user during the data input ...

... showing the default values stored in the prototype ... with the databases of the electrical machines ... with a customized dialog window for each object ... by asking for the missing data during the automatic dimensioning


ABB SACE - 34

Working with DOCWin 2.1

Network congruity

Single-line diagram drawing

Data input
Network congruity Automatic dimensioning

DOCWin 2.1 verifies the congruity of the network and signals every anomalous situation

ABB SACE - 35

Working with DOCWin 2.1

Load - Flow

Single-line diagram drawing

Data input
Network congruity Automatic dimensioning

DOCWin 2.1 calculates the load current for each object and the voltage level at each node using the Newton-Raphson method

Load- Flow

ABB SACE - 36

Working with DOCWin 2.1

Cable sizing

Single-line diagram drawing

Data input
Network congruity Automatic dimensioning

DOCWin 2.1 sizes and checks the cables in compliance with the following Standards: IEC 60364-5-23

Load- Flow
Cables, busways, trafos sizing

VDE 298-4 NFC 15-100 CEI 64-8

IEC 60890 (PTTA switchboards) IEC 60092 (for ship)

ABB SACE - 37

Working with DOCWin 2.1

Short-circuit

Single-line diagram drawing

Data input
Network congruity Automatic dimensioning

DOCWin 2.1 calculates the maximum and minimum short-circuit currents for LLL, LL, LN, L-PE in compliance with:
IEC 60909-1

Load- Flow
Cables, busways, trafos sizing Short-circuit

IEC 61363-1 (for ship)

Symmetrical component method

ABB SACE - 38

Working with DOCWin 2.1

Devices selection

Single-line diagram drawing

Data input
Network congruity Automatic dimensioning

DOCWin selects circuit-breakers and fuses taking in account the protection of cables, busways, switch disconnectors and residual current circuit breakers

Load- Flow
Cables, busways, trafos sizing Short-circuit Devices selection

Note:
Restrictions do not always allow a solution !

ABB SACE - 39

- Long discrimination or back-up chains - Protection against indirect contacts with wrong function - Ib too close to Iz of the protected cable - wrong Standard selection - ...

Working with DOCWin 2.1

Devices selection

Single-line diagram drawing

Data input
Network congruity Automatic dimensioning

DOCWin selects circuit-breakers taking in account discrimination and back-up relations between breakers

Load- Flow
Cables, busways, trafos sizing Short-circuit Devices selection

Note:

Tables used by DOCWin are valid up to 436V Computation time is function of the number of linked breakers and growths like a factorial funtion

ABB SACE - 40

Working with DOCWin 2.1

Manual refinement

Single-line diagram drawing

Data input
Network congruity Automatic dimensioning

The user shall check the solution proposed by DOCWin 2.1 to optimize it. In particular, the user can ...

Load- Flow
Cables, busways, trafos sizing Short-circuit Devices selection

... Select manually the objects ... Oversize the cables and the busways ... Select the tapping of the transformers ... Lock the manually choosen objects ... Set the relays

Manual refinement


ABB SACE - 41

Working with DOCWin 2.1

Drawing curves

Single-line diagram drawing

Time-current curves Specific let-through energy curves Limitation curves


Curva Picco Curva Curva Energia specifica passante Tempo-Corrente LLL LLL 1E3kA 1E4s 1E4MAs 1E3s

Data input
Network congruity Automatic dimensioning

Load- Flow
Cables, busways, trafos sizing Short-circuit Devices selection

1E3MAs 100s 100kA

10s 100MAs 1s 10MAs 10kA 0.1s


1MAs

Manual refinement Drawing curves


ABB SACE - 42

1E-2s
0.1MAs 0.1kA 1kA10kA 0.1kA 10kA 1kA 100kA 100kA 10kA

Working with DOCWin 2.1

Documentation printouts

Single-line diagram drawing

Single-line diagram Report Curves Settings


Curva Tempo-Corrente FFF 1E4s

Data input
Network congruity Automatic dimensioning

Load- Flow
Cables, busways, trafos sizing Short-circuit Devices selection

Reference voltage=400 V 1E3s Electronic rele: -QF1 S6X 400 PR212-LSI R400 L: Setting: 0.67 Curva: 18 100s S It=cost Setting: 9.5 Curva: 0.35 I Setting: 12 10s TM Rele: 1s LT: INST:
0.1s

Manual refinement Drawing curves


ABB SACE - 43

-QF2 T3N 250 R250 Setting: 212.499 [A] Preload: 202.272 [A] Setting: 2500 [A]

Documentation printouts

1E-2s

0.1kA

1kA

10kA

Working with DOCWin 2.1

Data export

Single-line diagram drawing

Data input

Network congruity Automatic dimensioning

DOCWin 2.1 can export data of ABB SACE products ...


Load- Flow
Cables, busways, trafos sizing Short-circuit Devices selection

... to CATs for the selection of the accessories ... to DMB for the switchboard configuration, for the budgedting or for the detailed drawing of the single-line diagram

Manual refinement Drawing curves


ABB SACE - 44

Documentation printouts

Data export

Working with DOCWin 2.1

Data export
Single-line diagram drawing

Data input
Network congruity Automatic dimensioning

Load- Flow
Cables, busways, trafos sizing Short-circuit Devices selection

Manual refinement Drawing curves


ABB SACE - 45

Documentation printouts

Data export

Learning

Instruments to learn DOCWin 2.1

ABB SACE - 46

Learning

User manual

ABB SACE - 47

Learning

Video course

ABB SACE - 48

Italian or english only !

Installation

System requirements and installation procedure

ABB SACE - 49

Installation

System requirements

OS from Win95 to Win2000 Unlimited number of installations Administrator privileges required At least 60 Mb of hard disk space Be sure no other application (anti-virus program) are running during the installation !!!!!


ABB SACE - 50

Installation

Installation procedure

Double-click Start.exe

ABB SACE - 51

Assistance

How to contact ABB SACE

ABB SACE - 52

Assistance

Call center


claudio.brazzola@it.abb.com claudio.bizzo@it.abb.com E-mail is the best way to communicate efficiently with the working group

Precise explanations of the problem and an example file attached to the e-mail help us to solve the problem

ABB SACE - 53

Assistance

http:\\bol.it.abb.com

to ask for a free version of the program to be informed about the news

http:\\bol.it.abb.com Now avalaible the english version


ABB SACE - 54

ABB SACE - 55

You might also like