You are on page 1of 36

OPERATIoN AND INSTALLATIoN

AIR | WATER HEAT PUMP

WPL 10 AC WPL 10 ACS

CONTENTs | OpERaTION  GENERal INFORmaTION


OPERATIoN__________________________________________________________2 1. 1.1 1.2 1.3 1.4 2. 2.1 2.2 2.3 3. 3.1 3.2 4. 5. 6. 6.1 7. 7.1 7.2 8. 8.1 8.2 9. 9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 10. 10.1 10.2 10.3 10.4 10.5 10.6 10.7 10.8 10.9 11. 11.1 11.2 11.3 11.4 12. General information_________________________________________2 Further applicable documents________________________________ 2 Safety instructions_______________________________________________ 2 Other symbols in this documentation_______________________ 3 Units of measurement__________________________________________ 3 Safety__________________________________________________________3 Intended use______________________________________________________ 3 Safety instructions_______________________________________________ 3 CE designation___________________________________________________ 3 Equipment description______________________________________4 Properties_________________________________________________________ 4 Function___________________________________________________________ 4 Settings _______________________________________________________4 Maintenance and care_______________________________________4 Troubleshooting______________________________________________4 Other problems__________________________________________________ 4 Safety__________________________________________________________5 General safety instructions____________________________________ 5 Instructions, standards and regulations____________________ 5 Equipment description______________________________________5 Standard delivery________________________________________________ 5 Accessories________________________________________________________ 5 Preparations__________________________________________________6 Acoustic emissions______________________________________________ 6 Mindestabstnde________________________________________________ 6 Preparation of the installation location_____________________ 6 Handling___________________________________________________________ 7 Positioning________________________________________________________ 7 Heat pump manager WPM II__________________________________ 8 Buffer cylinder___________________________________________________ 8 Preparing the electrical installation_________________________ 8 Mounting______________________________________________________9 Positioning________________________________________________________ 9 Heating water connection_____________________________________ 10 Flow and return connection__________________________________ 10 Oxygen diffusion________________________________________________ 10 Filling the heating system____________________________________ 10 Minimum ow rate_____________________________________________ 10 Condensate drain_______________________________________________ 11 External heat source 2_________________________________________ 11 Power supply____________________________________________________ 11 Commissioning_____________________________________________ 15 Checks before commissioning_______________________________ 15 Commissioning__________________________________________________ 17 Operation and control _________________________________________ 17 Taking the appliance out of use______________________________ 17 Maintenance________________________________________________ 18 13.2 Reset button_____________________________________________________ 19 13.3 Resetting the high limit safety cut-out_____________________ 19 14. 14.1 14.2 14.3 14.4 14.5 14.6 14.7 14.8 15. Specication________________________________________________ 20 Wiring diagram WPL 10 AC (three-phase)_________________ 20 Wiring diagram WPL 10 ACS (single phase)_______________ 22 Output diagrams, heating WPL 10 AC______________________ 24 Output diagrams, cooling WPL 10 AC_______________________ 25 Output diagrams, heating WPL 10 ACS_____________________ 26 Output diagrams, cooling WPL 10 ACS_____________________ 27 Data table________________________________________________________ 28 Dimensions_______________________________________________________ 29 Commissioning report_____________________________________ 30

WARRANTY ENVIRoNMENT AND RECYCLING_________________________________ 31

INSTALLATIoN_______________________________________________________5

OpERaTION
1. General information
The chapter Operation is intended for appliance users and heating contractors. The chapter Installation is intended for heating contractors.

Note Read these instructions carefully before using the appliance and retain them for future reference. Pass on the instructions to a new user if required.

1.1 Further applicable documents


Note Please observe the operating and installation instructions of system components.

1.2 Safety instructions


1.2.1 Layout of safety instructions

KEYWORD Type of risk Here, possible consequences are listed that may result from failure to observe the safety instructions. ff Steps to prevent the risk are listed.

13. Troubleshooting____________________________________________ 19 13.1 Light Emitting Diodes (LED)___________________________________ 19 2 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

OpERaTION  SaFETY
1.2.2 Symbols, type of risk
Symbol Type of risk Injury

2. Safety
2.1 Intended use
The appliance is designed for the following purposes: -- For central heating -- For central cooling -- For DHW heating Observe the operating limits listed in chapter Specication. This appliance is designed for domestic use. It can be used safely by untrained persons. The appliance can also be used in a nondomestic environment, e.g. in a small business, as long as it is used in the same way. Any other use beyond that described shall be deemed inappropriate. Observation of these instructions and of instructions for any accessories used is also part of the correct use of this appliance. Any changes or conversions to the appliance void any warranty. ENGLISH

Electrocution

1.2.3 Keywords
KEYWORD DANGER WARNING CAUTION Meaning Failure to observe this information will result in serious injury or death. Failure to observe this information may result in serious injury or death. Failure to observe this information may result in nonserious or minor injury.

1.3 Other symbols in this documentation

2.2 Safety instructions


Observe the following safety instructions and regulations. -- The electrical installation and installation of the heating circuit must only be carried out by a qualied contractor or by our customer service engineers. -- Contractors are responsible for adherence to all currently applicable regulations during installation and commissioning. -- Operate the appliance only when fully installed and with all safety equipment tted. -- Protect the appliance from dust and dirt ingress during building work.


Symbol

Note Notes are bordered by horizontal lines above and below the text. General information is identied by the symbol shown on the left. ff Read these texts carefully.

Damage to the appliance and environment Appliance disposal Never cover the appliance

ff This symbol indicates that you have to do something. The action you need to take is described step by step.

WARNING Injury The appliance may be used by children aged 8 and up and persons with reduced physical, sensory or mental capabilities or a lack of experience provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the resulting risks. Children must never play with the appliance. Children must never clean the appliance or perform user maintenance unless they are supervised.

1.4 Units of measurement

Note All measurements are given in mm unless stated otherwise.

2.3 CE designation
The CE designation shows that the appliance meets all essential requirements according to the: -- Electromagnetic Compatibility Directive -- Low Voltage Directive

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 3

OpERaTION  EQUIpmENT dEscRIpTION 3. Equipment description


3.1 Properties
The appliance is an air source heat pump for external installation that is designed to provide central heating. Heat is extracted from the outside air at a low temperature level, and is then transferred to the heating water at a higher level. The heating water can be heated up to a ow temperature of 60 C. The refrigerant circuit is reversed for cooling operation. The appliance is equipped with an electric emergency/booster heater (DHC). In mono mode, the electric emergency/booster heater is activated when the dual mode point can no longer be maintained, in order to safeguard heating operation and to provide high DHW temperatures. In such cases, the electric emergency/booster heater is activated in mono energetic operation as a booster heater. This appliance has further operational characteristics: -- Suitable for underoor and radiator heating. -- Preferred for low temperature heating systems. -- Still extracts heat from the outside air at -20 C outside temperature. -- Corrosion-protected, external casing made from galvanised sheet steel plus stove-enamelled nish. -- Comprises all components required for operation and all safety equipment. -- Filled with non-combustible safety refrigerant. -- Suitable for cooling through extraction of heat from the heating system.

Damage to the appliance and the environment In the defrost cycle, the fan is switched off and the heat pump circuit is reversed. The heat required for defrosting is drawn from the buffer cylinder. For operation without a buffer cylinder, the general conditions dened in the chapter Installation without buffer cylinder must be adhered to. Otherwise the heating water freezes under unfavourable conditions.

The heat pump automatically reverts to heating mode at the end of the defrost cycle.

Damage to the appliance and the environment In dual mode operation, the return water of the second heat source can ow through the heat pump. Please note that the return temperature must be no higher than 60 C.

4. Settings
The system is operated exclusively with the heat pump manager (WPM II). ff Observe the heat pump manager operating and installation instructions.

5. Maintenance and care


!

Damage to the appliance and the environment Maintenance work, such as checking the electrical safety, must only be carried out by a qualied contractor.

Note For centralised control over the entire heating system, you would need the WPM II heat pump manager.

A damp cloth is sufcient for cleaning all plastic and sheet steel parts. Never use abrasive or corrosive cleaning agents. Check the condensate drain monthly (visual inspection). Remove contaminants and blockages immediately (see chapter Positioning).

3.2 Function
Heat is extracted from the outdoor air via the heat exchanger (evaporator) on the air side. The evaporated refrigerant is compressed by a compressor. Electrical energy is necessary for this process. At this point, the refrigerant is at a higher temperature level. A further heat exchanger (condenser) transfers the heat to the heating circuit. During this process, the refrigerant expands again, and the cycle begins again. During cooling mode, the condenser becomes the evaporator and the evaporator becomes the condenser. The cycle is reversed. This enables heat to be transferred from the internal rooms to the outdoor air. At air temperatures below approx. +7 C, the humidity in the air condenses as hoarfrost on the evaporator ns. Any hoarfrost is automatically defrosted. Water created by this process collects in the defrost pan and is drained off via a hose.

Damage to the appliance and the environment Keep the air discharge and intake apertures free from snow and leaves.

We recommend an annual inspection (establishing the actual state) and, if required, maintenance (returning the set state) by a specialist contractor.

6. Troubleshooting
Fault There is no hot water or the heating system stays cold. Water collects below the appliance. Cause Remedy The fuse/MCB has blown/ Check the fuse/MCB in has responded. your fuse box/distribution panel. The condensate drain Call an authorised conmay be blocked. tractor to have the condensate drain cleaned out.

6.1 Other problems


If you cannot remedy the fault, notify your heating contractor. To facilitate and speed up your enquiry, please provide the serial 4 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

INsTallaTION  SaFETY
number from the type plate. The type plate is located on the front at the top on the right or left hand side of the casing. Sample type plate

7. Safety
1

7.1 General safety instructions


-- Only a qualied contractor should carry out installation, commissioning, maintenance and repair of the appliance. -- We guarantee trouble-free operation and operational reliability only if the original accessories and spare parts intended for the appliance are used.

26_03_01_1570

7.2 Instructions, standards and regulations

Montageanweisung beachten! Dichtheit geprft!

Made in Germany

1 Number on the type plate

Note Observe all applicable national and regional regulations and instructions.

8. Equipment description
The appliance protects the heating water lines against freezing up. The integral frost protection circuit starts the circulation pump in the heat pump circuit automatically at a condenser temperature of 8 C, and thereby ensures circulation in all water-carrying sections. If the temperature inside the buffer cylinder drops, the heat pump starts automatically no later than when the temperature falls below +5 C.

8.1 Standard delivery


Delivered with the appliance: -- Wiring diagram -- Condensate drain hose

8.2 Accessories
8.2.1 Required accessories
Description Heat pump manager with wall mounting casing, WPMW II Part no. 185450

8.2.2 Further accessories


Description Wall mounting support WK-WPL T-support SK-WPL Mounting bracket MK-WPL 10 AC(S) Hydraulic module HSBB 10 ACS Pressure hoses DN 25 Remote control for heating systems FEK Remote control for heating systems FE7 Part no. 231101 230865 232129 227996 220193 185579

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 5

ENGLISH

INsTallaTION

*xxxxxxxxxxxxxxxxxx*

INsTallaTION  PREpaRaTIONs 9. Preparations


The appliance is designed for siting in front of a wall. If the appliance is installed in an open space or on a roof, protect the air intake side by erecting a wall to shield it against the wind. Observe the minimum clearances

9.2 Mindestabstnde
800 200

9.1 Acoustic emissions


On the air intake and air discharge sides, the appliance is louder than on the enclosed sides. Please therefore observe the information below. For the sound power level, see chapter Specication/Data table. ff Ensure that the air intake direction is the same as the main wind direction. Air should not be drawn in against the wind. ff Never direct the air intake or discharge towards noise sensitive rooms of the house (e.g. bedrooms). Lawn areas and shrubs contribute to the reduction of noise. For this, observe the minimum clearances in the following gure: Noise can also be reduced through dense palisades if these are installed around the appliance. Observe the minimum clearances.
2000
D0000022153 91_00_00_0036

1000

500

ff Do not install the appliance in a recess. Two sides of the appliance must remain exposed. ff Avoid installation on large, echoing oor areas (e.g. those covered with tiles). ff Avoid installation between reective building walls. Reecting building walls can increase the sound level.

9.3 Preparation of the installation location


The substrate must be horizontal, level, solid and permanent. ff Ensure that the appliance is accessible from all sides.

6 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

INsTallaTION  PREpaRaTIONs
9.4 Handling
-- You can hook lifting straps to move the appliance at the area highlighted in grey at the bottom of the support frame. Example: T-support SK-WPL ENGLISH
5 B 2 8
26_03_01_1548

A 3 4 6

Damage to the appliance and the environment

Protect the appliance against heavy impact during transport.

Only allow the appliance to be tilted during transport for a short time to one of its longitudinal sides. The longer the appliance is tilted, the greater the distribution of refrigerant in the system. Wait approx. 30 minutes before starting the appliance after it has been tilted.

9.5 Positioning
ff Observe chapter Sound emissions. ff Observe the clearance dimension in the following diagram when using a wall mounting support.

A Frost level B 300 1 Heating circuit ow 2 Heating circuit return 3 Conduit for supply lines 4 Foundation 5 T-support 6 Gravel bed 7 Drainage pipe 8 Condensate hose ff Observe the static limits of the T-support used. Example: Wall mounting support WK-WPL

200

5 3
26_03_01_1683_

1
D0000019244

890

ff Only use weather-resistant cables. ff Protect the ow and return pipes against frost with sufcient thermal insulation. Provide thermal insulation in accordance with applicable regulations. ff Also protect all supply lines/cables against humidity, damage and UV radiation by means of a conduit.

1 Heating circuit ow 2 Heating circuit return 3 Condensate hose 4 Drainage pipe 5 Wall mounting bracket ff Observe the static limits of the building wall and the wall mounting supports.

Note When routing the condensate hose, observe chapter Installation / condensate drain.

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 7

D0000019236

INsTallaTION  PREpaRaTIONs
Example: Foundation slab
3 525 120 265
b01 e02 e01

9.6 Heat pump manager WPM II


1 1350

A WPMII heat pump manager is required to operate the appliance. This controls the entire heating system.

9.7 Buffer cylinder


A buffer cylinder is recommended to ensure a trouble-free appliance operation. The buffer cylinder (SBP) not only provides hydraulic separation of the volume ow in the heat pump and heating circuit, but also serves as an energy source for defrosting the evaporator. In this connection, read chapter Minimum ow rate.

4 80 5

635

110

610 2
D0000034844

Damage to the appliance and the environment The cooling operation will always require the SBP...cool buffer cylinder plus a diffusion-proof insulation of the pipework!

b01 Entry electrical cables from below e01 Heating circuit ow e02 Heating circuit return 1 Air intake side 2 Air discharge side 3 Main wind direction 4 Condensate hose 5 Outlet for supply lines

9.8 Preparing the electrical installation


WARNING Risk of electrocution! Carry out all electrical connection and installation work in accordance with national and regional regulations.

WARNING Risk of electrocution! Only use a permanent connection to the power supply. The appliance must be able to be separated from the power supply by an isolator that disconnects all poles with at least 3mm contact separation. This requirement can be met by contactors, isolators, fuses etc. Damage to the appliance and the environment The specied voltage must match the mains voltage. Observe the type plate.

4 9 70-80

5 2 8 1

2 A 1 3

!
7
D0000024451

Damage to the appliance and the environment Provide separate fuses for the 3 power circuits (for the appliance, the electric emergency/booster heater and the control unit).

A Frost level 1 Heating circuit ow 2 Heating circuit return 3 Conduit for supply lines 4 Foundation 5 Mounting bracket MK-WPL 10 AC(S) 6 Gravel bed 7 Drainage pipe 8 Condensate hose 9 Outlet for supply lines opt.

ff Route cables with the following cross-sections in accordance with the respective fuse rating: ff Always connect L for the heat pump and the control unit to the same phase.

8 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

INsTallaTION  MOUNTINg
Fuse protec- Assignment tion C 25 A Heat pump (single phase) C 16 A Heat pump (3-phase) C 35 A Electric emergency/booster heater (DHC) (single phase) C 16 A Electric emergency/booster heater (DHC) (3-phase) C 16 A Control Cable cross-section 2.5 mm for routing above the surface 4.0 mm for routing through a wall 2.5 mm 6.0 mm for routing through a wall 4.0 mm when routing multi-core cables on a wall or in an electrical conduit on a wall 2.5 mm 1.5 mm with only two live cores and routing on a wall or in an electrical conduit on a wall. 1.5 mm

The electrical data is given in the Specication chapter. You require a J-Y (St) 2x2x0.8mm cable as BUS cable.

10. Mounting
10.1 Positioning
ff When installing the appliance, observe the air intake direction. ff Position the standard unit on the prepared substrate.

ff Remove the transport locks (threaded rods) from the compressor.

ff Remove the cover.

26_03_01_1544

1 Sound insulation ff Position the cover on the appliance. ff Secure the cover with the four screws.

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 9

26_03_01_1759

26_03_01_1550

ENGLISH

INsTallaTION  MOUNTINg
10.2 Heating water connection
The heat pump heating system must be installed by a qualied contractor in accordance with the water installation drawings that are part of the technical documents. ff Thoroughly ush the pipework before connecting the heat pump. Foreign matter, such as welding pearls, rust, sand or sealant will impair the operational reliability of the heat pump and can result in the heat pump condenser becoming blocked.

10.5 Filling the heating system


10.5.1 Water quality In order to prevent damage caused by scale formation, you must observe the following when lling the system with heating water: The total water hardness must be <1dH(0.18 mmol/l alkaline earths). If the above conditions cannot be met, the water must be softened.

10.3 Flow and return connection

Damage to the appliance and the environment Insulate the heating ow and return lines with vapour diffusion-proof material.

Fit an anti-vibration mount at least 1 m long to the connectors. Structure-borne noise is substantially prevented by the anti-vibration construction of the heat pump and by the exible pressure hoses, which act as anti-vibration mounts. ff Take the position of the heating ow and return from the following gure:

Damage to the appliance and the environment Fully desalinated water or rainwater must not be used, as this leads to heavier corrosion. Suitable appliances for softening, as well as the lling and ushing of heating systems, can be hired from our in-house customer service or obtained via trade suppliers. You can also use our water softner tting HZEA.

10.5.2 Venting the heating system ff Vent the pipework carefully. For this, also activate the air vent valve integrated into the heating ow inside the heat pump.

10.6 Minimum ow rate


When operating without a buffer cylinder, safeguard the minimum ow rate specied in the following table as well as the defrost energy. 1 2 1 Heating circuit ow 2 Heating circuit return ff Connect the heat pump to the heating circuit. Check for tightness.
26_03_01_1552

Heat pump WPL 10 AC / WPL 10 ACS

Minimum flow rate 0.7 m/h

ff Make the correct adjustments to the overow valve.


Pump head 6m 7m 8m Pump head to be adjusted at the overflow valve* 4.1 m 5.1 m 6.1 m

10.4 Oxygen diffusion

*Relative to commercially available Wilo and Grundfos pumps.

Damage to the appliance and the environment In underoor heating systems, avoid open heating systems or the installation of steel pipes in conjunction with plastic pipes that are permeable to oxygen.

Note When installing a heat meter, note that most heat meters cause a substantial pressure drop. Consequently, size the circulation pump correspondingly larger.

Steel components, such as radiators and pipes, can corrode if plastic underoor heating system pipes, which are permeable to oxygen, are used. The products of corrosion, e.g. rusty sludge, can settle inside the heat pump condenser and result in a lower output by reducing the cross-section, or in a shutdown being activated by the high pressure limiter.

10 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

INsTallaTION  MOUNTINg
10.7 Condensate drain
A condensate drain connector is tted to the defrost pan at the factory to enable the condensate to drain off. 10.9.1 Access to the connecting chamber ENGLISH ff Remove the cover. 1 1 Cable entries ff Thread the connecting cables from below through the cable entries upwards to the connecting chamber. 1 1 Connecting chamber WPL 10 ACS | 11
26_03_01_1535 26_03_01_1552 26_03_01_1544

1 1 Condensate drain ff Secure a hose to the condensate drain connector. ff Insulate the hose to ensure frost protection.

Damage to the appliance and the environment Ensure the hose is not kinked. Route the hose with a slope.

ff Check after routing the hose that the condensate can drain correctly.

10.8 External heat source 2


For dual mode systems, always connect the heat pump into the return of the second heat source (e.g. oil boiler).

10.9 Power supply

Note Observe the operating and installation instructions of the WPM II heat pump manager.

Only qualied electricians must carry out the installation in accordance with these instructions. Permission to connect the appliance may need to be obtained from your local power supply utility. The terminals are located in the connecting chamber of the appliance. ff Observe chapter Preparing the electrical installation. ff Use appropriate cables in accordance with local regulations for all connections. ff Route all cables and leads through strain relief ttings.

WWW.sTIEBEl-ElTRON.COM

26_03_01_1552

INsTallaTION  MOUNTINg
10.9.2 Power supply WPL 10 AC (three-phase) ff Connect your power cable according to the following diagram. ff Connect the electric emergency/booster heater if you want to utilise the following appliance functions:
Appliance function Mono energetic operation Effect of the electric emergency/booster heater If the heat pump cannot reach the dual mode point, the electric emergency/booster heater ensures both the heating operation and the provision of high DHW temperatures. Emergency mode Should the heat pump suffer a fault that prevents its continued operation, the heating output will be covered by the electric emergency/booster heater. Heat-up program The electric emergency/booster heater must provide the (only for underfloor drying heat in case of return temperatures <25C. heating systems) With these low system temperatures, the drying heat must not be provided by the heat pump, otherwise the frost protection of the appliance can no longer be guaranteed during the defrost cycle. After expiry of the heat-up program, you can disconnect the electric emergency/booster heater if it is not required for the appliance operation. Please note that during the heat-up program, the emergency mode cannot be selected. Pasteurisation The electric emergency/booster heater starts automaticontrol cally when the pasteurisation control is active in order to regularly heat the DHW to 60 C to protect it against the growth of legionella bacteria.

X5

Electric emergency/booster heater (DHC) L1, L2, L3, N, PE Connected load 2.6 kW 3.0 kW 3.2 kW 5.6 kW 5.8 kW 6.2 kW 8.8 kW Terminal assignment L1 L2 L3 L1 L1 L1 L2 L2 L2 L3 L3 L3 N N N N N N N PE PE PE PE PE PE PE

1 2 3

X3 Power supply (heat pump, compressor) L1, L2, L3, N, PE X4 X2 Control voltage Mains supply: L, N, PE Low voltage (BUS cable) BUS High H Bus Low L BUS earth BUS + (is not connected) Earth terminal for screening the LV lead Ribbon heater Mains supply: L, N, PE

3 4

5 6

ff Earth the LV lead by inverting the screen over the external sheath and clamping it under the earth terminal. ff Then check the function of the strain relief ttings. 4

12 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

26_03_01_1730

D0000035392

INsTallaTION  MOUNTINg
10.9.3 Power supply WPL 10 ACS (single phase) ff Connect your power cable according to the following diagram. ff Connect the electric emergency/booster heater if you want to utilise the following appliance functions:
Appliance function Mono energetic operation Effect of the electric emergency/booster heater If the heat pump cannot reach the dual mode point, the electric emergency/booster heater ensures both the heating operation and the provision of high DHW temperatures. Emergency mode Should the heat pump suffer a fault that prevents its continued operation, the heating output will be covered by the electric emergency/booster heater. Heat-up program The electric emergency/booster heater must provide the (only for underfloor drying heat in case of return temperatures <25C. heating systems) With these low system temperatures, the drying heat must not be provided by the heat pump, otherwise the frost protection of the appliance can no longer be guaranteed during the defrost cycle. After expiry of the heat-up program, you can disconnect the electric emergency/booster heater if it is not required for the appliance operation. Please note that during the heat-up program, the emergency mode cannot be selected. Pasteurisation The electric emergency/booster heater starts automaticontrol cally when the pasteurisation control is active in order to regularly heat the DHW to 60 C to protect it against the growth of legionella bacteria.

X5

Electric emergency/booster heater (DHC) L, L, N, PE Connected load 3.0 kW 3.2 kW 6.2 kW Terminal assignment L N PE L N PE L L N PE

2 3 4

X3 Power supply (heat pump, compressor) L, N, PE X4 X2 Control voltage Mains supply: L, N, PE Low voltage (BUS cable) BUS High H Bus Low L BUS earth BUS + (is not connected) Earth terminal for screening the LV lead Ribbon heater Mains supply: L, N, PE

1
5

2 3

ff Earth the LV lead by inverting the screen over the external sheath and clamping it under the earth terminal. ff Then check the function of the strain relief ttings.

Damage to the appliance and environment Please note: When making the L and N connections of the compressor and the L and N connections of the control unit in single phase appliances, ensure that the same phase is used. Protect the circuit with an RCD.

WWW.sTIEBEl-ElTRON.COM

26_03_01_1529

WPL 10 ACS | 13

D0000035392

ENGLISH

INsTallaTION  MOUNTINg
Connection example
L N PE T 1 2 3 4
Auen Vorlauf WB Ein Recklauf

5 6
2. WE Quelle

7 8 9 10 11 12 13 14 15 16
Fhler 1 MischerUP-Sol/Kue Fhler 2 Fern 1 Mischer Analog Fern 3 BUS H BUS L BUS BUS + Mischer+

Pumpen L

UP-Quelle

UP-Zirkul.

UP-Hzg. 1

UP-Hzg. 2

UP-WWB

UP-WP 1

UP-WP 2

Netz L

Netz N

Netz L

3
K1 N

2. WE

1 2 3 4

5 6

7 8 9 10 11 12 13 14 15 16

2. WE

2
PE

BUS H BUS L BUS -

1 2 3 4

Heat pump Heat pump manager Main Control panel Power-OFF contactor

10.9.4 Closing the wiring chamber

1 Sound insulation ff Secure the cover with the four screws. ff Connect the circulation pump for the heat utilisation side to the heat pump manager in accordance with the engineering documents.

14 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

26_03_01_1759

D0000035461

L N PE L L N PE WP DHC

L N PE

1 2 3

INsTallaTION  COmmIssIONINg 11. Commissioning


A WPMII heat pump manager is required to operate the appliance. All necessary adjustments prior to and during operation are made on this device. Only heating contractors may carry out the adjustments on the heat pump manager commissioning list, commission the appliance and instruct the owner in its use. Carry out commissioning in accordance with these installation instructions and the operating and installation instructions of the heat pump manager. Our customer service can assist in the commissioning, which is chargeable. Where this appliance is intended for commercial use, the rules of the relevant Health & Safety at Work Act may be applicable for commissioning. For further details, check your local authorising body. After commissioning, complete the commissioning report that is part of these instructions. ENGLISH ff Remove the bracket highlighted in grey as follows: 1 1 IWS ff Position the panel highlighted in grey with the IWSas follows: ff Lift the panel highlighted in grey. 1 ff Secure the panel with the locking stay. WPL 10 ACS | 15
26_03_01_1532 26_03_01_1531 26_03_01_1530

11.1 Checks before commissioning


Before commissioning, check the following points. 11.1.1 Heating system -- Have you lled the heating system to the correct pressure, and opened the quick-acting air vent valve? 11.1.2 Temperature sensors -- Have you correctly located and connected the outside temperature sensor and the return temperature sensor (in conjunction with a buffer cylinder)? 11.1.3 Power supply -- Have you correctly connected the power supply? 11.1.4 Transport locks -- Have you removed the threaded rods that secure the compressor? 11.1.5 Checking the IWS DIP switch settings Carry out the following steps to make the IWS accessible.

ff Remove the cover.

WWW.sTIEBEl-ElTRON.COM

26_03_01_1544

INsTallaTION  COmmIssIONINg
IWS DIP switch (BA) ff Check whether the DIP switch (BA) is set correctly. Heating operation only: 1

BA
26_03_01_1537

BA

With cooling operation:


BA

BA
C26_03_01_0921

4 1 2 3 4 LEDs Reset button DIP switch (type WP) DIP switch (BA)

2 3

DIP switch (WP-Typ) With the DIP switch (WP-Typ), you can select the various heat pump types on the IWS. Factory setting: Single compressor mode with electric emergency/booster heater

WP-Typ
26_03_01_1513

ff Check whether the DIP switch is set correctly. Single compressor mode with an external second heat source 1 Sound insulation ff Position the cover on the appliance. ff Secure the cover with the four screws.

Damage to the appliance and environment In this case, do not connect the electric emergency/ booster heater.

If the appliance is operated in dual mode with an external secondheat source or as a module with a further heat pump of the same design, set the DIP switch to WP-Typ4. ff Set the DIP switch as follows.

16 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

26_03_01_1514

26_03_01_1759

26_03_01_1536

INsTallaTION  COmmIssIONINg
11.2 Commissioning
11.2.1 Heating curve adjustment The efciency of a heat pump decreases with rising ow temperature. The heating curve should therefore be adjusted with care. Heating curves that are adjusted too high lead to the zone and thermostatic valves closing, which may lead to the minimum ow rate required for the heating circuit not being achieved. ff Observe the WPM II operating and installation instructions. The following steps will help you to adjust the heating curve correctly: -- Fully open thermostatic or zone valves in a lead room (e.g. living room or bathroom). We do not recommend installing thermostatic or zone valves in the lead room. Control the temperature for these rooms via remote control. -- At different outside temperatures (e.g. - 10C and +10C), adjust the heating curve so the required temperature is achieved in the lead room. Standard values for the start:
Parameter Heating curve CNTRL RESP TM Underfloor heating system Heating system with radiators 0.4 5 0.8 15 20 C

11.2.2 Further WPMII settings 11.2.3 For operation without buffer cylinder ff At the commissioning level of the heat pump manager, call up parameter B-PUMP R-TIME. ff Activate the constant running of the buffer cylinder primary pump. ff Connect the heating circuit pump to the buffer cylinder primary pump terminals in accordance with the technical guide. When everything has been implemented correctly, the system can be heated to its maximum operating temperature and vented once again.

Damage to the appliance and environment With underoor heating systems, observe the maximum permissible temperature for the underoor heating system.

11.2.4 When using the heat-up program If you use the heat-up program, make the following settings on the WPM II: ff Initially set parameter DUAL MODE HEAT to 30C. ff Then set parameter HEAT LIMIT to 30C.

Room temperature 20 C

If the room temperature in spring and autumn is too low (approx. 10C outside temperature), the parameter room temperature must be raised.

Note If no remote control is installed, raising the parameter room temperature leads to a parallel offset of the heating curve.

Note After completing the heat-up process, reset the parameter DUAL MODE HEAT and HEAT LIMIT to their respective standard values or to the respective system values.

Increase the parameter HTG CURVE if the room temperature is not high enough when outside temperatures are low. If the parameter HTG CURVE has been raised, adjust the zone or thermostatic valve in the lead room to the required temperature at high outside temperatures.

11.3 Operation and control

Damage to the appliance and the environment Never interrupt the power supply, even outside the heating period. The systems active frost protection is not guaranteed if the power supply is interrupted.

Damage to the appliance and the environment Never reduce the temperature in the entire building by closing all zone or thermostatic valves, but by using the setback programs.

The system does not have to be switched off in summer. The WPM II has an automatic summer/winter changeover.

11.4 Taking the appliance out of use


If the appliance is to be taken out of use, set the WPMII to standby. This retains the safety functions designed to protect the system (e.g. frost protection).

When everything has been implemented correctly, the system can be heated to its maximum operating temperature and vented once again.

Damage to the appliance and the environment If the heat pump and frost protection are completely switched off, drain the system on the water side.

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 17

ENGLISH

Damage to the appliance and the environment With underoor heating systems, observe the maximum permissible temperature for the system.

INsTallaTION  MaINTENaNcE 12. Maintenance


Check the condensate drain (visual inspection). Remove contaminants and blockages immediately.

Damage to the appliance and the environment Keep the air discharge and intake apertures free from snow and ice.

Regularly remove all leaves and accumulated dirt from the evaporator ns, which can be accessed by removing the side panel on the condenser side .

18 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

INsTallaTION  TROUBlEshOOTINg 13. Troubleshooting


The following table shows the meaning of the LEDs of the IWS II.
LED indication Red LED flashes Red LED illuminates Meaning Single fault. Appliance stops and restarts after 10 minutes, and the LED extinguishes. More than 5 faults within 2 hours of operation. The appliance is shut down permanently and only restarts following a reset on the IWS. The internal fault counter will then be returned to zero. The appliance can then be restarted after 10 minutes. The LED extinguishes. The heat pump is initialising. The heat pump was initialised successfully and the connection with the WPM II is active.

Note Observe the heat pump manager operating and installation instructions (WPM II).

If a fault cannot be located during service using the heat pump manager, open the control panel in emergencies and check the IWS settings. This check must only be carried out by a heating contractor.

13.1 Light Emitting Diodes (LED)


LEDs on the IWS

Green LED (centre) flashes Green LED (centre) illuminates

Faults indicated by the red LED: -- High pressure fault -- Low pressure fault -- Other fault and -- Hardware fault on the IWS (see fault list)

13.2 Reset button


If the IWS was not initialised successfully, you can reset the settings with this button. ff For this also observe the chapter Reinitialising IWS in the heat pump manager operating and installation instructions.

BA

13.3 Resetting the high limit safety cut-out


BA

2 1 LEDs 2 Reset button

C26_03_01_0921

The electric emergency/booster heater stops if the heating water temperature exceeds 85 C, for example on account of a low ow rate. ff Remove the cause of the fault.

ff Reset the high limit safety cut-out. For this, press the button shown:

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 19

26_03_01_1528

ENGLISH

INsTallaTION  SpEcIFIcaTION 14. Specication


14.1 Wiring diagram WPL 10 AC (three-phase)
L N X4
X23

X7
X24

WP X23

DHC

X29
1 2 3 4

X36
3 2 1

L1L2 L3 N X3 X5
X23

L1L2 L3 N
X23

X35
6 5 4 3 2 1

K4

5 6 7 8

K5
1 3

10 11

K1
R3 R2 R1

1 2

3 4

5 6

X30
3 2 1

K6
1 3

12

K7

X38 K1
A2 A1 1 2 3

X34
7 6 5 4

4 3

6 5

K2

K2 X1
1 2 3 4 5
A2 A1

A2 (IWS II EEV)

3 2 1

K4
A2 A1

X33
5 4 3 2

K5
11 21 31 12 22 32

F5
T>

X37

K6
B A

V
M 3~

E1

K7
B A

P2=3000W P1=2600W

M1

F2

Y1

E2

A2 A3 B1 B2 B5 B6 B7 B8 B9 B10 E1 E2 F2 F5 K1 K2 K4 K5 K6 K7 M1 M6 M7

Integral heat pump control unit IWS Junctions PCB, earth temperature sensor Heat pump ow temperature sensor - KTY Heat pump return temperature sensor - KTY Hot gas temperature sensor - KTY Intake air temperature sensor - PT1000 Compressor intake temperature sensor - PT1000 Evaporator discharge temperature sensor - PT1000 Frost protection temperature sensor - KTY Discharge air temperature sensor - PT1000 Electric emergency/booster heater (DHC) Oil sump heater High pressure switch High limit safety cut-out for DHC Contactor resistor link Contactor, compressor start Contactor, fan start Instantaneous water heater relay Instantaneous water heater relay Instantaneous water heater relay Compressor motor Fan motor Stepper motor for electric expansion valve

P1 P3 R1 R2 R3 X1 X2 X3 X4 X5 X7 X23 X29 X30 X33 X34 X35 X36 X37 X38 X39 Y1

High pressure sensor Low pressure sensor Start-up resistance Start-up resistance Start-up resistance Terminal LV terminal Power supply Control terminal DHC terminal Ribbon heater terminal Power supply earth block 12-pin IWS plug - control unit 3-pin IWS plug - BUS 5-pin IWS plug - expansion valve 7-pin IWS plug - sensors 6-pin IWS plug - temperature sensors 3-pin IWS plug - fan 3-pole IWS plug - el. Injection valve 3-pin IWS plug - DHC Pressure sensor terminal Diverter valve

20 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

85_03_01_0011

P3=3200W

>p

INsTallaTION  SpEcIFIcaTION

Bus
H L X2 +

29
1 2 3 4 5 6 7 8 9 10 11 12

X36
3 2 1

X35
6 5 4 3 2

X30
3 2 1

38
1 2 3

X34
7 6 5 4 1 2 3 4

A3

X3

A2 (IWS II EEV)

3 2 1

3 4

5 6

X39 X33

K4
2

5 4 3 2 1 2 3 4 5 1

BU YE RD
M 1~

M _ _

M7

B1

B2

B9

P1

P3

B10

B8

B7

B6

B5

M6

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 21

85_03_01_0011

ENGLISH
X37

INsTallaTION  SpEcIFIcaTION
14.2 Wiring diagram WPL 10 ACS (single phase)
WP
X23 L N X3 X5

DHC
L L N X4
X23

L N

X7
X24

K1/M6

X29
1 2 3 4 5 6 7

X36
3 2 1

X35
6 5 4 3 2 1

X1/5 X1/3

R RC L N ON S

8 9

WPAB

10 11

K5
3 1

X30
3 2 1

12

K6
WPAB/ON
3

WPAB/N

X38 K1
A2 A1 1 2 3

X34
7 6 5 4

3 4

3 4

5 6

K1
2 6

K2
2

K2 X1
1 2 3 4 5
A2 A1

A2 (IWS II EEV)

3 2 1

Z1

K4

F5
T>

X33
5 A1 4 3 2

11 21 31 12 22 32

A2

K5
B A 1 2 3 4 5

X37

K6
C S R
X23
B A

M 1~

Bristol

>p

M1

E1 P3=3200W P2=3000W
P1=2600W

F2

Y1

E2

A2 A3 B1 B2 B5 B6 B7 B8 B9 B10 E1 E2 F2 F5 K1 K2 K4 K5 K6 K7 M1 M6 M7 P1

Internal heat pump control unit Junctions PCB, earth temperature sensor Heat pump ow temperature sensor - KTY Heat pump return temperature sensor - KTY Hot gas temperature sensor - KTY Intake air temperature sensor - PT1000 Compressor intake temperature sensor - PT1000 Evaporator discharge temperature sensor - PT1000 Frost protection temperature sensor - KTY Discharge air temperature sensor - PT1000 Electric emergency/booster heater (DHC) Oil sump heater High pressure switch High limit safety cut-out DHC Contactor, compressor start Contactor, compressor start Contactor, fan start Electric emergency/booster heater relay Electric emergency/booster heater relay Electric emergency/booster heater relay Compressor motor Fan motor Stepper motor for electric expansion valve High pressure sensor

P3 R1 R2 R3 X1 X2 X3 X4 X5 X7 X23 X29 X30 X33 X34 X35 X36 X38 X37 X39 Y1 Z1

Low pressure sensor Start-up resistance Start-up resistance Start-up resistance Terminal LV terminal Terminal Control terminal DHC terminal Ribbon heater terminal Power supply earth block 12-pin IWS plug - control unit 3-pin IWS plug - BUS 5-pin IWS plug - expansion valve 7-pin IWS plug - sensors 6-pin IWS plug - temperature sensors 3-pin IWS plug - fan 3-pin IWS plug - DHC 3-pole IWS plug - el. Injection valve Pressure sensor terminal Diverter valve Compressor capacitor, run

WPAB Softstart

22 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

85_03_01_0004

INsTallaTION  SpEcIFIcaTION

Bus
H L X2 +

X29
1 2 3 4 5 6 7 8 9 10 11 12

X36
3 2 1

X35
6 5 4 3 2

X30
3 2 1

X38
1 2 3

X34
7 6 5 4 1 2 3 4

A3

X3

A2 (IWS II EEV)

3 2 1

3 4

5 6

X39 X33

K4
2

5 4 3 2 1 2 3 4 5 1

BU YE RD
M 1~

M _ _

M7

B1

B2

B9

P1

P3

B10

B8

B7

B6

B5

M6

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 23

85_03_01_0004

ENGLISH

X37

INsTallaTION  SpEcIFIcaTION
14.3 Output diagrams, heating WPL 10 AC
Key to output diagrams Y Heating output [kW] | Power consumption [kW] | Coefcient of performance [-] X Inlet temperature of the heat source medium [C] 1 Flow temperature 35 C 2 Flow temperature 45 C 3 Flow temperature 55 C 4 Flow temperature 60 C Heating output

16 14 12 10 8 6 4 2 0 -20

1 2 3 4

-15

-10

-5

10

15

20

25

30

35

40

Power consumption

4 2 0 -20

1 2 3 4
-15 -10 -5 0 5 10 15 20 25 30 35 40

Coefcient of performance (COP)

6 4 2 0 -20

1 2 3 4
-15 -10 -5 0 5 10 15 20 25 30 35 40
84_03_01_0130

24 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

84_03_01_0128

INsTallaTION  SpEcIFIcaTION
14.4 Output diagrams, cooling WPL 10 AC
Key to output diagrams Y Cooling capacity [kW] | Power consumption cooling [kW] | Coefcient of performance cooling [-] X Inlet temperature of the heat source medium [C] 1 Flow temperature +7 C 2 Flow temperature +18 C Cooling capacity
12

10

1 2

2
84_03_01_0131

25

30

35

40

45

50

Power consumption
4

1 2
84_03_01_0132

0 25 30 35 40 45 50

Coefcient of performance (COP)


4

1 2
84_03_01_0133

0 25 30 35 40 45 50

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 25

ENGLISH

INsTallaTION  SpEcIFIcaTION
14.5 Output diagrams, heating WPL 10 ACS
Key to output diagrams Y Heating output [kW] | Power consumption [kW] | Coefcient of performance [-] X Inlet temperature of the heat source medium [C] 1 Flow temperature 35 C 2 Flow temperature 45 C 3 Flow temperature 55 C 4 Flow temperature 60 C Heating output

16 14 12 10 8 6 4 2

1 2 3 4

-15

-10

-5

10

15

20

25

30

35

40

Power consumption

4 2 0 -20

-15

-10

-5

10

15

20

25

30

35

40

Coefcient of performance (COP)

6 4 2 0 -20

1 2 3 4
-15 -10 -5 0 5 10 15 20 25 30 35 40
84_03_01_0083

26 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

84_03_01_0084

1 2 3 4

84_03_01_0085

0 -20

INsTallaTION  SpEcIFIcaTION
14.6 Output diagrams, cooling WPL 10 ACS
Key to output diagrams Y Cooling capacity [kW] | Power consumption cooling [kW] | Coefcient of performance cooling [-] X Inlet temperature of the heat source medium [C] 1 Flow temperature +7 C 2 Flow temperature +18 C Cooling capacity
12

10

1 2

2
84_03_01_0080

25

30

35

40

45

50

Power consumption
4

1 2
84_03_01_0081

0 25 30 35 40 45 50

Coefcient of performance (COP)


4

1 2
84_03_01_0082

0 25 30 35 40 45 50

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 27

ENGLISH

INsTallaTION  SpEcIFIcaTION
14.7 Data table
Output details apply to new appliances with clean heat exchangers. The power consumption of the integral auxiliary drives is stated as a maximum and may vary, subjectto operating point. The power consumption of the integral auxiliary drives is already included in the output details of the heat pump, as speci ed by the EN 14511.
WPL 10 ACS 227995 Outputs to EN 14511 Output at A-7/W35 (EN 14511) Output at A2/W35 (EN 14511) Output at A7/W35 (EN 14511) Output at A10/W35 (EN 14511) Heating output at A7/W45 (EN 14511) Refrigerating capacity at A35/W7 Cooling capacity at A35/W18 Power consumption Power consumption, emergency/booster heater Power consumption, fan heating max. Power consumptions to EN 14511 Power consumption at A-7/W35 (EN 14511) Power consumption at A2/W35 (EN 14511) Power consumption at A7/W35 (EN 14511) Power consumption at A10/W35 (EN 14511) Power consumption at A7/W45 (EN 14511) Power consumption - cooling at A35/W7 Power consumption Cooling at A35/W7 Coefficients of performance to EN 14511 Coefficient of performance at A-7/W35 (EN 14511) Coefficient of performance at A2/W35 (EN 14511) Coefficient of performance at A7/W35 (EN 14511) Coefficient of performance at A10/W35 (EN 14511) Coefficient of performance at A7/W45 Cooling factor at A35/W7 Cooling capacity at A35/W18 Sound data External sound power level, external installation (EN 12102) Sound pressure level at 5 m distance in a free field Sound pressure level at 10 m distance in a free field Application limits Min. application limit on the heating side Max. application limit on the heating side Heat source application limit (min.) Heat source application limit (max.) Electrical details Current (with/without softstarter) Fuse - compressor Emergency/booster heater fuse Control circuit fuse Frequency Rated compressor voltage Compressor phases Phases, emergency/booster heater Control phases Rated voltage, emergency/booster heater Rated control voltage Versions Refrigerant Refrigerant capacity Flow/return connection Defrost method IP-Rating Frost protection kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW 4.94 6.53 7.72 8.49 7.22 6.39 9.31 6.2 0.11 1.73 1.94 2.05 2.11 2.26 2.61 3.26 2.86 3.37 3.77 4.02 3.19 2.45 2.86 dB(A) dB(A) dB(A) C C C C A A A A Hz V 60 38 32 15 60 -20 40 26/C25 C35 C16 50 230 1/N/PE 1/N/PE 1/N/PE 230 230 R407 C 2.5 G 1 1/4 A Circuit reversal IP14B Yes WPL 10 AC 230236 5.11 6.74 7.83 8.29 7.26 6.22 9.12 8.8 0.11 1.67 1.92 2.03 2.06 2.25 2.56 3.16 3.06 3.51 3.86 4.02 3.22 2.43 2.95 60 38 32 15 60 -20 40 22 / C16 C16 C16 50 400 3/N/PE 3/N/PE 1/N/PE 400 230 R407 C 2.5 G 1 1/4 A Circuit reversal IP14B Yes

V V

kg

28 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

INsTallaTION  SpEcIFIcaTION
WPL 10 ACS Dimensions Height Width Depth Weights Weight Values Flow rate, heating side Heating flow rate (min.) Flow rate, heat source side Internal pressure differential mm mm mm kg m/h m/h m/h hPa 900 1270 593 120 1.4 0.7 2300 180 WPL 10 AC 900 1270 593 120 1.4 0.7 2300 180

14.8 Dimensions

e01 295 210 e02 100

b01

480

d45

900

g01

g02

35-40

b01 e01 e02 d45 g01 g02

Electrical cable entry Heating circuit ow Heating circuit return Condensate drain Air intake Air discharge

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 29

D0000016780

(890) 1160 1270

490 593

ENGLISH

INsTallaTION  COmmIssIONINg REpORT 15. Commissioning report


1. Customers address: 6. Installation conditions according to Stiebel Eltron installation and operating instructions: Installation room volume: 7. 2. Installer: Operating mode m

mono mode dual-mode - parallel - part parallel - alternative Dual-mode heat source

3.

Building type:

Detached house Appartment block Apartment block/Commercial Industrial/Commercial Public building Single heat pump Cascade 4. Equipment type:

Gas red boiler Oil red boiler Solid fuel boiler District heating Electric heating 8. yes Hydraulic connection of the heat pump with buffer cylinder no

Buffer cylinder content 9. DHW heating:

ID No: Serial No. Production No. 5. Heat pump location: Cellar First oor Second oor Top oor

independent of HP yes no with external heat exchanger yes no with internal heat exchanger yes no STE products: types:

External Internal

Third party products types: On concrete base On base plate On level ground Horizontal: yes no yes no

Anti-vibration mounts:

30 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

INsTallaTION  COmmIssIONINg REpORT


10. Heat source: Air Outside air Extract air min: max: Ground Ground probe No. C C

12. System periphery: Circulation pump source Manufacture / type Circulation pump heating Manufacture / type Circulation pump Heat pump/heat exchanger Manufacture / type
no

Temperature

Internal pipe diameter: Distributor: yes Depth of hole: Hydraulic connections as per Tichelmann yes no Ground collector Pipe length: Diameter: Area: Distributor: yes no

Circulation pump Heat exchanger / cylinder Manufacture / type Circulation pump heat pump/ buffer cylinder Manufacture / type Circulation pump DHW circulation Manufacture / type Circulation pump heat pump/ DHW cylinder Manufacture / type Mixing valve Manufacture / type Mixing valve servomotor Manufacture / type / / / / / /

Hydraulic connections as per Tichelmann yes no Process medium: Type: Concentration: Frost protection: Water Others: Well Surface water

13. Control unit STIEBEL-ELTRON product/type Third party: type Parameters set in acc. with the control unit commissioning report 14. Power supply: Cable type: No. of conductors Cross-section Installed acc. to VDE yes no

11. Heating system: Underoor heating Convectors Panels Radiators Design temperature: FL C/ RE C

Control cable heat pump: Cable type No. of conductors Cross-section:

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 31

ENGLISH

INsTallaTION  COmmIssIONINg REpORT


15. Actual data: Actual at the heat pump after 10 min. operation: Brine inlet/water/air: Brine outlet/water/air: Heat pump ow temp.: Heat pump return temp: C C C C Implemented: Values OK: yes yes no no 16. Tested to VDE 0701

17. System layout

Place, date

Installers signature

32 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

INsTallaTION 

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 33

ENGLISH

WARRANTY | ENVIRONMeNT AND ReCYCLING 

Warranty
The warranty conditions of our German companies do not apply to appliances acquired outside of Germany. In countries where our subsidiaries sell our products, it is increasingly the case that warranties can only be issued by those subsidiaries. Such warranties are only granted if the subsidiary has issued its own terms of warranty. No other warranty will be granted. We shall not provide any warranty for appliances acquired in countries where we have no subsidiary to sell our products. This will not affect warranties issued by any importers.

Environment and recycling


We would ask you to help protect the environment. After use, dispose of the various materials in accordance with national regulations.

KYOTO | R407C
This device is lled with refrigerant R407C. Refrigerant R407C is a CFC greenhouse gas mentioned in the Kyoto protocol with a global greenhouse potential (GWP) = 1653. Never release refrigerant R407C to atmosphere.

34 | WPL 10 ACSwww.sTIEBEl-ElTRON.COM

NOTES 

WWW.sTIEBEl-ElTRON.COM

WPL 10 ACS | 35

ENGLISH

Deutschland STIEBEL ELTRON GmbH & Co. KG Dr.-Stiebel-Strae | 37603 Holzminden Tel. 05531 702-0 | Fax 05531 702-480 info@stiebel-eltron.de www.stiebel-eltron.de

Verkauf Tel. 05531 702-110 | Fax 05531 702-95108 | info-center@stiebel-eltron.de Kundendienst Tel. 05531 702-111 | Fax 05531 702-95890 | kundendienst@stiebel-eltron.de Ersatzteilverkauf Tel. 05531 702-120 | Fax 05531 702-95335 | ersatzteile@stiebel-eltron.de

Australia STIEBEL ELTRON Australia Pty. Ltd. 4/8 Rocklea Drive | Port Melbourne VIC 3207 Tel. 03 9645-1833 | Fax 03 9645-4366 info@stiebel.com.au www.stiebel.com.au Austria STIEBEL ELTRON Ges.m.b.H. Eferdinger Str. 73 | 4600 Wels Tel. 07242 47367-0 | Fax 07242 47367-42 info@stiebel-eltron.at www.stiebel-eltron.at Belgium STIEBEL ELTRON bvba/sprl 't Hofveld 6 - D1 | 1702 Groot-Bijgaarden Tel. 02 42322-22 | Fax 02 42322-12 info@stiebel-eltron.be www.stiebel-eltron.be Czech Republic STIEBEL ELTRON spol. s r.o. K Hjm 946 | 155 00 Praha 5 - Stodlky Tel. 251116-111 | Fax 235512-122 info@stiebel-eltron.cz www.stiebel-eltron.cz Denmark Pettinaroli A/S Mandal All 21 | 5500 Middelfart Tel. 06341 666-6 | Fax 06341 666-0 info@stiebel-eltron.dk www.stiebel-eltron.dk Finland STIEBEL ELTRON OY Kapinakuja 1 | 04600 Mntsl Tel. 020 720-9988 | Fax 020 720-9989 info@stiebel-eltron.fi www.stiebel-eltron.fi

4<AMHCMN=jcadcj>

Irrtum und technische nderungen vorbehalten! | Subject to errors and technical changes! | Sous rserve derreurs et de modifications techniques! | Onder voorbehoud van vergissingen en technische wijzigingen! | Salvo error o modificacin tcnica! | Excepto erro ou alterao tcnica | Zastrzeone zmiany techniczne i ewentualne bdy | Omyly a technick zmny jsou vyhrazeny! | A muszaki vltoztatsok s tvedsek jogt fenntartjuk! | . . | Chyby a technick zmeny s vyhraden! Stand 8836

A 292032-37361-8842 B 291753-37361-8842

France STIEBEL ELTRON SAS 7-9, rue des Selliers B.P 85107 | 57073 Metz-Cdex 3 Tel. 0387 7438-88 | Fax 0387 7468-26 info@stiebel-eltron.fr www.stiebel-eltron.fr Hungary STIEBEL ELTRON Kft. Gyr u. 2 | 2040 Budars Tel. 01 250-6055 | Fax 01 368-8097 info@stiebel-eltron.hu www.stiebel-eltron.hu Japan NIHON STIEBEL Co. Ltd. Kowa Kawasaki Nishiguchi Building 8F 66-2 Horikawa-Cho Saiwai-Ku | 212-0013 Kawasaki Tel. 044 540-3200 | Fax 044 540-3210 info@nihonstiebel.co.jp www.nihonstiebel.co.jp Netherlands STIEBEL ELTRON Nederland B.V. Daviottenweg 36 5222 BH 's-Hertogenbosch Tel. 073 623-0000 | Fax 073 623-1141 info@stiebel-eltron.nl www.stiebel-eltron.nl Poland STIEBEL ELTRON Polska Sp. z o.o. ul. Dziakowa 2 | 02-234 Warszawa Tel. 022 60920-30 | Fax 022 60920-29 stiebel@stiebel-eltron.pl www.stiebel-eltron.pl Russia STIEBEL ELTRON LLC RUSSIA Urzhumskaya street 4, building 2 | 129343 Moscow Tel. 0495 7753889 | Fax 0495 7753887 info@stiebel-eltron.ru www.stiebel-eltron.ru

Slovakia TATRAMAT - ohrievae vody, s.r.o. Hlavn 1 | 058 01 Poprad Tel. 052 7127-125 | Fax 052 7127-148 info@stiebel-eltron.sk www.stiebel-eltron.sk Switzerland STIEBEL ELTRON AG Industrie West Gass 8 | 5242 Lupfig Tel. 056 4640-500 | Fax 056 4640-501 info@stiebel-eltron.ch www.stiebel-eltron.ch Thailand STIEBEL ELTRON Asia Ltd. 469 Moo 2 Tambol Klong-Jik Amphur Bangpa-In | 13160 Ayutthaya Tel. 035 220088 | Fax 035 221188 info@stiebeleltronasia.com www.stiebeleltronasia.com United Kingdom and Ireland STIEBEL ELTRON UK Ltd. Unit 12 Stadium Court Stadium Road | CH62 3RP Bromborough Tel. 0151 346-2300 | Fax 0151 334-2913 info@stiebel-eltron.co.uk www.stiebel-eltron.co.uk United States of America STIEBEL ELTRON, Inc. 17 West Street | 01088 West Hatfield MA Tel. 0413 247-3380 | Fax 0413 247-3369 info@stiebel-eltron-usa.com www.stiebel-eltron-usa.com

You might also like