Definitions EN 60079-10-1
Source of Release: A point of location from which a gas, vapour, mist or liquid may be released into the atmosphere so that an explosive gas atmosphere could be formed. Grades of release: There are three basic grades of release, as listed in order of decreasing frequency and likelihood of the explosive gas atmosphere being present:
Continous grade Primary Grade y Grade Secondary
Primary grade release: a release that is likely to occur periodically or occasionally in normal operations, i.e. a release which, in operating procedures is anticipated to occur
If it is likely to be present for between 10 to 1000 hours per year.
Secondary grade release: A release that is unlikely to occur in normal operation and, in any event, will do so only infrequently and for short periods i.e. i e a release which in operating procedures is not anticipated to occur. Such release may be of unknown size e.g. fracture of a drain or unknown size e.g. corrosion hole.
If it is likely to be present for 1 to 10 hours per year. year
7
Hazardous Area Classification Data Sheets Part I: Flammable Material List and data
Hazardous Area Classification Data Sheets Part II: List of sources of release
For detailed recommendations regarding the extent of the hazardous areas in specific industries or applications, reference may be made to national or industry codes relating to those applications.
POINT SOURCE
14
G(i) G(ii)
15
16
17
18
For offshore oil/gas installations, where there is a strong control of ignition sources outside the classified area, area LEVEL I is typically selected.
19
HOLE DIA 2 2 2 2
FLUID CAT. B B C C
20
HOLE DIA 2 2
FLUID CAT. B C
21
HOLE DIA 1 1 1 1 1
RADIUS R1 R2 2500 N/A 2000 N/A 1100 N/A 1400 N/A 1600 N/A
22
Control valves, often used block valves and valves not well maintained: A zone 1 with R = 0.3 m. A specific evaluation shall be made to decide if there is a further zone 2 around the zone 1.
23
24
No classification!
25
26
For dry gas seals on compresors, John J h Crane C states the two last rows for pumps will apply for th dry the d gas seals, l depending on execution of the dry gas seal
Single seal ( without fixed throttle bushing, in a pump with no wear Use IP-15 calculation ( Hole rings). This may be a component or size. 0,23xshaft dia.)* cartridge, general-purpose seal Single seal with a fixed throttle bushing or a single seal in an API 0,0003 Single 610 pump. This may be a component or cartridge, generalpurpose seal l Single seal,, supplied to ISO 21049, with a fixed throttle bushing ( code 1CW-FX) or a single seal, supplied Single 0,00015 to ISO 21049 with a solid floating bushing ( code 1CW-FL) in an API 610 or ISO 13709 pump. Dual, unpressurised seal ( without fixed throttle bushing bushing, in a pump with Use IP-15 calculation ( Hole Dual unpress. no wear rings). This may be a size 2 mm )** cartridge or non-cartridge, generalpurpose seal Dual, unpressurised seal ( ISO 21049, code 2CW-CW, 2CW-CS, with auxiliary plan 52, 75 or 76 ) with Dual unpress. 0,00001 a fixed throttle bushing or the same seal arrangement but in an API 610 pump or ISO 13709 pump. Dual, unpressurised seal as above Dual unpress. but containement system connected 0,00001 at seal. 0,0025 at vent to an open vent pipe Dual pressurised seal (without fixed Use IP-15 calculation ( Hole Dual press throttle bushing, innon-cartridge, size 2 mm )** general purpose seal Dual, pressurised Seal (ISO 21049, code 3CW-CW 3CW-CW, with auxiliary plan 53 or 54 ) with a fixed throttle Dual press NIL bushing or the same seal arrangement but in a API 610 or ISO 13709 pump Dual, pressurised Seal (ISO 21049, code 3NC, with auxiliary plan 74 ) Dual press with a fixed throttle bushing or the 0,01 same seal arrangement but in a API 610 or ISO 13709 pump Single
See IP-15
<2
<2
See IP-15 ( 4 to 6 )
<2
<2
See IP-15 ( 4 to 6)
2***
* Use seal chamber presssure as release pressure ( If not known use discharge pressure ) ** Use 5 bara as release pressure *** For R2, Cat C use 2,5 m
27
28
ENCLOSED AREAS
Minimum 12 ACH (IP 15), no stagnant zones to ensure area classification will correspond to grade of release. Pressurisation to safe a room adjacent to classified area: Min. 5 mm WG overpressure (IP 15)
29