You are on page 1of 3

STEP 1.

DETERMINE THE TOTAL LINE CURRENT


X'MER
LOCATION
A
back of main library
B
front of clinic
C
corner of CBAA
D
near CASS
E
back of CSM
F
corner of COE
G
AUET/RAC/MET
H
coener of COE (gym)
I
corner of CED
J
graduate school dormitory
TOTAL

Dec-11 POWER
1.076
STEP 2. DETERMINE MVA LOADIN
SECONDARY CURRENT (A)
real power (MW)
244.33333
0.103518571
285.33333
0.120889354
250
0.105919412
274.66667
0.116370129
375
0.158879118
248.33333
0.105213281
233.33333
0.098858117
324.66667
0.137554011
289.33333
0.122584065
14.66667
0.00621394
2539.66666
1.076
1.076+0.290206i

REACTIVE POWER
0.290206
STEP 2. DETERMINE MVA LOADING PER X'MER
real power (MW) reactive power (MVAR)
0.103518571
0.027919805
0.120889354
0.032604848
0.105919412
0.028567332
0.116370129
0.031385976
0.158879118
0.042850998
0.105213281
0.028376882
0.098858117
0.026662843
0.137554011
0.037099442
0.122584065
0.033061925
0.00621394
0.001675951
1.076
0.290206
1.076+0.290206i
1.114449

STEP 3. COMBINE MVA


X'MERS
MW
MVAR
BE
0.279768 0.075456
CD
0.22229 0.059953
FGHIJ
0.470423 0.126877
A
0.103519 0.02792

COMPLEX POWER
0.279768472875098+0.0754558452037088i
0.222289541305393+0.0599533072714433i
0.470423414968955+0.126877042346172i
0.103518570850554+0.0279198051786765i

72875098+0.0754558452037088i
41305393+0.0599533072714433i
14968955+0.126877042346172i
70850554+0.0279198051786765i

MAGNITUDE
0.289765
0.230233
0.487233
0.107218

STEP 4. PERCENT SHARE


%
26.00079
26
20.65888
20
43.71965
44
9.620685
10
100

You might also like