10.5.

2 Effective earth continuity between the exposed conductive parts of the ASSEMBLY and the protective circuit It shall be verified that the different exposed conductive parts of the ASSEMBLY are effectivelyconnected to the terminal for the incoming external protective conductor and that theresistance of the circuit does not exceed 0,1 .Verification shall be made using a resistance measuring instrument which is capable of driving a current of at least 10 A (a.c. or d.c.). The current is passed between each exposedconductive part and the terminal for the external protective conductor. The resistance shallnot exceed 0,1 . NOTE It is recommended to limit the duration of the test where low-current equipment otherwise may beadversely affected by the test.