Figure 2-3 FTS 830-2E System Installation Wiring

FTM 181 Revision 3 12-17-2002 2-5

ANODE

TRIG

CATHODE

TRIG RTN

GND

RED

BLU

BLK

WHT

PUR

SHIELD

BLU RED

BLK

SSALR

BLU RED

BLK

BLU RED

BLK

WHT PUR SHIELD

BLU RED BLU RED BLK

WHT PUR SHIELD

BLK

OPERATING MODE. INCLUDES: TYPICAL UNIT WIRING SHOWN. EXTERNAL WIRING TO TRANSFORMERS VARIES DEPENDING ON MODE OF OPERATION

DISPLAY NOTES DEFAULT VIEW THE MONITOR DETECTS A WORKING LIGHT X NO COMMUNICTION BETWEEN THE MONITOR AND LIGHT F THE MONITOR DETECTS A PROBLEM (FAIL) S THE LIGHT HAS BEEN TURNED OFF (SHUT DOWN BY CCR AND MGL
(TYPICAL)

WHT PUR SHIELD

OPERATION)

WHT PUR SHIELD

NOTES:
PC 830-2EN
CONTROL

"ALSF-2" "SSALR" "INVALID MODE"

PC 430-2EN OR PC 830-2EN
CONTROL

TB1 TB2
ANODE CATHODE TRIGGER TRIG RTN
10 11 16 1 CONTROL 2 RTN 3 GND 4 5

Figure 2-4 FTS 830-2EN System Installation Wiring


BAR #10 FH 800 (#15) BAR #17 FH 800 (#8) SEE NOTE 8 TYP. OF ALL
PC 830-2EN PC 830-2EN PC 830-2EN PC 830-2EN PC 830-2EN PC 830-2EN PC 830-2EN PC 830-2EN PC 830-2EN PC 830-2EN PC 830-2EN

TB1 TB2

1.
RED

DENOTES GROUNDING ROD CONNECTION. GROUNDING TO COUNTERPOISE NOT RECOMMENDED.


SERIES POWER
1 2 BLU 3 BLK 4 WHT 5 6

NOT SUPPLIED BY FTCA

MONITOR 17 RTN
18

VIO GND
SHIELD

CCR

BLK

WHT BLK

NOT SUPPLIED BY FTCA

F1 TB1
WHT

F2 TB3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

MGL

#18 BLK

#18 WHT

#18 BARE

Revision 3 12-17-2002
BAR #21 FH 800 (#4)
CONTROL

2. BARE #6 SOLID COPPER WIRE RECOMMENDED FOR COUNTERPOISE, IF USED.


DRAIN WIRE (DO NOT CUT OR BREAK)

PC 830-2EN
TB1
RTN

3. THE LIGHTING UNITS ARE PHASE SENSITIVE. ALL LIGHTING UNITS MUST HAVE THE SAME PHASE.
TB2

1 CONTROL 2 RTN RED ANODE 1 3 GND 4 2 BLU 5 CATHODE 3 BLK 10 SERIES TRIGGER 4 POWER TRIG RTN 5 WHT 11 6 16 MONITOR 17 RTN 18 VIO

GND

SHIELD

1 CONTROL 2 3 GND 4 5 10 11 16

ANODE CATHODE TRIGGER TRIG RTN SERIES POWER

BEACON ALARM CONTACTS TO CUSTOMER'S MONITORING EQUIPMENT. SEE NOTE 9. (OPEN ON ALARM)
FH#3 FH#4 FH#5 FH#6 FH#7 FH#8 FH#9 FH#10 FH#11 FH#12 FH#13 FH#14 FH#15

1 2 BLU 3 BLK 4 WHT 5 6

RED

4. ALL UNITS ARE WIRED THE SAME.

NOT SUPPLIED BY FTCA

MONITOR 17 RTN
18

VIO GND
SHIELD

FH#1

FH#2

5. 600 VOLT INSULATION RECOMMENDED FOR ALL INTERCONNECTION WIRES. THE SERIES POWER WIRES MUST BE RATED FOR 20KV.
DRAIN WIRE (DO NOT CUT OR BREAK)
DRAIN WIRE (DO NOT CUT OR BREAK)

TB4 TB5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

PC 830-2EN
CONTROL

TB1
RTN

TB2
ANODE

TB2

1 CONTROL 2 3 GND 4 5 10 11 16

RED 1
2 BLU 3 BLK 4

6. THIS DRAWING DEFINES MINIMUM SYSTEM REQUIREMENTS FOR WIRING AND MAY NOT MEET ALL APPLICABLE ELECTRICAL CODES.
SERIES POWER CATHODE TRIGGER TRIG RTN
5 6

WHT

1 2

1 2

NOT SUPPLIED BY FTCA

MONITOR 17 RTN
18

VIO GND
SHIELD

DRAIN WIRE (DO NOT CUT OR BREAK)

7. TO DETERMINE THE CONSTANT CURRENT REGULATOR SIZE, USE A VALUE OF 200 VOLT-AMPERES PER LIGHTING UNIT.
PC 830-2EN
CONTROL

RELAY K2A (MGL)

TB1
RTN

8. ARROW ON FLASHLAMP GLASS MUST ALIGN TOWARD HOLE IN BEZEL.


TB2
ANODE CATHODE TRIGGER TRIG RTN
10 11 16 1 CONTROL 2 3 GND 4 5

ALARM CONTACTS FOR REMOTE MONITORING SEE NOTE 9

RED

9. ALARM CONTACTS RATED 1A, 125V.


SERIES POWER
1 2 BLU 3 BLK 4 WHT 5 6

TO CUSTOMER'S 120V, 60Hz POWER SUPPLY AT 40VA FOR CONTROLLER

RELAY K2B K1 RELAY CCR

NOT SUPPLIED BY FTCA

MONITOR 17 RTN
18

VIO GND
SHIELD

AWG 18 TWISTED PAIR (SHIELDED)

MONITOR SERIES POWER 2.8A TO 6.6A SEE NOTE 3

COUNTERPOISE SEE NOTES 1 & 2

SERIES POWER 2.8A TO 6.6A SEE NOTE 3

DRAIN WIRE (DO NOT CUT OR BREAK)

FTM 181

CCR POWER

WHT PUR SHIELD

2-6
BAR #11 FH 800 (#14) BAR #12 FH 800 (#13) BAR #16 FH 800 (#9) BAR #20 FH 800 (#5) BAR #19 FH 800 (#6) BAR #13 FH 800 (#12) BAR #14 FH 800 (#11) BAR #15 FH 800 (#10) BAR #18 FH 800 (#7) T
X F TO LIGHTS 10 TO 15 (BAR 15 TO 10) ALL WIRED SIMILARLY X F X F X F X F X F X F X F X F X F X F

TRANSFORMER

T T T T T T T T T T

#14 AWG 600 VAC, MIN.

(2 SEPARATE WIRES)

(TWISTED TOGETHER)

AWG 18 TWISTED PAIR (SHIELDED) ROUTED TOGETHER

LIGHTS NUMBERED: TOP ROW 1-5 MIDDLE ROW 6-10 BOTTOM ROW 11-15

BAR #20 FH 800 (#5)

MONITOR DISPLAY

FH 800 FOR THE PC830 FH400 FOR THE PC430 SYSTEMS CANNOT BE MIXED.

FH 400

BAR #22 FH 800 (#3)

BAR #23 FH 800 (#2)

BAR #24 FH 800 (#1)

COUNTERPOISE

SEE NOTES 1 & 2

J1 J2 J3
J1

J303 RIBBON CABLE

TO J13 ON 2-4121-11 BOARD

DISPLAY PANEL END VIEW


TO J10 ON 2-4121-11 BOARD

2-4122-01 ALARM BRD

J17

J9 J10 J11 J12 J13 J1 J2 J3 J4 J5 J6 J7 J8 J14 J15 J16 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK WHT BLK

J18 2 BLK 1 WHT

TO TB1-2 TO F1 (SIDE)

TB4

10 11 12

13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

CABLE CLIPS
J4 J2 BLK WHT J4 J2 BLK WHT

J3

J1

J3

J1

TO J1

SURGE SUPPRESSOR 2-8653-01D (HIGH)

SURGE SUPPRESSOR 2-8653-02 (LOW)

TB5
CABLE CLIP

PRIMARY 120VAC TRANSFORMER SECONDARY 24VAC

BLK/WHT BLK/RED BLK/YEL BLK

BLU

J15 GRN BLU BLU 3 2 1

J13

BLU/YEL

J12

BLU

2-4121-18 MONITOR BRD


J10

BLK/RED

BLK

CHASSIS GROUND WHT GRN

J1 2 1

J2 J3 J4 J5 J6 J7 J8 J9 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 4 3 2 1 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 BLK WHT

GRN GRN

GRN

GRN

GRN

BLK/WHT

BLK/YEL

WHT

GRN

TO J18-1 BLK

WHT

BLK GRN WHT WHT BLK

BLK

TO J18-2 TB2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 TB3

RJ-11 TELEPHONE LINE

TB1

G W B

F1 2A

120VAC POWER CORD

BEACON ALARM CONTACTS (OPEN ON ALARM) FH#1 FH#2 FH#3 FH#4 FH#5 FH#6 FH#7 FH#8 FH#9 FH#10 FH#11 FH#12 FH#13 FH#14 FH#15

10 11 12

13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

TB4 MONITOR CLOSES ON ALM COM OPENS ON ALM

TB5

CCR

WHT

GND

WHT

BLK

10 11 12

13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

TB2

SHLD

TB3 FTM 181W MONITOR TERMINAL STRIP LEGEND 3-8618-10 REV B

Figure 2-5 FTM 181R or FTM 181W Monitor Internal Wiring

FTM 181

Revision 3 12-17-2002

WHT

BLK

BLK

MGL

WHT

BLK

BLK

BLK

BLK

BLK

2-7