Date 18-Feb-14 Computed by _ Approved by _

DESIGN

CALCULATION SHEET

--Sheet No. of

Subject Building

Typical Floor Roof DOHA INTERCONTINENTAL HOTEL

Checked by _

DESIGN OF SECTION ACCORDING TO BS8110-1997


Slab Basic mesh (-ve moment in guest rooms) SECTION TYPE
FLANGED (F) or UNFLANGED (U) ? u C T

MATERIALS PROPERTIES
CONCRETE CUBE STRENGTH (fCU) STEEL YIELD STRESS (fY) = = 350 4200 Kg/Cm Kg/Cm
2 2

SECTION PROPERTIES
TOTAL THICKNESS (t) WIDTH OF WEB (bw) EFFECTIVE WIDTH (b) COMPRESSION STEEL COVER (d') TENSION STEEL DEPTH (d) = = = = = 70.00 25.00 25.00 5.00 65.00 Cm Cm Cm Cm Cm

STRAINING ACTION
ULTIMATE MOMENT (MU) MOMENT DISTRIBUTION RATIO (bb) = = 58 0 m.t. %

K'

0.156

STEEL REINFORCEMENT
K LEVER ARM (z) DEPTH TO NEUTRAL AXIS (x) TENSILE STEEL AREA (As) TENSION STEEL = = = = 0.157 50.498 32.227 Cm Cm Cm2 COMPRESSION STEEL AREA (As') COMPRESSION STEEL = 0.200 Compression steel is needed for flexural strength

32.12
%

3.50
%

Cm2

1.836

r'
2 1 1

8 10 12 16 18 20 22 25 30 32 7 5 4

f
n

8 10 12 16 18 20 22 25 30 32 7 5 4 2 2 1 1

n 64 41 29 16 13 11 9

Note: In Section Type, the purpose of stating if the section is flanged or unflanged is that the minimum steel area depends on the existence or non-existence of a flange, even if the flange is in tension. Thus, even if you need to design a rectangular section, it can be flanged due to the presence of a slab.

211976381.xls.ms_office - Rev. 1.0

Page 1 / 2

2/18/2014

Project No. ---

Date 18-Feb-14 Computed by _ Approved by _

DESIGN CALCULATION SHEET

Sheet No. of

Subject Building

Typical Floor Roof DOHA INTERCONTINENTAL HOTEL

Checked by _

DESIGN OF SECTION ACCORDING TO BS8110-1987


Slab Basic mesh (-ve moment in guest rooms) SECTION TYPE
FLANGED (F) or UNFLANGED (U) ? FLANGE IN COMP. (C) or TENSION (T)? FLANGE IS: T-SHAPE (T) , L-SHAPE. (L)? F C T

MATERIALS PROPERTIES
CONCRETE CUBE STRENGTH (fCU) STEEL YIELD STRESS (fY) = = 350 4200 Kg/Cm Kg/Cm
2 2

SECTION PROPERTIES
TOTAL THICKNESS (t) WIDTH OF WEB (bw) EFFECTIVE WIDTH (b) COMPRESSION STEEL COVER (d') TENSION STEEL DEPTH (d) = = = = = 66.00 25.00 200.00 0.00 33.00 Cm Cm Cm Cm Cm FLANGE WIDTH (B) FLANGE THICKNESS (hf) = = 200.00 20.00 Cm Cm

STRAINING ACTION
ULTIMATE MOMENT (MU) MOMENT DISTRIBUTION RATIO (bb) = = 22 0 m.t. %

K'

0.156

STEEL REINFORCEMENT
K LEVER ARM (z) DEPTH TO NEUTRAL AXIS (x) TENSILE STEEL AREA (As) TENSION STEEL = = = 0.029 31.350 3.667 Cm Cm Cm2 COMPRESSION STEEL AREA (As') r' = COMPRESSION STEEL = 0.000 Compression steel is not needed for flexural strength

r
7 6

= 17.59 1.066 %

0.00
%

Cm2

8 10 12 16 18 20 22 25 30 32 5 4 3 3

f
n

8 10 12 16 18 20 22 25 30 32 0 0 0 0 0 0 0 0 0 0

n 35 23 16 9

Slab Basic mesh (-ve moment in guest rooms) SECTION TYPE


FLANGED (F) or UNFLANGED (U) ? FLANGE IN COMP. (C) or TENSION (T)? FLANGE IS: T-SHAPE (T) , L-SHAPE. (L)? F C T

MATERIALS PROPERTIES
CONCRETE CUBE STRENGTH (fCU) STEEL YIELD STRESS (fY) = = 350 4200 Kg/Cm2 Kg/Cm2

SECTION PROPERTIES
TOTAL THICKNESS (t) WIDTH OF WEB (bw) EFFECTIVE WIDTH (b) COMPRESSION STEEL COVER (d') TENSION STEEL DEPTH (d) = = = = = 66.00 25.00 200.00 0.00 33.00 Cm Cm Cm Cm Cm FLANGE WIDTH (B) FLANGE THICKNESS (hf) = = 200.00 20.00 Cm Cm

STRAINING ACTION
ULTIMATE MOMENT (MU) MOMENT DISTRIBUTION RATIO (bb) = = 22 0 m.t. %

K'

0.156

STEEL REINFORCEMENT
K LEVER ARM (z) DEPTH TO NEUTRAL AXIS (x) TENSILE STEEL AREA (As) TENSION STEEL = = = 0.029 31.350 3.667 Cm Cm Cm2 COMPRESSION STEEL AREA (As') r' = COMPRESSION STEEL = 0.000 Compression steel is not needed for flexural strength

r
7 6

= 17.59 1.066 %

0.00
%

Cm2

8 10 12 16 18 20 22 25 30 32 5 4 3 3

f
n

8 10 12 16 18 20 22 25 30 32 0 0 0 0 0 0 0 0 0 0

n 35 23 16 9