Rodurflex Insulators
are well-suited well-suited for: for: are High High contamination contamination applications applications Areas Areas where where vandalism is is vandalism a problem problem a High High creepage creepage on a a short short length length on Compact Compact line line applications applications
Key Features
Outstanding resistance to environmental factors such as UV light, ozone, acid, contamination and moisture. Interior tensile strength higher than steel, despite weighing approximately 75% LESS. Worldwide transmission system applications up to 765 kV. Reduced installation costs. No heavy lifting equipment required. High resistance to discharges and leakage currents. Reduced creepage requirtements for optimal performance when compared to porcelain, due to hydrophobic properties. Greater resistance to vandalism. High explosion resistance of hollow insulators in case of internal pressure build-up.
20 24
UP TO
INCHES FEET
The Rodurflex design allows for infinitely variable section lengths & creepage distances for every product.
Water-repellent, UV and coronaresistant silicone rubber base polymer housing. Pre-molded weathersheds are chemically bonded to the housing, eliminating mold-lines and allowing variable creepage distances for a fixed insulator length.
Metal fittings are fixed to the fiber glass core, not the silicone housing for maximum mechanical strength. Corona ring applied to the metal fittings to protect the housing. Housing is chemically bonded to the fiberglass core. Hydrolysis-resistant resin system applied to the fiberglass reinforced resin rod.
3mm-thick high temperature vulcanized (HTV) silicone rubber sheath improves the systems mechanical characteristics while reducing FRP rods electric field strength. Also protects the FRP rod during handling and installation. Metastable silicone sealing system prevents moisture ingress to the FRP rod.
1
TOWER END SECTION FITTING LENGTH (INCHES) Section length must be indicated with 3 digits and rounded to the nearest inch. Y= S= E= C= T= B= Y Clevis Socket Oval Eye Clevis Tongue Ball
LINE END CREEPAGE FITTING DISTANCE (INCHES) B= E= T= Y= C= S= Ball Oval Eye Tongue Y Clevis Clevis Socket Creepage Distance must be indicated with 3 digits and rounded to the nearest inch. A= B= C= D=
CORONA RING None (Standard Design) 230 kV (Line End) 345 kV (Line End) 500 kV (Both Ends)
Sample Number
CS2-041-YB-074-A
Suspension Insulator
Mechanical Rating SML: 25,000 lbs 111 kN RTL: 12,500 lbs 56 kN
Section Length
Ball:ANSI 52-5
Y-Clevis
45
1.57
Clevis:ANSI 52-6
0.69 1.4
Oval Eye
0.79
.67 1.18
2.36 1.24
TYPICAL LINE VOLTAGE 69 69 69/115 115 138 138/161 161 161 161/230 230 230 230 345 500
1. 2. 3. 4. 5.
PART NUMBER CS2-036-YB-064-A CS2-036-YB-092-A CS2-040-YB-072-A CS2-040-YB-101-A CS2-047-YB-089-A CS2-047-YB-127-A CS2-054-YB-106-A CS2-054-YB-120-A CS2-060-YB-121-A CS2-060-YB-145-A CS2-065-YB-140-A CS2-065-YB-159-A CS2-071-YB-141-A CS2-071-YB-170-A CS2-077-YB-157-A CS2-077-YB-190-A CS2-083-YB-187-A CS2-083-YB-215-A CS2-088-YB-192-A CS2-088-YB-225-A CS2-097-YB-234-A CS2-097-YB-295-A CS2-107-YB-244-A CS2-107-YB-305-A CS2-120-YB-257-A CS2-120-YB-309-A CS2-137-YB-307-A CS2-137-YB-382-A
ANSI SECTION CREEPAGE ARCING LOW FREQUENCY CLASS LENGTH DISTANCE DISTANCE FLASHOVER
DRY WET
60-1 60-2 60-3 60-4 60-5 60-6 60-7 60-8 60-9 60-10 60-12 60-13
64 92 72 101 89 127 106 120 121 145 140 159 141 170 157 190 187 215 192 225 234 295 244 305 257 309 307 382
27 31 38 45 51 56 62 68 74 79 88 98 111 128
269 307 374 442 499 547 605 663 720 768 854 950 1075 1238
257 287 337 388 431 468 511 555 598 634 699 772 866 990
446 506 609 713 801 875 964 1053 1141 1215 1347 1495 1688 1939
455 516 622 729 820 896 988 1079 1170 1247 1383 1535 1734 1991
All section lengths are based on Y-Clevis & Ball end fittings. Electrical data shown for insulators without corona rings. Lapp recommends corona rings to be installed at 230kV and above. Additional section lengths and creepage distances are available. Contact sales agency for details. All dimensions, tolerances and tests are within allowable ANSI standards. All dimensions are in inches and pounds.
Suspension Insulator
Mechanical Rating SML: 30,000 lbs 133 kN RTL: 15,000 lbs 67 kN
Section Length
Ball:ANSI 52-5
Y-Clevis
45
1.57
Clevis:ANSI 52-6
0.69 1.4
Oval Eye
0.79
.67 1.18
2.36 1.24
TYPICAL LINE VOLTAGE 69 69/115 115 138 161 161 161/230 230 230 230/345 345 345 345/500 500 500/765 765
1. 2. 3. 4. 5.
PART NUMBER CS3-042-SB-080-A CS3-042-SB-113-A CS3-048-SB-090-A CS3-048-SB-130-A CS3-054-SB-101-A CS3-054-SB-120-A CS3-060-SB-112-A CS3-060-SB-141-A CS3-068-SB-130-A CS3-068-SB-163-A CS3-074-SB-145-A CS3-074-SB-178-A CS3-083-SB-168-A CS3-083-SB-201-A CS3-089-SB-184-A CS3-089-SB-231-A CS3-096-SB-153-A CS3-096-SB-243-A CS3-104-SB-170-A CS3-104-SB-241-A CS3-120-SB-243-A CS3-120-SB-333-A CS3-130-SB-281-A CS3-130-SB-352-A CS3-140-SB-301-A CS3-140-SB-372-A CS3-170-SB-350-A CS3-170-SB-482-A CS3-180-SB-398-A CS3-180-SB-483-A CS3-195-SB-432-A CS3-195-SB-526-A
CREEPAGE DISTANCE 080 113 90 133 101 120 112 141 130 163 145 178 168 201 184 231 153 243 170 241 243 333 281 352 301 372 350 482 398 483 432 526
WEIGHT 7 9 8 11 8 10 9 11 10 12 11 13 12 14 13 16 11 16 11 16 16 21 18 22 19 23 21 29 24 29 25 31
333 390 449 506 583 641 726 784 850 928 1082 1178 1274 1562 1658 1801
306 349 393 436 494 538 603 647 696 755 871 944 1016 1234 1305 1414
545 633 724 812 930 1019 1151 1240 1342 1461 1698 1846 1994 2438 2584 2806
557 648 741 831 953 1045 1181 1272 1377 1500 1744 1896 2049 2505 2656 2884
All section lengths are based on Socket & Ball end fittings. Electrical data shown for insulators without corona rings. Lapp recommends corona rings to be installed at 230kV and above. Additional section lengths and creepage distances are available. Contact sales agency for details. All dimensions, tolerances and tests are within allowable ANSI standards. All dimensions are in inches and pounds.
Suspension Insulator
Mechanical Rating SML: 50,000 lbs 222 kN RTL: 25,000 lbs 111 kN
Section Length
Ball:ANSI 52-11
Y-Clevis
45
1 81
Clevis:ANSI 52-12
1.0 2.2
Oval Eye
1.02
.67 1.18
2.36 1.46
TYPICAL LINE VOLTAGE 69 115/138 138 138/161 161 161 230 230 230/345 345 345 345 345/500 500 500/765 765
1. 2. 3. 4. 5.
PART NUMBER CS5-045-EB-073-A CS5-045-EB-087-A CS5-056-EB-103-A CS5-056-EB-122-A CS5-062-EB-114-A CS5-062-EB-132-A CS5-068-EB-129-A CS5-068-EB-153-A CS5-074-EB-140-A CS5-074-EB-173-A CS5-080-EB-155-A CS5-080-EB-188-A CS5-092-EB-181-A CS5-092-EB-219-A CS5-100-EB-199-A CS5-100-EB-237-A CS5-106-EB-162-A CS5-106-EB-228-A CS5-112-EB-211-A CS5-112-EB-334-A CS5-123-EB-231-A CS5-123-EB-364-A CS5-134-EB-280-A CS5-134-EB-370-A CS5-145-EB-315-A CS5-145-EB-381-A CS5-154-EB-333-A CS5-154-EB-517-A CS5-185-EB-402-A CS5-185-EB-539-A CS5-195-EB-431-A CS5-195-EB-676-A
ANSI SECTION CLASS LENGTH 70-1 70-2 70-3 70-4 70-5 70-6 70-8 70-9 70-11 45 56 62 68 74 80 92 100 106 112 123 134 145
CREEPAGE DISTANCE 73 87 103 122 114 132 129 153 140 173 155 188 181 219 199 237 162 228 211 334 231 364 280 370 315 381 333 517 402 539 431 676
WEIGHT 14 15 17 18 17 19 19 20 19 22 21 23 23 25 24 26 21 26 25 33 27 36 30 36 33 37 34 47 39 49 42 59
314 419 477 535 593 650 765 843 898 958 1062 1169 1274 1360 1657 1751
292 371 415 458 502 545 632 691 732 777 856 937 1016 1081 1306 1376
516 678 767 856 945 1033 1210 1330 1415 1507 1667 1833 1994 2127 2583 2729
527 694 786 877 968 1059 1241 1365 1452 1547 1712 1882 2048 2185 2655 2805
154
185 195
All section lengths are based on Oval Eye & Ball end fittings. Electrical data shown for insulators without corona rings. Lapp recommends corona rings to be installed at 230kV and above. Additional section lengths and creepage distances are available. Contact sales agency for details. All dimensions, tolerances and tests are within allowable ANSI standards. All dimensions are in inches and pounds.
Suspension Insulator
Mechanical Rating SML: 100,000 lbs 445 kN RTL: 50,000 lbs 222 kN
Section Length
Oval Eye
1.38
1.14
2.95
WEIGHT 49 50 64 64 65 66
All section lengths are based on Oval Eye-Oval Eye end fittings. Electrical data shown for insulators without corona rings. Lapp recommends corona rings to be installed at 230kV and above. Additional section lengths and creepage distances are available. Contact sales agency for details. All dimensions, tolerances and tests are within allowable ANSI standards. All dimensions are in inches and pounds.
5.75
0.75
45
1.57
NUMBER OF BELLS
PART NUMBER CS2-023-SB-049-A CS2-026-YB-052-A CS2-029-SB-062-A CS2-031-YB-064-A CS2-036-SB-069-A CS2-039-YB-072-A CS2-040-SB-081-A CS2-043-YB-083-A CS2-046-SB-094-A CS2-049-YB-096-A
SECTION SECTION LENGTH LENGTH PORCELAIN POLYMER 23 23 28.75 28.75 34.5 34.5 40.25 40.25 45.6 45.6 23 26 29 31 36 39 40 43 46 49
CREEPAGE ARCING LOW CRITICAL DISTANCE DISTANCE FREQUENCY IMPULSE FLASHOVER FLASHOVER
DRY WET POS NEG
WEIGHT
4 5 6 7 8
1. 2. 3. 4.
49 52 62 64 69 72 81 83 94 96
16 18 22 23 29 31 33 35 39 41
173 198 222 230 285 306 323 345 381 401
146 167 222 228 270 286 299 315 342 358
275 314 374 387 471 504 530 564 619 652
328 375 381 394 481 515 541 576 633 667
6 7 7 8 7 8 8 9 9
All section lengths based on Socket Ball and Y-Clevis Ball combinations. Electrical data shown for insulators without corona rings. Lapp recommends corona rings to be installed at 230kV and above. All dimensions, tolerances and tests are within allowable ANSI standards. All dimensions are in inches and pounds.
LINE END FITTING 1 = Drop Tongue 2 = Horizontal Trunnion 3 = Spade Tongue 4 = Vertical Trunnion 5 = Flange 5 BC
CREEPAGE DISTANCE (INCHES) Creepage Distance must be indicated with 3 digits and rounded to the nearest inch.
2 = Gain
Sample Number
CL2-047-21-104-A
Section Length
Gain Base
Drop Tongue
1.65 0.87 0.75
1.00
3.62
Flat Base
0.39 .87
10.0 12.0
0.79
5 Flange
6.18
TYPICAL LINE VOLTAGE 69 69/115 115 138 161 161 230 230 230 230 345
1. 2. 3. 4. 5.
PART NUMBER CL2-035-22-059-A CL2-035-22-078-A CL2-042-22-080-A CL2-042-22-090-A CL2-048-22-096-A CL2-048-22-105-A CL2-054-22-111-A CL2-054-22-130-A CL2-060-22-127-A CL2-060-22-141-A CL2-068-22-154-A CL2-068-22-173-A CL2-075-22-166-A CL2-075-22-190-A CL2-085-22-195-A CL2-085-22-223-A CL2-090-22-210-A CL2-090-22-238-A CL2-096-22-220-A CL2-096-22-249-A CL2-105-22-230-A CL2-105-22-291-A
ANSI CLASS 250-41 250-47 250-54 250-60 250-66 250-75 250-85 250-95 250-105
SECTION CREEPAGE LENGTH DISTANCE 59 78 80 90 96 105 111 130 127 141 154 173 166 190 195 223 210 238 220 249 230 291
ARCING DISTANCE
RCL LBS
WEIGHT
35 42 48 54 60 68 75 85 90 96 105
22 29 35 42 48 56 63 73 78 84 94
190 289 370 448 521 615 692 793 841 893 967
189 270 335 397 457 533 595 676 715 757 817
368 482 579 676 773 902 1016 1178 1260 1356 1502
410 526 624 723 822 954 1070 1234 1318 1415 1565
3066 2417 2048 1774 1567 1355 1211 1052 987 920 833
All section lengths are based on Gain Base & Trunnion end fittings. Electrical data shown for insulators without corona rings and mounted horizontally. Lapp recommends corona rings to be installed at 230kV and above. Additional section lengths and creepage distances are available. Contact sales agency for details. All dimensions, tolerances and tests are within allowable ANSI standards. All dimensions are in inches and pounds.
2 = Gain
CORONA LINE END CREEPAGE RING FITTING DISTANCE (INCHES) Creepage Distance A= None 1 = Drop Tongue must be indicated 2 = Horizontal B= Line End with 3 digits and Trunnion rounded to the 3 = Spade Tongue nearest inch. 4 = Vertical Trunnion 5 = Flange 3 BC
Sample Number
CL1-028-44-053-A
PART NUMBER CL1-020-44-031-A CL1-024-44-044-A CL1-028-44-053-A CL1-020-42-030-A CL1-025-42-044-A CL1-028-42-052-A CL1-023-22-030-A CL1-028-22-044-A CL1-030-22-051-A
ANSI CLASS 51-14 51-15 51-16 51-24 51-25 51-26 51-34 51-35 51-36
LINE END FITTING Vert.Trunnion Vert.Trunnion Vert.Trunnion Horiz.Trunnion Horiz.Trunnion Horiz.Trunnion Horiz.Trunnion Horiz.Trunnion Horiz.Trunnion
Section Length
Gain Base
Drop Tongue
1.34 1.38 0.75
12.0
10.0
0.75
0.71
7/8 - 9 + .015
BASE END FITTING 3/4 Stud 3/4 Stud 7/8 Stud 3/4 Stud 3/4 Stud 7/8 Stud Gain Base Gain Base Gain Base
1. 2. 3. 4. 5.
SECTION LENGTH 20 24 28 20 25 28 23 28 30
CREEPAGE DISTANCE 31 44 53 30 44 52 30 44 51
RCL LBS 1808 1447 1209 1808 1380 1209 1808 1377 1258
WEIGHT
16 18 19 16 18 19 35 37 38
Electrical data shown for insulators without corona rings and mounted horizontally. Various section lengths and creepage distances are available. Contact sales agency for details. All dimensions, tolerances and tests are within allowable ANSI standards. All dimensions are in inches and pounds.
11
CREEPAGE DISTANCE
(INCHES)
DESIGN VARIATION This number is assigned by Lapp Engineering. Refer to drawing for individual components.
Section length of the post must be indicated with 3 digits and rounded to the nearest inch.
Creepage distance of the post must be indicated with 3 digits and rounded to the nearest inch.
Sample Number
CBP2-071-152-01
PART NUMBER
POST NUMBER
CBP2-045-107-01 CBP2-052-128-01 CBP2-058-149-01 CBP2-062-157-01 CBP2-067-177-01 CBP2-070-185-01 CBP2-075-195-01 CBP2-084-227-01 CBP2-090-242-01 CBP2-096-263-01
CL2-045-21-107-A CL2-052-21-128-A CL2-058-21-149-A CL2-062-21-157-A CL2-067-21-177-A CL2-070-21-185-A CL2-075-21-195-A CL2-084-21-227-A CL2-090-21-242-A CL2-096-21-263-A
Approximately 60
SUSPENSION NUMBER
CS2-058-EE-111-A CS2-068-EE-133-A CS2-077-EE-154-A CS2-083-EE-160-A CS2-091-EE-180-A CS2-095-EE-189-A CS2-103-EE-197-A CS2-116-EE-229-B CS2-125-EE-242-B CS2-134-EE-263-B
1. 2. 3.
45 52 58 62 67 70 75 84 90 96
107 128 149 157 177 185 195 227 242 263
10,125 10,125 10,125 10,125 10,125 10,125 10,125 10,125 10,125 10,125
320 385 455 505 560 590 655 630 685 745
285 350 410 440 500 520 560 560 610 655
525 615 700 775 870 915 1000 990 1080 1180
585 670 770 860 915 965 1035 1080 1180 1270
All braced posts shown with 12 upsweep bendable gain base and standard coupling shackles. Other hardware combinations are available, contact sales agency for details. All dimensions, tolerances and testing are within allowable ANSI standards.
13
Sample Number
CP1-018-11-041-A
TR NUMBER
TYPE
PART NUMBER
SECTION LENGTH
WEIGHT
POLYMER RCL* 1240 2000 875 1500 2700 3000 1911 1700 1575 1450 1350 1200
PORCELAIN WL**
RODURFLEX PORCELAIN RODURFLEX PORCELAIN RODURFLEX PORCELAIN RODURFLEX PORCELAIN RODURFLEX PORCELAIN RODURFLEX PORCELAIN
22 30 30 45 54 62
Section Length
5 Flange
0.79
6.18
3 Flange
2.5
3.9
END FITTINGS
MECHANICAL VALUES
TENSILE (LBS) TORSION (INCH LBS) COMPRESSION (LBS) IMPULSE WITHSTAND
ELECTRICAL VALUES
60 HZ WET WITHSTAND RIV TEST VOLTAGE MAX. RIV.AT 100 KHZ (MICROVOLTS)
11250 14000 11250 16000 22500 25000 22500 20000 22500 20000 22500 20000
8140 12000 8140 15000 22100 40000 22100 40000 22100 60000 22100 40000
11250 15000 5845 25000 23600 60000 10340 60000 6750 60000 5170 60000
135 100 190 145 160 145 265 230 355 275 315
30 44 44 73 88 103
< 200 < 200 < 200 < 200 < 200 <500
* RCL = Reference Cantilever Load for polymer and is the maximum load the insulator can withstand in service. It is approximately 50% of the ultimate cantilver rating of each design. Cantilever shown for porcelain is the ultimate value. ** WL = Working Load of porcelain and is approximately 40% of the ultimate rating. All dimensions are in inches and pounds.
15
230KV RECOMMENDED CORONA RING APPLICATION Line end Ground end Suspension Part Number suffix Line Post Part Number suffix YES NO -B -B
345KV YES NO -C -B
SUSPENSION INSULATOR ADJUSTMENTS WHEN ADDING CORONA RINGS Arcing distance (in) -3 -3 -6 25k, 30k, Low Frequency Flashover Dry (kV) -20 -30 -60 50k, 80k, Low Frequency Flashover Wet (kV) -20 -20 -45 100k Critical Impulse Flashover Pos (kV) -40 -40 -90 Critical Impulse Flashover Neg (kV) -40 -40 -90 Weight (lbs) +7 +7 +7.3
All suspension corona rings are: 13.8 OD Galvanized steel Open style Reversible mounting
LINE POST INSULATOR ADJUSTMENTS WHEN ADDING CORONA RINGS Arcing distance (in) -4 -4 2.5 Low Frequency Flashover Dry (kV) -40 -35 Line Low Frequency Flashover Wet (kV) -30 -30 Posts Critical Impulse Flashover Pos (kV) -70 -70 Critical Impulse Flashover Neg (kV) -70 -70 Weight (lbs) +9.5 +9.5
All line post corona rings are: 13.8 OD Galvanized steel Closed Ring style
Corona Rings
13.8
1.5
230 kV
2.4
13.8
1.9
345 kV
2.4
13.8
1.9
500 kV
2.0
17
Every day we go to work with one goal in mind: To always exceed customer expectations.
20 24
UP TO
INCHES FEET
The Rodurflex design allows for infinitely variable section lengths & creepage distances for every product.
Terms and Warranties All sales of Lapp Insulators and accessories described in this catalog are subject to Lapp Insulators Terms and Conditions of Sales as contained in Lapp Insulators Sales Order or Order Acknowledgement Forms and the limited warranties and limitations of liability thereunder.
LeRoy, New York USA 14482-1393 Tel: 585-768-6221 Fax: 585-768-6219 www.lappinsulator.com