Calculation of Size of Earth Conductor
Calculation of Size of Earth Conductor
Value of earth fault current of negligible impedance which can flow Cross sectional area in Square millimeters Constant depends on material of earth strip Operating time of the disconnecting device in seconds
S =
k = 5
x
1000
80 5 = 80
x
1.000 x
Minimum cross section of Earthing Conductor (Calculated) = Size of selected Earthing Conductor = Cross sectional area of considered Earthing conductor =
62.50 25 150
Sq.mm X Sq.mm
Value of earth fault current of negligible impedance which can flow through the protective device, in ampres Cross sectional area in Square millimeters Constant depends on material of earth strip Operating time of the disconnecting device in seconds
S =
k = 5
x
1000
80 5 = 80
x
1.000 x
Minimum cross section of Earthing Conductor (Calculated) = Size of selected Earthing Conductor = Cross sectional area of considered Earthing conductor =
62.50 25 150
Sq.mm X Sq.mm 6
12 of 3
Value of earth fault current of negligible impedance which can flow Cross sectional area in Square millimeters Constant depends on material of earth strip Operating time of the disconnecting device in seconds
S =
x k
x 80
1000
5 =
1.000 x 80
Minimum cross section of Earthing Conductor (Calculated) = Size of selected Earthing Conductor = Cross sectional area of considered Earthing conductor =
62.50 25 150
Sq.mm X Sq.mm
Value of earth fault current of negligible impedance which can flow through the protective device, in ampres Cross sectional area in Square millimeters Constant depends on material of earth strip Operating time of the disconnecting device in seconds
S =
x k
x 80
1000
5 =
1.000 x 80
Minimum cross section of Earthing Conductor (Calculated) = Size of selected Earthing Conductor = Cross sectional area of considered Earthing conductor =
62.50 25 150
Sq.mm X Sq.mm