Permissible voltage / frequency variation in %age to be indicated - 10% Max DC resistance of conductor at 20 deg cel ( ohm/km ) 0.100 Outer sheath thickness to be 3mm ( minimum ) - Ok Maximum AC resistance of conductor at 90 deg cel ( ohm/km ) to indicate - 0.129 Approx. cable capacitance , reactance, impedance to mention in ohm/km 0.32, 0.093 & 0.159 Continuous current carrying capacity in ground and in air to be mentioned
respectively.
relevant to us.
10. Vendor shall intimate the readiness of factory inspection along with the cable drum schedule, MRF shall communicate the drums selections required to be moved to the testing bay for high voltage testing purpose. Now it is mentioned the testing is for the complete LOT. We should insists on drum schedule where MRF can choose the drum to be tested not less that 50% of the quantity. As per IS-7098, sampling plan is: