The Dwelling Unit has floor area of approximately 220 SQM (110 SQM per floor).

It has typical household appliances including, one (1) 8-KW Electric Range, one (1) 1HP Refrigerator, one (1) 1.5HP room air-conditioning unit, and three (3) 1-HP Room air conditioning units. Total Load: a.) General Lighting 220 SQM x 24 VA/m^2 = 5280 VA Provide Three 15-Ampere Branch Circuits b.) Small Appliances load Three 20-Ampere Branch Circuits @1500VA (3*1500VA) = 4500VA Provide Three 20-Ampere Convenience Outlet Branch Circuits C.) Subtotal = 9780 VA Application of Demand Factor First 4500 VA @ 100% D.F. Remainder @ 35% D.F. (5280 VA x 0.35) Subtotal Other Load: One 1.5 HP Room ACU, (10 A X 230 X 1 @ 100 D.F.) Three 1.0 HP Room ACU, (8 A X 230 X 3 @ 100 D.F.) Provide Two 20 Ampere Spare Branch Circuits @ 1500 VA X 2 Net Other Load Cooking / Kitchen Load One 8kW Electirc Range (8000 VA) Application Demand Factor Total VA Cooking Load @ 80% D.F. 8000VA X 0.80 One 1.0 HP Refrigerator, (8 A X 230 X 1 @ 100 D.F.) Net Cooking/Kitchen Load Total Net Computed Load Circuit Requirements Use: Three - 15 Ampere Branch Circuits Eight 20 Ampere Branch Circuits Two 30 Ampere Branch Circuits One 40 Ampere Branch Circuits = 6400 VA = 1840 VA = 8240 VA = 25408 VA = 10820 VA = 2300 VA = 5520 VA = 3000 VA = 4500.00 VA = 1848.00 VA = 6348.00 VA

Circuit Requirements Total Full Load Current 25408 VA + 0.25 (2760) /230V = USE WIRE! Service Equipment [(250%X2760 VA) + 6348 VA +2300+5520+8240]/230 = USE SAME