MEGGER TESTING REGISTER

EQUIPMENT: DESCRIPTION: DRAWING: SHEET: AREA: THECNICIAN: SIGNATURE

MEASUREMENT OF ISOLATION

INSULATION TEST REGISTER


PROJECT: DESCRIPTION: DRAWING: MELCHORITA PERU LNG EMERGENCY DIESEL GENERATOR FOR PERMANENT COMMUNITY BUILDINGS ELECTRICAL TECHNICIAN: INSULATION RESISTANCE MEASUREMENT U-V-W-N GROUND 9 G EQUIPMENT NAMEPLATE BRAND: MODEL: SERIAL NUMBER: FRECUENCY: Catterpiller 3512 ZAH00802 60 Hz POWER: VOLTAGE: CURRENT: RPM: 1800 rpm 1.275 MVA 480 V BRAND: MODEL: SERIAL NUMBER: INSULATION RESISTANCE MEGGER MIT420 EN/100110/4559 BRAND: MODEL: SERIAL NUMBER: U-V-W-N GROUND 30 Seconds G-9001 (STATOR) 500 V 1 Minute 15.5 G U-V <0.1 AREA: Jaime Huaynate / Luis Pariahuamn COIL RESISTANCE () U-W <0.1 V-W <0.1 OBSERVATIONS Less than 0.1 DATE 6/22/2013 REGISTER: A-9000 SIGNATURE:
GD-9001-1-13

SHEET:

ELECTRICAL EQUIPMENT

VOLTAGE TEST

TESTING EQUIPMENT COIL RESISTANCE Simpson 260 06-117890

LAST CALIBRATION 21-Feb-11 LAST CALIBRATION 21-Feb-11 FINAL COMMENTS: According to ANSI/IEEE 43-2000 for rotative machines less than 1000V, the insulation test voltage is 500Vdc during 1 minute. If resistance is more than 500 M, the polarization index test doesn't apply. The insulation test was perform in the generator terminal box with the generator isolated (leads were removed from the bars). The test was perform @ 20C, its correction @ 40C is 3.1 G and IA=1.72. This values are indicating that the stator insulation is in good condition. Heaters are working. ELECTRICAL SUPERVISOR Name: Signature: Date: QUALITY CONTROL SUPERVISOR Name: Signature: Date: CUSTOMER Name: Signature: Date: