QLS SERIES ENCAPSULATED DELAY ON BREAK ANTI-SHORT CYCLE

"
!

FEATURES

Lock Out Delay Starts With Opening of Thermostat or Loss of Power ! 24 Volts AC Normal Operation ! 19 Volts AC or Less Brown-Out Protection Prevents Low Voltage Start Up ! Anticipator Compensation Circuitry Prevents Anticipator From Effecting Normal Operation ! Eliminates Rapid Cycling of Compressors And Relay Chatter ! Fixed or Adjustable Delays

SPECIFICATIONS
1. Time Delay. 1.1 Type: Analog 1.2 Range: 0.1 to 5 mins. adjustable, 2,3 or 5 min. fixed 1.3 Repeat accuracy: 2% 1.4 Reset time: 100 milliseconds 2. Input. 2.1 Operating voltage: 24 VAC 2.2 Frequency: 50 - 60 Hertz 3. Output. 3.1 Type: Solid state 3.2 Form: SPST 3.3 Rating: 1.0 ampere (40mA minimum or consult factory) 10 amperes inrush 3.4 Life: 100,000,000 operations minimum under full load 4. Protection. 4.1 Transient: 1500 volts for 150 microseconds 4.2 Dielectric breakdown: 1500 volts RMS minimum 5. Mechanical. 5.1 Mounting: One #8 or #10 screw 5.2 Termination: 1/4" quick connect 5.3 Style: Surface mount / encapsulated 6. Environmental. 6.1 Operating temperature: -20C to +60C 6.2 Storage temperature: -40C to +85C 6.3 Humidity: 95% relative, non-condensing

DIMENSIONS
1.35 Max. .750

2.00

.250 Dia.

2.00

.250 Quick Connect Terminals

CONNECTION DIAGRAM

Compressor Relay Thermostat

MODE OF OPERATION

DELAY ON BREAK - ANTI-SHORT CYCLE Power is applied when the thermostat closes and the compressor immediately energizes. When the thermostat opens, at the end of each cycle, a lockout delay begins which prevents the compressor relay from re-energizing. If the thermostat is closed, after the time delay is completed, the compressor relay will energize. In case of a momentary loss of power, the lockout will begin, preventing the compressor relay from closing for the duration of the delay. -Prevents rapid cycling or chatter of compressor contactors in cooling, heat pump, and refrigeration systems. -Allows head pressure to equalize before a start

Transformer 24VAC

ORDERING INFORMATION
SERIES QLS24 TIME DELAY A - 0.1 to 5 Minutes Adjustable -2 - 2 Minutes Fixed -3 - 3 Minutes Fixed -5 - 5 Minutes Fixed