ExProtectionConcepts

Electrical Electrical
Electrical Symbol TypicalIEC
EPL
TypicalZones IECStandard
(statusatJuly2008)
Basicconceptofprotection
Increasedsafety e Gb 1,2 IEC600797 Noarcs,sparksorhotsurfaces.
Enclosure IP54 or better T ( ki ) A G 2 IEC 60079 15 EnclosureIP54orbetter Typen(nonsparking) nA Gc 2 IEC6007915
Flameproof d Gb 1,2 IEC600791 Containtheexplosion,quenchthe
flame Typen(enclosedbreak) nC Gc 2 IEC6007915
Quartz/sandfilled q Gb 1,2 IEC600795 Quenchtheflame
Intrinsicsafety ia Ga 0,1,2 IEC6007911
i i h f k d f I t i i f t ib Gb 1 2 IEC 60079 11 Limittheenergyofsparksandsurface
temperatures
Intrinsicsafety ib Gb 1,2 IEC6007911
Intrinsicsafety ic Gc 2 IEC6007911
Typen(energylimitation) nL Gc 2 IEC6007915
Pressurised(upto2007) p Gb 1,2 IEC600792
Pressurised px Gb 1,2 IEC600792
i d b
Keeptheflammablegasout
Pressurised py Gb 1,2 IEC600792
Pressurised pz Gc 2 IEC600792
Typen(sealing&hermetic
sealing)
nC Gc 2 IEC6007915
Typen(restricted
breathing)
nR Gc 2 IEC6007915
breathing)
Typen(simplepressurised) nZ Gc 2 IEC6007915
Encapsulation ma Ga 0,1,2 IEC6007918
Encapsulation mb Gb 1,2 IEC6007918
Oilimmersion o Gb 1,2 IEC600796