Quick Start Modbus Channel Configuration for Micrologix


1100/1200/1500

Step 1 : Select channel configuration
Step 2 : Select Channel 0 tab
Step 3 : Choose Modbus RTU Slave driver and assign driver characteristics.



Step 4 : Enter Modbus data table file number for required Modbus function


Q Qu ui ic ck k S St ta ar rt t M Mi ic cr ro ol lo og gi ix x 1 12 20 00 0/ /1 15 50 00 0 a an nd d M Mo od db bu us s C Co om mm mu un ni ic ca at ti io on ns s


Step 5 : Enter data table size and type for each required file.



The data table file will be created automatically.



Q Qu ui ic ck k S St ta ar rt t M Mi ic cr ro ol lo og gi ix x 1 12 20 00 0/ /1 15 50 00 0 a an nd d M Mo od db bu us s C Co om mm mu un ni ic ca at ti io on ns s


Use the Following Table to assign memory mapping.
Example:
To access word 5 of the holding register (data file N104:5 above) you would read 40006.


Note: Status file information are currently required to be copied to integer or binary files for mapping.