You are on page 1of 2

For Electricians

For Programmers

Installation

1. Start up Loxone Config


2. Open your current project
3. Add an Extension
4. Enter the serial number in the properties
5. Copy the names / labels from this card
into your project
6. Save the program on the Miniserver
7. The LED on the extension will start
flashing green after a few seconds

See back for


Specification

First start up / Configuration

1. Mount extension on DIN rail


2. Connect 24V DC power supply, but do
not switch on until the whole installation
is completed (Recommendation: Loop
through the Miniserver)
3. Connect the inputs and outputs
4. Connect the Loxone Bus
5. Note: If its the last extension, termi nate the Loxone Bus with a 120
resistor (included with the Miniserver)
6. Switch on the power supply
7. After a few seconds, the left LED will
flash green if the extension is already
configured, or orange if not

www.loxone.com

www.loxone.com

Quick Connection Guide


Installation:

Serial Number:

Brief Specification
12 Digital inputs 24V DC, which can
also be used for frequency counting
(max. frequency: 150Hz)
8 Digital outputs (relays) 250V AC 5A,
with cos=1, 30V DC 5A
4 Analogue inputs 010V DC or
4 Digital inputs 24V DC
4 Analogue outputs 010V DC, 20mA
Power consumption c. 60mA

Extension

g
For further information alon
all technical details go to:
with
n
www.loxone.com/Extensio

ing your product at:

Enjoy benefits by register

www.loxone.com/reg

Loxone Electronics GmbH


Falkensteinstrae 6
4154 Kollerschlag
Austria
+43 7287 7070-0
office@loxone.com
www.loxone.com

The Miniserver based


home automation.

Reset

+ 24V
+ 24V

24V Input

I1
I2

24V Output
Ground
Loxone Bus +

I1
I2

Loxone Bus

I3

Q1
Q2

Q1
Q3

Q3

Q4

Q4

Q5

Q5

Q6

Q6
Q7
Q8

Q7
Q8

Digital Outputs
(Relays)

Q2

Digital
Inputs

I5
I6
I7
I8
I9
I10
I11

I4
I5
I6
I7
I8
I9
I10

I12

I11
AI1

Analogue
Inputs

Note down each connection you make in


the white boxes below. You can later copy
this information into Loxone Config when
youre configuring the project.

AI2

I12
Ground

AI3
AI4

AI1
AI2

AQ1

Analogue
Outputs

wires crossed:

I4

Extension

Loxone
Bus

i Dont get your

I3

Power
Supply

Ground

Ground

AQ2

AI3

AQ3

AI4

AQ4

Ground
AQ1
AQ2

www.loxone.com

Ground
AQ3
AQ4

You might also like