Computation of the FAD (Free Air Delivery) of a Compressor using the
Krohne Vortex FAD Meter Model VFM5090 FAD.
Brief Description of the FAD of a COMPRESSOR
Although FAD stands for Free Air Delivery, it is the amount of Atmospheric Air (Free Air) that can be sucked in by the Compressor at inlet conditions( Suction Side ) of
Atmospheric Pressure at 1 atmosphere. Atmospheric Temperature at 20C/15C. Relative Humidity at 0% (100% Dry Air) & The motor RPM at 100% of its rated value
The Krohne Vortex FAD meter VFM 5090 FAD is installed at the outlet (Discharge Side ) of the compressor, where the
Operating pressure is typically 7 to 10 Bar (g). Operating temperature may be close to 35-40C or higher (in case of no after cooler) Relative humidity is 70% to 100% & The RPM of the Motor Shaft may be 80% of its rated RPM value.
FAD Appl note Total 6 pages : 2 of 6
The Krohne Vortex FAD meter VFM 5090 FAD measures the Air flow at the
Discharge Side i.e. V (op) , P (op) , & T (op)
and compensates for the same at the
Suction Side i.e. V (nor) , P (nor) & T (nor) , RH at the Inlet & actual RPM
READ ON to Understand HOW the Krohne Vortex FAD meter VFM 5090 FAD does so
FAD Appl note Total 6 pages : 3 of 6
AIM
To Compute the FAD Free Air Delivery of the Compressor
To do this, we need to ESTABLISH a relationship between the MASS of Free Air Q m ( Inlet ) being taken in or sucked by the Compressor
and
the MASS of Air Q m ( Outlet ) being delivered at the Outlet of the Compressor
To do so, we need to carry out a MASS BALANCE of the Air at the Inlet to that at the Outlet MASS of Free Air Q m ( Inlet ) MASS of Air Q m ( Outlet )
The Krohne Vortex FAD meter VFM 5090 FAD is installed at the Outlet & we first need to compute the MASS of Air Q m ( Outlet ) at the Outlet.
MASS of Air Q m ( Outlet ) = V (op) * r ( op )
The Krohne Vortex VFM 5090 FAD measures the Operating Flow V (op) , while
the Density operating r ( op ) is a function of Operating Pressure P (op) & and Operating Temperature T (op) - the Krohne Vortex FAD meter VFM 5090 FAD has a PT 219 Pressure Sensor & PT 1000 Temperature Sensor built in, to continuously monitor the same. Molecular Weight of the gas ( built into the software of the FAD meter ) Real gas constant R . Compressibility factor Z ( op ) Correction and Wet gas mixture computation (to accommodate Relative Humidity changes)
Thus using the GAS LAWS the Density operating r ( op ) is computed.
P (op) * V (op) = n * R * T (op) * Z ( op )
V (op = Mass & n = Mass Density operating r ( op ) Mol Wt. of the wet gas
Rearranging, we get
Density operating r ( op) = P (op) * Mol Wt. of wet gas R * T (op) * Z (op)
FAD Appl note Total 6 pages : 4 of 6
In the above equation, the Compressibility factor Z (op) is computed using the Redlich Kwonk equation and needs to be corrected for, as the error can be close to 0.4% for Air at an operating pressure of 10Bar (g)
&
the Relative Humidity factor is corrected for , as the error at 70 % RH & 100 % RH can be - 4.0 % & - 5.6 % respectively.
Now, the MASS of Air Q m ( Outlet ) at the Outlet can be computed using the equation.
MASS of Air Q m ( Outlet ) = Volumetric Flowrate V (op) * Density operating P ( op )
Since, the
MASS of Air at the INLET =
MASS of Air at the Outlet
MASS of Free Air Q m ( Inlet ) =
MASS of Air Q m ( Outlet )
V ( nor ) ( Inlet ) = Q m ( Outlet )
Density Normal r ( nor ) Inlet
Similarly , the Inlet Density r ( nor ) Inlet , like the Density operating r ( op) , is a function of
Relative Humidity , Compressibility factor Z Temperature &, Pressure at the Inlet Conditions & can be computed.
V ( nor ) ( Inlet ) is the amount of FREE AIR being sucked in by the compressor
V ( FAD ) ( actual ) = V ( nor ) ( Inlet * RPM rated RPM specified
Compare the V ( FAD ) ( actual ) against the value given by the Compressor manufacturer V ( FAD ) ( specified )
The Krohne Vortex FAD meter VFM 5090 FAD is the Ultimate in Performance
FAD Appl note Total 6 pages : 5 of 6
Power Cost of Compressed Air
Every Compressor manufacturer specifies the FAD of the Compressor vis a vis the KWh Rating of the Motor ( Refer the Table on the following page )
As per the Table
1474 cfm Compressor requires a 275 KWh motor
1474 * 60 cubic feet of Air ( Free Air ) require 275 KWh Power per hour
Therefore , Cost of 88,500 ( 1474 * 60 ) cubic feet per hour of Air ( Free Air ) is 275 * Rs 3/- ( 1 KWh costs Rs 3/- )
88,500 cubic feet of Air ( Free Air ) costs 82,500 paise
1 cubic feet of Air ( Free Air ) costs approx 0.95 paise
Very simple to compute the Monthly Bill of your compressor Example : Your s is a 2,340 cfm ( Free Air ) Compressor
then, your Monthly Electricity Bill is
In Rupees = 2,340 * 0.95 * 60 * 24 * 30 / 100 = Rs 9,36, 000 /- = Rs 1, 15, 24, 000 /- per Year = approx Rs 1 Crore 15 Lacs per year
An Investment of close to 1% of this 1 Crore 15 Lacs is worth investing to monitor this 1 Crore 15 Lacs
FAD Appl note Total 6 pages : 6 of 6
This is not cfm or m 3 /min., because it is at Reference Conditions of 1 Atm & 20 0 C
It is therefore S cfm or N m 3 /min.
Customers also use the WRONG TERMINOLOGY and we do the incorrect sizing in turn.