Subcooler
Customer / Project Proiect Frigorifice Selection ID NUJ5Y3W8F
User name Alina Print date 1/13/2014
Freeze Warning
This heat exchanger's minimum fluid temperature of -18.0C is below the freezing temperature of 0.0C for water.
Model: SC3 (DX-A)
Cooling rate (kW) 1.7 Model size 5x12
Log mean temp. diff. (C) 46.9 Nominal surface (m) 0.5
Overall HTC (W/mK) 803 Dimensions 124W x 310H x 46D
Orifice pressure drop (kPa) 25.8 Net weight (kg) 3.4
Oversurface percent 1005.3
Design Conditions Side A - Evaporating Side B - Liquid
Refrigerant R-134a
Ref. mass flow (kg/min) 0.8
Target evaporator temp. (C) -18.0
Leaving pressure (bar ga) 0.4
Superheat (C) 5.0
Liquid temp. entering TXV (C) 38.0
Fluid type Water
Fluid mass flow rate (kg/min) 30
Entering fluid temp. (C) 30.0
Leaving fluid temp. (C) 29.2
Fluid flow rate (L/min) 30.4
Fluid fouling factor (mK/W) 0.000018
Model Parameters
Number of channels 7 8
Velocity (m/s) 1.1 0.3
Pressure drop (kPa) 8.5 22.4
Heat transfer coef. (W/mK) 877 11,721
Internal volume (L) 0.595 0.680
GEA Heat Exchangers, Inc. PHE Division
100 GEA Drive
York, PA 17406 USA
Ph: +717-268-6200
Fax: +717-268-6162
info.phe-systems.usa@gea.com
Website: www.gea-phe.com/usa
Notes
- To ensure proper part-load operation, the use of a hot-gas-bypass (HGBP) is recommended for this application. Contact
factory for details.
Ratings at Varying Conditions
Percent difference -15% -7% 0% 7% 15%
Pressure drop (kPa) (Side A) 7.2 7.8 8.5 9.1 9.8
Pressure drop (kPa) (Side B) 22.4 22.4 22.4 22.4 22.4
Cooling rate (kW) 1.4 1.6 1.7 1.8 2.0
Fluid flow rate (L/min) (Side B) 30.4 30.4 30.4 30.4 30.4
Fluid mass flow rate (kg/min) (Side B) 30 30 30 30 30
Entering fluid temp. (C) (Side B) 30.0 30.0 30.0 30.0 30.0
Leaving fluid temp. (C) (Side B) 29.3 29.3 29.2 29.1 29.1
Oversurface percent 1096.4 1048.5 1005.9 967.5 932.7
Disclaimer
This software and the generated calculations provided herein are estimates only and should be treated as such. GEA PHE Systems North America, Inc. always strives to give
complete and accurate information, but cannot provide any guarantees. This software and its output are provided "as is" and any express or implied warranties, including, but
not limited to, the implied warranties of merchantability and fitness for a particular purpose are disclaimed. In no event shall GEA PHE Systems North America, Inc. be liable
for any direct, indirect, incidental, special, exemplary, or consequential damages (including, but not limited to, procurement of substitute goods or services; loss of use, data,
or profits; or business interruption) however caused and on any theory of liability, whether in contract, strict liability, or tort (including negligence or otherwise) arising in any
way out of the use of this software, even if advised of the possibility of such damage.
Contact:
Customer / Project:
Model Nomenclature:
Selection ID:
Dimension Sheet Brazed Plate Heat Exchanger
GEA PHE Systems North America, Inc.
100 GEA Drive, York, PA 17406
Toll Free: 1-800-774-0474
Phone: 1-717-268-6200
Fax: 1-717-268-6163
www.gea-phe.com
E-mail: info.geaphena@geagroup.com
A:
B:
C:
D:
F:
G:
H:
Dimensions - inches (mm): Reference only
Connections Volume per BPHE
Circuit A Circuit B
Position 1 Position 2 Position 3 Position 4
Circuit A Circuit B
Net Weight:
Technical Data
Allowable Working Pressure and Temperature:
Max pressure Circuit A:
Circuit B:
Max temperature
Min temperature
Standard construction materials:
Braze Alloy:
Connector:
Plate:
Code Approvals:
Note: Code approval applies to heat exchangers only.
Installation Notes:
Pipe in counter flow direction.
Water strainer should be installed in the fluid inlet circuit to protect the heat exchanger from blockage (20-40 mesh).
Solder / Sweat Connections Use 45% silver solder (minimum), AWS grade Bag-24 or equivalent.
GEA Heat Exchangers
Mounting Bracket
(optional)
A:
B:
C:
D:
F:
G:
H:
NUJ5Y3W8F
SC3 (DX-A)
Copper 99.9%
304 Stainless Steel
316L Stainless Steel
450 psig (31.0 bar ga)
350.0 F (176.7 C)
-320.0 F (-195.6 C)
UL Listed, CRN
Optional: ASME (UM stamped), PED (CE)
Proiect Frigorifice
4.90 (124.5)
12.20 (309.9)
2.70 (68.6)
9.96 (253.0)
2.48 (63.0)
3.54 (89.9)
1.80 (45.7)
0.021 ft (0.595 L) 0.024 ft (0.680 L)
7.6 lb (3.4 kg) 7/8" IDS 5/8" IDS 1-1/8" IDS 1-1/8" IDS