Perancangan Sistem Listrik Industri TEE 542
Sesuai IEC 60044-1 spesifikasi class untuk CT:
Kelas
ketelitian
+/- % kesalahan ratio arus
pada % dari arus pengenal
+/- % pergeseran fase pada % dari
arus pengenal , menit (centiradians)
5 20 100 120 5 20 100 120
0,1 0,4 0,2 0,1 0,1 15 8 5 5
0,2 0,75 0,35 0,2 0,2 30 15 10 10
0,5 1,5 0,75 0,5 0,5 90 45 30 30
1,0 3,0 1,5 1,0 1,0 180 90 60 60
Kelas
ketelitian
+/- % kesalahan ratio arus
pada % dari arus pengenal
+/- % pergeseran fase pada % dari
arus pengenal , menit (centiradians)
1 5 20 100 120 1 5 20 100 120
0,2S 0,75 0,35 0,2 0,2 0,2 30 15 10 10 10
0,5S 1,5 0,75 0,5 0,5 0,5 90 45 30 30 30
Kelas
ketelitian
+/- % kesalahan ratio arus pada % dari arus pengenal
50 100
3 3 3
5 5 5
Perancangan Sistem Listrik Industri TEE 542
TRAFO ARUS
MASING MASING CLASS TRAFO ARUS
UNTUK PENGUKURAN
Untuk kebutuhan industri : CL2 or CL1
Untuk kWh meter di pelanggan : CL0.5
Untuk memperkecil kesalahan : CL0.2S
Untuk kebutuhan laboratorium : CL0.1
Akurasi burden pengenal:
Untuk kebutuhan instrument : CL3 or CL5
2,5 VA; 10 VA; 30 VA
5 VA ; 15 VA
7,5 VA ; 20 VA
Perancangan Sistem Listrik Industri TEE 542
Trafo Arus
CT Proteksi
CT Metering
I
eXct
E
S
Kurva CT untuk pengukuran
Kurva CT untuk proteksi
Knee point
Kurva magnetisasi CT
Perancangan Sistem Listrik Industri TEE 542
Trafo Tegangan
Trafo tegangan:
Instrumen trafo yang dipergunakan untuk memperkecil tegangan
tinggi ke tegangan rendah , dipergunakan untuk pengukuran atau
proteksi
Accuracy classes sesuai IEC 60044-2
Class Burden Voltage Ratio Phase Application
(%) (%) (%) displacement
(min)
0,1 25 - 100 80 - 120 0,1 5 laboratory
0,2 25 - 100 80 - 120 0,2 10 Precision and revenue metering
0,5 25 - 100 80 - 120 0,5 20 standard revenue metering industrial
1,0 25 - 100 80 - 120 1,0 40 grade meters intruments
3,0 25 - 100 80 - 120 3 -
3P 25 - 100 5-Vf 3,0 120 Protection
6P 25 - 100 5-Vf 6,0 240 Protection
Range Limit of Errors
Perancangan Sistem Listrik Industri TEE 542
Trafo Tegangan
Untuk pengukuran tegangan jatuh disisi sekunder 0,05 % s/d 0,1 % x
tegangan pengenal sekunder PT
Tegangan pengenal primer : kV (150 kV, 20 kV atau 150 kV/3 , 20 kV/3)
Tegangan pengenal sekunder: volt (110 V , 110 V atau 110 V/3 , 100 V/3)
R
S
T
Primer
20.000/3
Sekunder
100/3
s
r t
Rangkaian ekivalen
Tipe trafo tegangan:
Inductive voltage transformers
Capacitive voltage transformers
Perancangan Sistem Listrik Industri TEE 542
Klasifikasi Trafo Tegangan
Jenis INDUKTIF (PT)
Terdiri dari belitan Primer dan belitan sekunder, Belitan
primer akan menginduksikannya ke belitan sekunder
melalui core.
Jenis KAPASITIF (CVT)
Terdiri dari rangkaian kondensor yang berfungsi sebagai
pembagi tegangan tinggi dari trafo pada tegangan
menengah yang menginduksikan tegangan ke belitan
sekunder melalui media capasitor.
Perancangan Sistem Listrik Industri TEE 542
Trafo Tegangan Induktif
7
6
5
1
2
3
4
8
Keterangan gambar:
1. Kertas/Isolasi Minyak Mineral/Quartz filling.
2. Belitan Primer: vernis ganda-isolasi kawat
tembaga, tahan pada suhu tinggi.
3. Inti: bukan orientasi listrik baja memperkecil
resiko resonansi besi
4. Belitan Sekunder
5. Isolator Keramik
6. Dehydrating Breather
7. Terminal Primer
8. Terminal Sekunder
Perancangan Sistem Listrik Industri TEE 542
1). HV.T adalah terminal tegangan tinggi
2) kapasitor C1 & C2 pembagi tegangan
(capacitive voltage divider) yang
berfungsi sebagai pembagi tegangan
tinggi untuk diubah oleh trafo
tegangan menjadi tegangan
pengukuran yang lebih rendah
3). L0 adalah induktor penyesuai
tegangan (medium voltage choke)
yang berfungsi untuk
mengatur/menyesuaikan supaya tidak
terjadi pergeseran fasa antara
tegangan masukan (vi) dengan
tegangan keluaran (vo) pada
frekuensi dasar.
1
5
4
3
7
2
4) Belitan primer
5) Isolator keramik
7) Terminal sekunder
Perancangan Sistem Listrik Industri TEE 542
Kesalahan rasio trafo tegangan
Kesalahan besaran tegangan karena perbedaan rasio name plate
dengan rasio sebenarnya dinyatakan dalam
% = 100 (Kn Vs - Vp)/Vp
Composite Error
c
= 100/ V
p
100/T (K
n
v
s
v
p
)
2
dt
v
s
dan v
p
merupakan nilai tegangan sesaat sisi sekunder dan sisi primer.
Perancangan Sistem Listrik Industri TEE 542
PERHITUNGAN OCR
IEEE Extremely Inverse
IEEE Very Inverse
IEEE Moderately Inverse
ANSI Standard
Perancangan Sistem Listrik Industri TEE 542
Perancangan Sistem Listrik Industri (TEE 542)
Grounding System
Preview Perancangan Listrik Industri
Perancangan Sistem Listrik Industri TEE 542
Introduction
From an electrical point of view, the world
is effectively a huge conductor at zero
potential and is used as a reference point
which is called earth (in the UK) or
ground (in the USA).
Perancangan Sistem Listrik Industri TEE 542
Perancangan Sistem Listrik Industri TEE 542
The meaning
Earthing is a process that is used to
connect all of the parts that could become
charged, to the general mass of earth and
in so doing, provide a path for fault
currents which will hold these parts as
close as possible to earth (i.e. zero)
potential.
Earthing system is the electrical
potential of the conductors relative to that
of the earths conductive surface.
Perancangan Sistem Listrik Industri TEE 542
Electrical supply systems and equipment
are grounded in order to maintain the
voltage at any part of the system at a
known potential relative to true earth and
to provide a path for current flow under
earth fault conditions so that protective
devices operate correctly.
Perancangan Sistem Listrik Industri TEE 542
Ungrounded System
Power systems are always grounded
through the system capacitance, even if
the system neutral(s) is ungrounded.
Operate without a grounded conductor.
An ungrounded system does not have a
grounded (neutral) conductor routed
between the supply transformer and the
service equipment because the supply
transformer is not earth grounded.
Perancangan Sistem Listrik Industri TEE 542
Ungrounded System
Perancangan Sistem Listrik Industri TEE 542
Ungrounded System
Advantage:
An ungrounded system can ride through the
ground fault on one phase.
Disadvantage:
It can produce high transient line-to-ground
overvoltages. The insulation system in rotating
machines (motors and generators) is then
severely stressed and can cause insulation
breakdown.
The recommended solution to the above
disadvantage is to add a resistor in the neutral,
which will reduce potential phase-to-ground
overvoltages
Perancangan Sistem Listrik Industri TEE 542
High Resistance Grounded System
Shall not be used unless they are provided
with ground fault indicators or alarms, or
both, and qualified personnel are available
to quickly locate and eliminate such
ground faults.
A high-impedance grounding system has a
high-impedance unit, installed between the
grounded (neutral) conductor and the
grounding electrode conductor, which is
used to regulate fault current.
Perancangan Sistem Listrik Industri TEE 542
High Resistance Grounded System
Perancangan Sistem Listrik Industri TEE 542
High Resistance Grounded System
For correctly installed, the following can be
concluded:
1. Suppresses transient overvoltage
caused by line-to-ground faults
2. Limited to systems with charging
current not exceeding 5.5 A
3. Not enough ground current for selective
relaying
Perancangan Sistem Listrik Industri TEE 542
High Resistance Grounded
System
High-resistance grounding is
recommended for the following systems,
with the associated precautions listed:
1. Low-voltage systems with
predominantly three phase loads (Delta
or ungrounded Wye)
2. Medium-voltage systems up to 4.16 kV
where power interruption will be
detrimental to the process
Perancangan Sistem Listrik Industri TEE 542
Low-Resistance (LR) Grounded
System
To protect power transformers and
generators from damaging fault currents
LR Grounding for Wye-Connected
System
In these systems, a resistor sized for and
rated at 100400 A is connected to the
neutral of the transformer secondary
winding.
Perancangan Sistem Listrik Industri TEE 542
Low-Resistance (LR) Grounded
System
LR Grounding for Wye-Connected
System
Perancangan Sistem Listrik Industri TEE 542
Low-Resistance (LR) Grounded
System
LR Grounding for Delta-Connected
System
The preferred arrangement is to use a
three-phase zig-zag grounding transformer
with a resistor connected to its neutral.
The short time rating of the zig-zag
grounding transformer is the same as the
resistor rating
the continuous rating shall be at least 10%
of the available ground-fault current
Perancangan Sistem Listrik Industri TEE 542
Low-Resistance (LR) Grounded
System
LR Grounding for Delta-Connected
System
Perancangan Sistem Listrik Industri TEE 542
Low-Resistance (LR) Grounded
System
Additional :
The neutral can shift to the system phase-to-
ground voltage, and the first ground fault
must be detected to remove the fault circuit
from the system.
This grounding method suppresses the
transient phase-to-ground overvoltages.
Selective ground-fault relaying is possible.
Burning damage at the point of fault is
considerably reduced.
Requires that the cable insulation be 133%,
as the ground fault is cleared quickly.
Perancangan Sistem Listrik Industri TEE 542
Low-Resistance (LR) Grounded
System
Recommended to be applied :
Where a network is extensive and
subsidiary switching stations exist, and
Where selective tripping is required to
achieve the objective level of service
reliability.
It is also appropriate for overhead line
feeders.
Perancangan Sistem Listrik Industri TEE 542
Solidly Grounded Neutral System
The neutral is solidly connected to ground,
and hence the neutral is always at ground
potential.
Having the following characteristic :
1. It eliminates transient phase-to-ground
overvoltages during ground faults.
2. The first ground fault, due to the
unrestricted operation of the ground-fault
3. protection, quickly removes the faulted
circuit from operation.
4. Can cause extensive damage from arcing
ground faults.
Perancangan Sistem Listrik Industri TEE 542
Solidly Grounded Neutral
System
Perancangan Sistem Listrik Industri TEE 542
Solidly Grounded Neutral
System
The use of solidly grounded neutrals is
recommended for:
1. Low-voltage systems (three-phase, four-
wire) when the majority of the load is
connected between phase and neutral
2. HV, EHV, or UHV systems (above 34.5
kV) for better surge protection and for the
application of lower BIL (basic insulation
level) equipment, as the healthy phase
voltages during faults are significantly
reduced and lowerrated surge arrestors
can be safely applied
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
System classification
In order to identify the different systems, the IEE
Regulations for Electrical Installations recognize
the following designations of grounding systems
using a two-, three- or four-letter code as follows:
The first letter indicates the type of supply
earthing
The second letter indicates the earthing
arrangement in the installation
The third and fourth letters indicate the
arrangement of the earthed supply conductor
system
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
System classification
The first letter
T indicates that one or more points of the
supply are directly earthed (for example,
the earthed neutral at the transformer);
I indicates either that the supply system is
not earthed (at all) or that the earthing
includes a deliberately inserted
impedance, the purpose of which is to limit
fault current.
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
System classification
The second letter
T indicates that all exposed conductive
metalwork is connected directly to earth;
N indicates that all exposed conductive
metalwork is connected directly to an
earthed supply conductor provided by the
electricity supply company.
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
System classification
The third and fourth letter
S ensure that neutral and earth
conductor systems are quite separate;
C ensure that neutral and earth are
combined into a single conductor.
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
The integrity of the earthing of the installation
depends on a reliable and effective connection of
the PEN or PE conductors to earth;
One or more points in the generator or transformer
are connected to earth (usually the star point in a
three-line system).
The body of the electrical device is then connected
with earth via this earth connection at the
transformer and exposed conductive parts of the
installation are then connected to that point by
protective conductors .
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
The conductor that connects together the
exposed metallic parts of the consumer
installation is called the protective earth
(PE),
The conductor that connects to the star
point in a three-line system (or which
carries the return current in a single-line
system) is called the neutral (N)
There are three variants of TN systems:
TN-C, TN-S and TN-C-S.
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
1. TN-C system
is one where the neutral (N) and protective
earth (PE) functions are combined in a
single conductor throughout the system
and this combined neutral and earth wiring
is then used both by the supply and from
within the installation itself .
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
1. TN-C system
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
1. TN-C system (disadvantages)
RCDs (residual current devices) are far less likely
to detect an insulation fault.
They are vulnerable to unwanted triggering
caused by contact between earths of circuits, on
different RCDs or with real ground.
Any connection between the combined neutral and
earth core and the body of the earth could end up
carrying significant current under normal
conditions.
If there is a contact problem in the PEN conductor,
then all parts of the earthing system beyond the
break will rise to the potential of the live
conductor(s).
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
2. TN-S system
have separate protective earth (PE) and
neutral (N) conductors from the
transformer to the consuming device and
these conductors remain separated
throughout the system.
The TN-S is the most common earthing
system in the UK and one where the
electricity supply company provides an
earth terminal at the incoming mains
position
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
2. TN-S system
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
2. TN-S system
Advantages :
Concerns Electromagnetic Compatibility
The consumer has a low-noise
connection to earth and does not suffer
from the voltage that appears on the
neutral conductor as a result of the return
currents and the impedance of that
conductor
Save costs by having a fairly low-
impedance earth connection near each
consumer
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
3. TN-C-S system
Is one that uses a combined PEN
conductor between the transformer and
the building distribution point substation
and the entry point into the building and
then splits up into separate PE and N lines
within the building to fixed indoor wiring
and flexible power cords
So, it will save the cost of an additional
conductor
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
3. TN-C-S system
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TN systems
3. TN-C-S system
The use of TN-C-S is not recommended
for locations such as petrol stations etc.,
where there is a combination of lots of
buried metalwork and explosive gases.
Owing to the possibility of a lost neutral,
the use of TN-C-S supplies is banned for
caravans and boats in the UK and it is
often recommended to make outdoor
wiring TT with a separate rod.
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TT systems
Is one which has one point of the energy
source directly earthed and the exposed
conductive parts of the consumers
installation are provided with a local
connection to earth, independent of any
earth connection at the generator.
TT systems (similar to TN-S systems)
have a low-noise connection to earth,
which is particularly important with some
types of telecommunication and
measurement equipment.
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TT systems
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
TT systems
This type of installation is usually found in
rural locations where the system is not
provided with an earth terminal by the
electricity supply company and the
installation is fed from an overhead supply
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
IT systems
Is one which has no direct connection
between live parts and earth and where
the exposed conductive parts of the
electrical installation are earthed
The supply earthing in an IT system can
either be from an unearthed supply or one
which is connected to earth through a
current-limiting impedance.
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
IT systems
Perancangan Sistem Listrik Industri TEE 542
Types of Earthing System
IT systems
This lack of earth will usually mean that
normal protective methods cannot be used
For this reason, IT systems are not
normally allowed in the UK public supply
system
Except for hospitals and other medical
locations where they are recommended for
use with circuits supplying medical
equipment intended for life-support of
patients.
Perancangan Sistem Listrik Industri TEE 542
References . . .
http://www.csanyigroup.com/grounded-or-
ungrounded-systems diakses 19-05-2013
jam 19.00 WIB
http://www.postglover.com/lowresistance.h
tml diakses 19-05-2013 jam 19.10 WIB
Shoaib Khan. 2007. Industrial Power
Systems. London & New York : CRC
Press & Taylor and Francis Group
Ray Tricker. 2008. Wiring Regulations in
Brief. UK: Elsevier Ltd