Preface, Contents

Product Overview

Configuration and Elements of


Function Block Diagram

Addressing

Bit Logic Instructions

Timer Instructions

Counter Instructions

Integer Math Instructions

Floating-Point Math Instructions

This reference manual is part of the documentation


package with the order number:

Comparison Instructions

6ES7810-4CA04-8BR0

Move and Conversion


Instructions

10

Word Logic Instructions

11

Shift and Rotate Instructions

12

Data Block Instructions

13

Jump Instructions

14

Status Bit Instructions

15

Program Control Instructions

16

SIMATIC S7
Function Block Diagram (FBD)
for S7-300 and S7-400
Programming
Reference Manual

10/98
C79000-G7076-C566
Release 01

Appendix
Glossary, Index

Safety Guidelines

This manual contains notices which you should observe to ensure your own personal safety, as well as to
protect the product and connected equipment. These notices are highlighted in the manual by a warning
triangle and are marked as follows according to the level of danger:

Danger
indicates that death, severe personal injury or substantial property damage will result if proper precautions
are not taken.

Warning
indicates that death, severe personal injury or substantial property damage can result if proper precautions
are not taken.

Caution
indicates that minor personal injury or property damage can result if proper precautions are not taken.

Note
draws your attention to particularly important information on the product, handling the product, or to a
particular part of the documentation.

Correct Usage

Trademarks

Note the following:

Warning
This device and its components may only be used for the applications described in the catalog or the
technical description, and only in connection with devices or components from other manufacturers which
have been approved or recommended by Siemens.

SIMATICR,
AG.

SIMATIC HMIR

and

SIMATIC NETR are registered trademarks of SIEMENS

Third parties using for their own purposes any other names in this document which refer to trademarks might
infringe upon the rights of the trademark owners.

Copyright E Siemens AG 1998 All rights reserved

Disclaimer of Liability

The reproduction, transmission or use of this document or its contents is


not permitted without express written authority. Offenders will be liable for
damages. All rights, including rights created by patent grant or registration
of a utility model or design, are reserved.

We have checked the contents of this manual for agreement with the
hardware and software described. Since deviations cannot be precluded
entirely, we cannot guarantee full agreement. However, the data in this
manual are reviewed regularly and any necessary corrections included in
subsequent editions. Suggestions for improvement are welcomed.

Siemens AG
Bereich Automatisierungs- und Antriebstechnik
Geschaeftsgebiet Industrie-Automatisierungssysteme
Postfach 4848, D-90327 Nuernberg

E Siemens AG 1998
Technical data subject to change.

Siemens Aktiengesellschaft

C79000-G7076-C566

Function Block Diagram (FBD) for S7-300 and S7-400

Preface

Purpose of the
Manual

This manual is your guide to creating user programs in the Function Block
Diagram (FBD) programming language.
This manual also includes a reference section that describes the syntax and
functions of the language elements of Function Block Diagram.

Audience

The manual is intended for S7 programmers, operators, and


maintenance/service personnel. A working knowledge of automation
procedures is essential.

Where is this
Manual Valid?

This manual is valid for release 5.0 of the STEP 7 programming software
package.

Which Standards
Does the Software
Comply With?

FBD corresponds to the Function Block Diagram language defined in the


International Electrotechnical Commissions standard IEC 1131-3. For
further details, refer to the table of standards in the STEP 7 file
NORM_TBL.WRI.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

iii

Preface

Requirements

To use this Function Block Diagram manual effectively, you should already
be familiar with the theory behind S7 programs which is documented in the
online help for STEP 7. The language packages also use the STEP 7 standard
software, so you should be familiar with handling this software and have read
the accompanying documentation.

Documentation

Purpose

STEP 7 Basic Information with

S
S
S

Basic information for technical


Working with STEP 7 V5.0, Getting Started personnel describing the methods of
implementing control tasks with
Manual
STEP 7 and the S7-300/400
Programming with STEP 7 V5.0
programmable controllers.
Configuring Hardware and Communication
Connections, STEP 7 V5.0

Order Number
6ES7810-4CA04-8BA0

S From S5 to S7, Converter Manual


STEP 7 Reference with

S Ladder Logic (LAD)/Function Block


Diagram (FBD)/Statement List (STL) for
S7-300/400 manuals

S Standard and System Functions for


S7-300/400

Online Helps

Provides reference information and


describes the programming
languages LAD, FBD and STL and
standard and system functions
extending the scope of the STEP 7
basic information.

Purpose

6ES7810-4CA04-8BA0

Order Number

Help on STEP 7

Basic information on programming


and configuring hardware with
STEP 7 in the form of an online
help.

Part of the STEP 7


Standard software.

Reference helps on STL/LAD/FBD

Context-sensitive reference
information.

Part of the STEP 7


Standard software.

Reference help on SFBs/SFCs


Reference help on Organization Blocks

Accessing the
Online Help

You can display the online help in the following ways:

S Context-sensitive help about the selected object with the menu command
Help > Context-Sensitive Help, with the F1 function key, or by clicking
the question mark symbol in the toolbar.

S Help on STEP 7 via the menu command Help > Contents.


References

iv

References to other documentation are indicated by reference numbers in


slashes /.../. Using these numbers, you can check the exact title in the
References section at the end of the manual.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Preface

SIMATIC Customer
Support Online
Services

The SIMATIC Customer Support team offers you substantial additional


information about SIMATIC products via its online services:

S General current information can be obtained:


on the Internet under
http://www.ad.siemens.de/simatic/html_00/simatic
via the Fax-Polling number 08765-93 02 77 95 00

S Current product information leaflets and downloads which you may find
useful are available:
on the Internet under http://www.ad.siemens.de/support/html_00/
via the Bulletin Board System (BBS) in Nuremberg (SIMATIC
Customer Support Mailbox) under the number +49 (911) 895-7100.
To dial the mailbox, use a modem with up to V.34 (28.8 Kbps) with
the following parameter settings: 8, N, 1, ANSI; or dial via ISDN
(x.75, 64 Kbps).

Additional
Assistance

If you have other questions, please contact the Siemens representative in your
area. The addresses are listed, for example, in catalogs and in Compuserve
(go autforum).
Our SIMATIC Basic Hotline is also ready to help:

S in Nuremberg, Germany
Monday to Friday 07:00 to 17:00 (local time): telephone:
+49 (911) 8957000
or E-mail: simatic.support@nbgm.siemens.de

S in Johnson City (TN), USA


Monday to Friday 08:00 to 17:00 (local time): telephone:
+1 423 4612522
or E-mail: simatic.hotline@sea.siemens.com

S in Singapore
Monday to Friday 08:30 to 17:30 (local time): telephone:
+65 7407000
or E-mail: simatic@singet.com.sg
The SIMATIC Premium Hotline is available round the clock worldwide
with the SIMATIC card (telephone: +49 (911) 895-7777).

Courses for
SIMATIC Products

Siemens offers a number of training courses to introduce you to the SIMATIC


S7 automation system. Please contact your regional training center or the
central training center in Nuremberg, Germany for details:
Telephone: +49 (911) 895-3154.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Preface

Questionnaires on
the Manual and
Online Help

vi

To help us to provide the best possible documentation for you and future
STEP 7 users, we need your support. If you have any comments or
suggestions relating to this manual or the online help, please complete the
questionnaire at the end of the manual and send it to the address shown.
Please include your own personal rating of the documentation.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

iii

Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1-1

Configuration and Elements of Function Block Diagram . . . . . . . . . . . . . . . . . . .

2-1

2.1

Elements and Box Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-2

2.2

Boolean Logic and Truth Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-6

2.3

Significance of the CPU Registers in Statements . . . . . . . . . . . . . . . . . . . .

2-9

Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-1

3.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-2

3.2

Types of Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-4

Bit Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-1

4.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-2

4.2

AND Logic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-3

4.3

OR Logic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-4

4.4

AND-before-OR Logic Operation and OR-before-AND Logic Operation .

4-5

4.5

Exclusive OR Logic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-6

4.6

Insert Binary Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-7

4.7

Negate Binary Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-8

4.8

Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-9

4.9

Midline Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-10

4.10

Save RLO to BR Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-11

4.11

Set Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-12

4.12

Reset Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-13

4.13

Set Counter Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-14

4.14

Up Counter Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-16

4.15

Down Counter Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-17

4.16

Pulse Timer Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-18

4.17

Extended Pulse Timer Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-20

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

vii

Contents

viii

4.18

On-Delay Timer Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-22

4.19

Retentive On-Delay Timer Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-24

4.20

Off-Delay Timer Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-26

4.21

Positive RLO Edge Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-28

4.22

Negative RLO Edge Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-29

4.23

Address Positive Edge Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-30

4.24

Address Negative Edge Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-31

4.25

Set_Reset Flip Flop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-32

4.26

Reset_Set Flip Flop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-33

Timer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-1

5.1

Memory Areas and Components of a Timer . . . . . . . . . . . . . . . . . . . . . . . . .

5-2

5.2

Choosing the Right Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-4

5.3

Pulse S5 Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-5

5.4

Extended Pulse S5 Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-7

5.5

On-Delay S5 Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-9

5.6

Retentive On-Delay S5 Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-11

5.7

Off-Delay S5 Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-13

Counter Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6-1

6.1

Memory Address and Components of a Counter . . . . . . . . . . . . . . . . . . . . .

6-2

6.2

Up-Down Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6-3

6.3

Up Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6-5

6.4

Down Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6-7

Integer Math Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-1

7.1

Add Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-2

7.2

Add Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-3

7.3

Subtract Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-4

7.4

Subtract Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-5

7.5

Multiply Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-6

7.6

Multiply Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-7

7.7

Divide Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-8

7.8

Divide Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-9

7.9

Return Fraction Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-10

7.10

Evaluating the Bits of the Status Word with Integer Math Instructions . . .

7-11

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Contents

10

Floating-Point Math Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8-1

8.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8-2

8.2

Add Real . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8-3

8.3

Subtract Real . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8-4

8.4

Multiply Real . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8-5

8.5

Divide Real . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8-6

8.6

Evaluating the Bits of the Status Word with Floating-Point Instructions . .

8-7

8.7

Forming the Absolute Value of a Floating-Point Number . . . . . . . . . . . . . .

8-8

8.8

Forming the Square (SQR) of a Floating-Point Number . . . . . . . . . . . . . . .

8-9

8.9

Forming the Square Root (SQRT) of a Floating-Point Number . . . . . . . . .

8-10

8.10

Forming the Natural Logarithm of a Floating-Point Number . . . . . . . . . . . .

8-11

8.11

Forming the Exponential Value of a Floating-Point Number . . . . . . . . . . . .

8-12

8.12

Forming Trigonometric Functions of Angles as Floating-Point Numbers .

8-13

Comparison Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-1

9.1

Compare Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-2

9.2

Compare Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-3

9.3

Compare Real . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-4

Move and Conversion Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-1

10.1

Assign Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-2

10.2

BCD to Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-3

10.3

Integer to BCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-4

10.4

Integer to Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-5

10.5

BCD to Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-6

10.6

Double Integer to BCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-7

10.7

Double Integer to Real . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-8

10.8

Ones Complement Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-9

10.9

Ones Complement Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-10

10.10

Twos Complement Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11

10.11

Twos Complement Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-12

10.12

Negate Real Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-13

10.13

Round to Double Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-14

10.14

Truncate Double Integer Part . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-15

10.15

Ceiling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-16

10.16

Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-17

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

ix

Contents

11

12

13

14

15

16

Word Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11-1

11.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11-2

11.2

(Word) AND Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11-3

11.3

(Word) AND Double Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11-4

11.4

(Word) OR Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11-5

11.5

(Word) OR Double Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11-6

11.6

(Word) Exclusive OR Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11-7

11.7

(Word) Exclusive OR Double Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11-8

Shift and Rotate Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12-1

12.1

Shift Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12-2

12.2

Rotate Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-10

Data Block Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13-1

13.1

Open Data Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13-2

Jump Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14-1

14.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14-2

14.2

Unconditional Jump in a Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14-3

14.3

Conditional Jump in a Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14-4

14.4

Jump-If-Not . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14-5

14.5

Jump Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14-6

Status Bit Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15-1

15.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15-2

15.2

Exception Bit Binary Result . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15-3

15.3

Result Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15-4

15.4

Exception Bit Unordered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15-6

15.5

Exception Bit Overflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15-7

15.6

Exception Bit Overflow Stored . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15-8

Program Control Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16-1

16.1

Calling an FC/SFC without Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16-2

16.2

Calling an FB, FC, SFB, SFC, and Multiple Instances . . . . . . . . . . . . . . . .

16-4

16.3

Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16-7

16.4

Master Control Relay Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16-8

16.5

Master Control Relay Activate/Deactivate . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-10

16.6

Master Control Relay On/Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-13

Alphabetical Lists of Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-1

A.1

A-2

List of Instructions with International Names . . . . . . . . . . . . . . . . . . . . . . . .

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Contents

A.2

List of Instructions with International (English) Names and German


Equivalents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-6

A.3

List of Instructions with German SIMATIC Names . . . . . . . . . . . . . . . . . . . .

A-10

A.4

List of Instructions with German Names and International (English)


Equivalents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-14

Programming Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-1

B.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-2

B.2

Bit Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-3

B.3

Timer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-7

B.4

Counter and Comparison Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-11

B.5

Integer Math Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-13

B.6

Word Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-14

References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C-1

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Glossary-1

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Index-1

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

xi

Contents

xii

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Product Overview

What is FBD?

FBD stands for Function Block Diagram. FBD is a graphic programming


language and uses logic boxes familiar from Boolean algebra to represent
logic. Complex functions (for example math functions) can also be
represented directly connected to the logic boxes.

The FBD
Programming
Language

The Function Block Diagram programming language has all the elements
necessary for creating a complete user program. It contains a wide range of
instructions. These include the various basic instructions and a wide range of
addresses and address types. Functions and function blocks allow you to
structure your FBD program clearly.

The Programming
Package

The FBD programming package is an integral part of the STEP 7 Standard


Software. This means that following the installation of your STEP 7 software,
all the editor functions, compiler functions, and test/debug functions for FBD
are available to you.
Using FBD, you can create your own user program. With the Incremental
Editor, the input of the local data structure is made easier with the help of
table editors.
There are three programming languages in the standard software, STL, FBD,
and LAD. You can switch from one language to the other almost without
restriction and choose the most suitable language for the particular block you
are programming.
If you write programs in LAD or FBD, you can always switch over to the
STL representation. If you convert LAD programs into FBD programs and
vice versa, program elements that cannot be represented in the destination
language are displayed in STL.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

1-1

1-2

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Configuration and Elements of Function


Block Diagram

Chapter
Overview

Page

Section

Description

2.1

Elements and Box Structure

2-2

2.2

Boolean Logic and Truth Tables

2-6

2.3

Significance of the CPU Registers in Statements

2-9

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

2-1

Configuration and Elements of Function Block Diagram

2.1

Elements and Box Structure

FBD Instructions

FBD instructions consist of elements and boxes that are connected


graphically to form networks. The elements and boxes can be classified in
the following groups:

Instructions as
Elements

STEP 7 represents some of the FBD instructions as individual elements that


do not require addresses or parameters (see Table 2-1).
Table 2-1

FBD Instruction as an Element without Address or Parameters


Element

Instruction as a
Box with Address

Section in this Manual

Negate binary input

4.7

STEP 7 represents some of the FBD instructions as boxes for which you must
specify an address (see Table 2-2). For more detailed information about
addressing, refer to Chapter 3.
Table 2-2

FBD Instruction as Box with Address


Element

<Address>

Instruction as a
Box with Address
and Value

Description

Description

Section in this Manual

Assign

4.8

STEP 7 represents some of the FBD instructions as boxes for which you
specify an address and a value (for example a timer or counter value, see
Table 2-3).
For more detailed information about addressing, refer to Chapter 3.
Table 2-3

FBD Instruction as a Box with Address and Value


Element

Description

Section in this Manual

Retentive on-delay timer

4.19

<Address>>
SS
<Time
value>

2-2

TV

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Configuration and Elements of Function Block Diagram

Instruction as Box
with Parameters

STEP 7 represents some of the FBD instructions as boxes with inputs and
outputs (see Table 2-4). The inputs are on the left of the box and the outputs
on the right. You specify the input parameters and some of the output
parameters. Most outputs are provided by the STEP 7 software. To assign
parameters, you must use the specific notation of the data types.
The parameters of the Enable input (EN) and the Enable output (ENO) are
described below. For further information about input and output parameters,
refer to the descriptions of the individual instructions in this manual.
Table 2-4

FBD Operation as a Box with Inputs and Outputs


Box

Description

Section in this Manual

Divide real

8.5

DIV_R
EN

Enable Input and


Enable Output
Parameters

IN1

OUT

IN2

ENO

If the Enable input (EN) of an FBD box is activated, the box carries out a
specific function. If the function is executed by the box without errors, the
Enable output (ENO) is activated. The parameters EN and ENO of an FBD
box are of the BOOL data type and can be located in the I, Q, M, D, or L
memory areas (see Table 2-5 and 2-6).
How EN and ENO function is described below:

S If EN is not activated (its signal state is 0), the box does not execute its
function and ENO is not activated (its signal state is also 0).

S If EN is activated (its signal state is 1) and if the box executes its function
without errors, ENO is also activated (its signal state is also 1).

S If EN is activated (its signal state is 1) and if an error occurs during the


execution of the function, ENO is not activated (its signal state remains
0).

Memory Areas and


Functions

The majority of the addresses in FBD refer to memory areas. The following
table shows the types and their functions.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

2-3

Configuration and Elements of Function Block Diagram

Table 2-5

Memory Areas and Their Functions


Access to Area

Name of Area

Function of Area

Process input
image

At the beginning of the scan cycle, the operating system reads


the inputs from the process and records the values in this area.
The program uses these values when it is running cyclically.

Using Units of the


Following Size:

Process output During the scan cycle, the program calculates output values and
image
enters them in this area. At the end of the scan cycle, the
operating system reads the calculated output values from this
area and sends them to the process outputs.

Abbr.

Input bit
Input byte
Input word
Input double word

I
IB
IW
ID

Output bit
Output byte
Output word
Output double word

Q
QB
QW
QD

Bit memory

This area provides memory space for interim results calculated Memory bit
in the program.
Memory byte
Memory word
Memory double word

M
MB
MW
MD

I/Os

Using this area, your program has direct access to input and
output modules (peripheral inputs and outputs).

Peripheral input byte


Peripheral input word
Peripheral input double
word

PIB
PIW
PID

Peripheral output byte


Peripheral output word
Peripheral output double
word

PQB
PQW
PQD

Timer (T)

Ext. inputs
I/Os:
Ext. outputs
Timers

Timers are function elements in FBD. This area provides


memory space for timer cells. In this area, the clock timing
accesses the timer cells and updates them by decrementing the
timer value. Timer operations access these timer cells.

Counters

Counters are function elements in FBD. This area provides


Counter (C)
memory space for counters. Count instructions access the cells
in this area.

Data block

This area contains data that can be accessed from within any
block. If it is necessary to open two data blocks at the same
time, you can open one with the OPN DB instruction and the
other with the OPN DI instruction. The notation of the
addresses, for example L DBWi and L DIWi identifies the data
block to be accessed.
Although you can access any data block with the OPN DI
i
instruction,
i
this
hi iinstruction
i iis mainly
i l used
d to open iinstance ddata
blocks that are assigned to function blocks (FBs) and system
function blocks (SFBs). For more detailed information about
FBs and SFBs, refer to the STEP 7 Online Help.

Data block opened with


the OPN DB
instruction:
Data bit
Data byte
Data word
Data double word

DBX
DBB
DBW
DBD

Data block opened with


the OPN DI
instruction:
Data bit
Data byte
Data word
Data double word

DIX
DIB
DIW
DID

This area contains temporary local data belonging to a logic


block (FB or FC). This type of data is also called dynamic local
data. This area is used as a buffer. When the logic block is
closed, the data are lost. These data are located in the local data
stack (L stack).

Temporary local data bit


Temporary local data
byte
Temporary local data
word
Temporary local data
double word

Local data

2-4

L
LB
LW
LD

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Configuration and Elements of Function Block Diagram

Table 2-6 lists the maximum address ranges for the various memory areas.
For more detailed information about the address ranges on your CPU, refer to
the corresponding manual /70/ or /101/.
Table 2-6

Memory Areas and Their Address Ranges


Access Using

Name of Area

Units of the Following Sizes:

Abbr.

M i
Maximum
Address
Add
Range
R

Process input image Input bit


Input byte
Input word
Input double word

I
IB
IW
ID

0.0 to 65 535.7
0 to 65 535
0 to 65 534
0 to 65 532

Process output
image

Output bit
Output byte
Output word
Output double word

Q
QB
QW
QD

0.0 to 65 535.7
0 to 65 535
0 to 65 534
0 to 65 532

Bit memory

Memory bit
Memory byte
Memory word
Memory double word

M
MB
MW
MD

0.0 to 255.7
0 to 255
0 to 254
0 to 252

I/Os:
External inputs

Peripheral input byte


Peripheral input word
Peripheral input double word

PIB
PIW
PID

0 to 65 535
0 to 65 534
0 to 65 532

I/Os:
External outputs

Peripheral output byte


Peripheral output word
Peripheral output double word

PQB
PQW
PQD

0 to 65 535
0 to 65 534
0 to 65 532

Timers

Timer

0 to 255

Counters

Counter

0 to 255

Data block

Data block opened with the DB [OPN]


instruction
DBX
DBB
DBW
DBD

0.0 to 65 535.7
0 to 65 535
0 to 65 534
0 to 65 532

Data bit in the instance DB


Data byte
Data word
Data double word

DIX
DIB
DIW
DID

0.0 to 65 535.7
0 to 65 535
0 to 65 534
0 to 65 532

Temporary local data bit


Temporary local data byte
Temporary local data word
Temporary local data double word

L
LB
LW
LD

0.0 to 65 535.7
0 to 65 535
0 to 65 534
0 to 65 532

Data bit in the data block


Data byte
Data word
Data double word
Data block opened with the DI [OPN] instruction

Local data 1)

1)

With FBD instructions, you can only use an address in the L memory area when
you declare it as VAR_TEMP in the variable declaration table.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

2-5

Configuration and Elements of Function Block Diagram

2.2

Boolean Logic and Truth Tables

Boolean Logic

The FBD programming language is based on the binary logic of Boolean


algebra in which variables can adopt the values true (1) or false (0).
Each logic instruction checks the signal state of a variable for 1 (true,
satisfied) or 0 (false, not satisfied) and then produces a result. The instruction
then either saves the result or uses it to perform a Boolean logic operation.
The result of the logic operation is known as the RLO.
To represent the logic, the logic boxes known from Boolean algebra are used.
The results of the logic instructions for all possible combinations of logical
variables are listed in truth tables.
The rules of Boolean logic are illustrated below based on the AND, OR, and
exclusive OR logic operations.

AND Logic
Operation

In an AND logic operation, the signal states of two or more specified


addresses are checked. If the signal state of the address is 1 the condition is
satisfied and the instruction produces the result 1. If the signal state of the
address is 0, the condition is not satisfied and the operation produces the
result 0.
Figure 2-1 illustrates an AND logic operation in the FBD programming
language.

The condition is satisfied when the


signal state is 1 at inputs I1.0 AND
I1.1.

&
I1.0
I1.1
Figure 2-1

Q4.0
=
AND Logic Operation in FBD

The possible results of an AND logic operation can be represented in a truth


table. Here, 1 means satisfied and 0 means not satisfied. The possible
logic instructions and their results are shown in Table 2-7.
Table 2-7

AND Truth Table

If the result of the signal and the result of the signal the result of the logic instruction is as follows:
state check at address I1.0 state check at address I1.1
is as below
is as below

2-6

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Configuration and Elements of Function Block Diagram

OR Logic
Operation

In an OR logic operation, the signal states of two or more specified addresses


are checked. If the signal state of one of the addresses is 1, the condition is
satisfied and the instruction provides the result 1. If the signal state of all
addresses is 0, the condition is not satisfied and the instruction produces the
result 0.
Figure 2-2 shows an OR logic operation in the FBD programming language.

>=1
Q4.0
=

I1.0
I1.1

Figure 2-2

The condition is satisfied when the


signal state is 1 at inputs I1.0 OR
I1.1.

OR Logic Operation in FBD

The possible results of an OR logic operation can be shown in a truth table.


Here, 1 means satisfied and 0 means not satisfied. The possible logic
operations and their results are shown in Table 2-8.
Table 2-8

Exclusive OR
Logic Operation

OR Truth Table

If the result of the signal state check at address I1.0 is as below

and the result of the


the result of the logic instruction
is as follows:
signal state check at
address I1.1 is as below

In an exclusive OR logic operation, the signal states of two or more specified


addresses are checked. If the signal state of one of the addresses is 1 the
condition is satisfied and the instruction provides the result 1. If the signal
state of all addresses is 0 or 1, the condition is not satisfied and the
instruction produces the result 0.
Figure 2-3 shows an exclusive OR logic operation in the FBD programming
language.

XOR
Q4.0
=

I1.0
I1.1

Figure 2-3

The condition is satisfied when the


signal state is 1 at input I1.0 OR at
input I1.1 exclusively (i.e. not at
both).

Exclusive OR Logic Operation in FBD

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

2-7

Configuration and Elements of Function Block Diagram

The possible results of an exclusive OR logic operation can be represented in


a truth table. Here, 1 means satisfied and 0 means not satisfied. The
possible logic operations and their results are shown in Table 2-9.
Table 2-9

Exclusive OR Truth Table

and the result of the


the result of the logic instruction
If the result of the
signal state check at
is as follows:
signal state check at
address I1.0 is as below address I1.1 is as below

2-8

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Configuration and Elements of Function Block Diagram

2.3

Significance of the CPU Registers in Statements

Explanation

Registers help the CPU perform logic, math, shift, or conversion instructions.
These registers are described below.

Accumulators

The accumulators are general-purpose registers that you use to process bytes,
words, and double-words. The accumulators are 32-bits wide.

31

24

23

High byte

16

8 7

Low byte

High word
Figure 2-4

15
High byte

0
Low byte

Low word

Accumulator (1 or 2)

Areas of an Accumulator

Status Word

The status word contains bits that you can reference in the address of bit
logic instructions. The following sections explain the significance of bits
0 through 8.
215...

Figure 2-5

Changes in the
Bits of the Status
Word

...29

28

27

26

25

BR

CC1

CC0

OV

24
OS

23

22

21

20

OR

STA

RLO FC

Structure of the Status Word

Value

Meaning

Sets the signal state to 0

Sets the signal state to 1

Changes the state

State remains unchanged

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

2-9

Configuration and Elements of Function Block Diagram

First Check

Bit 0 of the status word is called the first-check bit (FC bit, see Figure 2-5).
At the start of an FBD network, the signal state of the FC bit is always 0,
unless the previous network ended with the SAVE box
Each logic instruction checks the signal state of the FC bit as well as the
signal state of the contact that the instruction addresses. The signal state of
the FC bit determines the sequence of a logic string. If the FC bit is 0 (at the
start of an FBD network), the instruction stores the result in the result of
logic operation bit (RLO) of the status word and sets the FC bit to 1. This is
known as the first check. The 1 or 0 that is set in the RLO bit after the first
check is then referred to as the result of first check.
If the signal state of the FC bit is 1, an instruction then combines the result of
its signal state check at the addressed contact with the RLO formed at the
addressed contact after the first check, and sets the result in the RLO bit.
A logic string made up of FBD instructions always ends with an output
instruction (for example set output, reset output, assign) or with a jump
instruction dependent on the result of the logic operation (RLO). These
instructions reset the FC bit to 0.

Result of Logic
Operation

Bit 1 of the status word is called the result of logic operation bit (RLO bit,
see Figure 2-5). This bit stores the result of a string of logic instructions or
compare instructions. The signal state of the RLO bit provides information
about signal flow.
The first instruction in an FBD network checks the signal state of an address
and produces a result of 1 or 0. The instruction enters the result of this signal
state in the RLO bit. The second instruction in a string of logic operations
also checks the signal state of an address and produces a result. The
instruction now combines this result with the value of the RLO bit of the
status word according to the rules of Boolean logic (see First Check above).
The result of the logic operation is entered in the RLO bit of the status word
and replaces the previous value in the RLO bit. Each subsequent instruction
in the string of logic operations combines two values: the result of the signal
check at the specified address and the current RLO.
You can, for example, assign the state of a bit memory location to the RLO
during a first check using a Boolean logic operation or trigger a jump
instruction.

2-10

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Configuration and Elements of Function Block Diagram

Status Bit

Bit 2 of the status word is called the status bit (STA bit, see Figure 2-5). The
status bit stores the value of a bit that is referenced. The status of a logic
instruction that reads memory is always the same as the value of the bit that
this instruction checks (the bit on which it performs its logic operation). The
status of a bit instruction that writes to memory (Set Output, Reset Output, or
Assign) is the same as the value of the bit to which the instruction writes. If
no writing takes place, the value is the same as the value of the bit that the
instruction references. The status bit has no significance for bit instructions
that do not access memory. These instructions set the status bit to 1 (STA=1).
The status bit is not checked by an instruction. It is interpreted during
program test (program status) only.

OR Bit

Bit 3 of the status word is called the OR bit (see Figure 2-5). The OR bit is
required to execute an AND before OR logic operation. An AND logic
operation can contain the instructions AND input and AND NOT input. The
OR bit indicates to the instructions that a previously executed AND logic
operation produced the value 1 so that the result of the OR logic operation
has already been determined. Any other bit-processing instruction resets the
OR bit.

Overflow Bit

Bit 5 of the status word is called the overflow bit (OV bit, see Figure 2-5).
The OV bit indicates an error. It is set by a math instruction or a compare
floating-point numbers instruction after an error has occurred (overflow,
illegal instruction, illegal floating-point number). The bit is set or reset
according to the result of the math or compare instruction (error).

Stored Overflow
Bit

Bit 4 of the status word is called the store overflow bit (OS bit, see Figure
2-5). The OS bit is set together with the OV bit when an error occurs. Since
the OS bit is unchanged when math instructions are executed without errors
(in contrast to the OV bit), this indicates whether or not an error occurred in
one of the previously executed instructions. The following instructions reset
the OS bit: JOS (jump if stored overflow bit = 1, must be programmed in
STL), block calls and block end statements.

CC1 and CC0

Bits 7 and 6 of the status word are called condition code 1 and condition
code 0 (CC1 and CC0, see Figure 2-5). The CC1 and CC0 bits provide
information about the following results or bits:

S Result of a math instruction


S Result of a compare instruction
S Result of a digital instruction
S Bits that have been shifted out of the address by a shift or rotate
instruction.
Tables 2-10 to 2-15 list the meaning of CC1 and CC0 after your program has
executed certain instructions.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

2-11

Configuration and Elements of Function Block Diagram

Table 2-10

CC1 and CC0 after Math Instructions, without Overflow

CC1

CC0

Explanation

Result = 0

Result < 0

Result > 0

Table 2-11

CC1 and CC0 after Integer Math Instructions, with Overflow

CC1

CC0

Explanation

Negative range overflow in Add Integer and Add Double Integer

Negative range overflow in Multiply Integer and Multiply


Double Integer
Positive range overflow in Add Integer, Subtract Integer, Add
Double Integer, Subtract Double Integer, Twos Complement
Integer, and Twos Complement Double Integer

Positive range overflow in Multiply Integer and Multiply Double


Integer, Divide Integer, and Divide Double Integer
Negative range overflow in Add Integer, Subtract Integer, Add
Double Integer, and Subtract Double Integer

Division by 0 in Divide Integer, Divide Double Integer, and


Return Fraction Double Integer

Table 2-12

2-12

CC1 and CC0 after Floating-Point Math Instructions, with Overflow

CC1

CC0

Gradual underflow

Negative range overflow

Positive range overflow

Not a valid floating-point number

Explanation

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Configuration and Elements of Function Block Diagram

Table 2-13

CC1 and CC0 after Comparison Instructions

CC1

CC0

IN2 = IN1

IN2 < IN1

IN2 > IN1

IN1 or IN2 is not a valid floating-point number

Table 2-14

CC1 and CC0 after Shift and Rotate Instructions

CC1

CC0

Bit shifted out last = 0

Bit shifted out last = 1

Table 2-15

Binary Result Bit

Explanation

Explanation

CC1 and CC0 after Word Logic Instructions

CC1

CC0

Explanation
Result = 0

Result <> 0

Bit 8 of the status word is called the binary result bit (BR bit, see Figure 2-5).
The BR bit forms a link between the processing of bits and words. This bit is
an efficient method with which you can interpret the result of a word
instruction as a binary result and include this result in a binary string of logic
operations. The BR bit represents an internal memory bit in which the RLO
can be saved prior to a word instruction that changes the RLO so that the old
RLO is available again after the operation when the interrupted series of bit
instructions is resumed.
With the BR bit, you can, for example, program a function block (FB) or a
function (FC) in Statement List (STL) and call the FB or FC in FBD.
If you write a function block or a function that you want to call in FBD,
regardless of whether you write the FB or FC in STL or FBD, you must take
into account the BR bit. The BR bit corresponds to the Enable output (ENO)
of an FBD box. You save the RLO in the BR bit using the SAVE instruction
(in STL) or with the SAVE FBD box according to the following criteria:

S Save an RLO of 1 in the BR bit when the FB or FC is processed without


errors.

S Save an RLO of 0 in the BR bit if an error occurs during the processing of


an FB or FC.
Program these instructions at the end of the FB or FC so that they are the last
instructions executed in the block.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

2-13

Configuration and Elements of Function Block Diagram

Meaning of
EN/ENO

Warning
The BR bit can be reset to 0 unintentionally.
When you write FBs or FCs in FBD and do not handle the BR bit as
described above, an FB or FC might overwrite the BR bit of another FB or
FC.
To avoid this problem, save the RLO at the end of each FB or FC as
described above.

The Enable input (EN) and Enable output (ENO) parameters of an FBD box
function as explained below:

S If EN is not activated (its signal state is 0), the box does not execute its
function and ENO is not activated (it also has a signal state of 0).

S If EN is activated (its signal state is 1) and the box executes its function
without errors, ENO is also activated (its signal state is also 1).

S If EN is activated (its signal state is 1) and an error occurs while the


function is being executed, ENO is not activated (its signal state is 0).
When you call a system function block (SFB) or a system function (SFC) in
your program, the SFB or SFC indicates whether or not the CPU executed the
function without errors by setting the signal state of the BR bit:

S If an error occurred during execution, the BR bit is set to 0.


S If the function was executed without errors, the BR bit is 1.

2-14

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Addressing
Chapter
Overview

Section

Description

Page

3.1

Overview

3-2

3.2

Types of Addresses

3-4

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

3-1

Addressing

3.1

Overview

What is
Addressing?

Many FBD instructions operate with one or more addresses. The address
specifies a constant or a location at which the instruction finds a variable
which it uses to perform a logic operation. This location can be a bit, byte,
word, or double word.
Examples of possible addresses are as follows:

S A constant, the value of a timer or counter, or an ASCII character string


S A bit in the status word of the programmable controller
S A data block and a location within the data block area
Immediate and
Direct Addressing

The following types of addressing are available:

S Immediate addressing (specifying a constant as the address)


S Direct addressing (specifying a variable as the address)
Figure 3-1 shows an example of immediate and direct addressing.
The function of the box is to compare two input parameters (in this case, two
16-bit integers) to see if the first input is less than or equal to the second. The
constant 50 is entered as input parameter IN1. Memory word MW200, a
location in memory, is entered as input parameter IN2.
Because the constant 50 in the example is the actual value with which IN1 of
the box will work, 50 is an immediate address of the instruction box. Because
MW200 points to a location in memory where there is another value with
which IN2 of the box will work, MW200 is a direct address. MW200 is a
location, not the actual value itself.

CMP
<= I

Figure 3-1

3-2

50

IN1

MW200

IN2

Immediate and Direct Addressing

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Addressing

Table 3-1

Constant Formats for Immediate Addressing Using Addresses of Elementary Data Types

Size in Format Options


Type and
Description Bits

Range and Number Notation


(Lowest Value to Highest Value)

Example

BOOL
(Bit)

Boolean Text

TRUE/FALSE

TRUE

BYTE
(Byte)

Hexadecimal

B#16#0 to B#16#FF

B#16#10
byte#16#10

WORD
(Word)

16

Binary

2#0001_0000_0000_0000

Hexadecimal

2#0 to
2#1111_1111_1111_1111
W#16#0 to W#16#FFFF

BCD
Unsigned decimal

C#0 to C#999
B#(0,0) to B#(255,255)

Binary

2#0 to
2#1111_1111_1111_1111_
1111_1111_1111_1111
DW#16#0000_0000 to
DW#16#FFFF_FFFF
B#(0,0,0,0) to
B#(255,255,255,255)

2#1000_0001_0001_1000_
1011_1011_0111_1111

DWORD
(Double
word)

32

Hexadecimal
Unsigned decimal

W#16#1000
word16#1000
C#998
B#(10,20)
byte#(10,20)

DW#16#00A2_1234
dword#16#00A2_1234
B#(1,14,100,120)
byte#(1,14,100,120)

INT
(Integer)

16

Signed decimal

-32768 to 32767

DINT
(Double
integer)

32

Signed decimal

L#-2147483648 to L#2147483647

L#1

REAL
(Floating
point)

32

IEEE
floating point

Upper limit: 3.402823e+38


Lower limit: 1.175495e-38 )

1.234567e+13

S5TIME
(SIMATIC
time)

16

S5 Time in
10-ms units (as
default value)

S5T#0H_0M_0S_10MS to
S5T#2H_46M_30S_0MS and
S5T#0H_0M_0S_0MS

S5T#0H_1M_0S_0MS
S5TIME#0H_1M_0S_0MS

TIME
(IEC time)

32

IEC time in 1-ms


units, signed
integer

T#-24D_20H_31M_23S_648MS to
T#24D_20H_31M_23S_647MS

T#0D_1H_1M_0S_0MS
TIME#0D_1H_1M_0S_0MS

DATE
(IEC date)

16

IEC date
in 1-day units

D#1990-1-1 to
D#2168-12-31

D#1994-3-15
DATE#1994-3-15

TIME_OF_
DAY
(Time of
day)

32

Time of day in
1-ms units

TOD#0:0:0.0 to
TOD#23:59:59.999

TOD#1:10:3.3
TIME_OF_DAY#1:10:3.3

CHAR
(Character)

Character

A,B, etc.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

3-3

Addressing

3.2

Types of Addresses

Possible
Addresses

One of the following elements can be used as the address of an FBD


instruction:

S A bit whose signal state will be checked


S A bit to which the signal state of the logic operation string will be
assigned

S A bit to which the result of logic operation (RLO) will be assigned


S A bit that will be set or reset
S A number that indicates a counter that will be incremented or
decremented

S A number that indicates a timer to be used


S An edge memory bit that saves the previous RLO
S An edge memory bit that saves the previous signal state of a different
address

S A byte, word, or double word containing a value with which the FBD
element or box will work

S The number of a data block (DB or DI) that will be opened or created
S The number of a function (FC), system function (SFC), a function block
(FB), or system function block (SFB) that will be called

S A label as the destination for a jump


Address Identifiers

Variables as addresses consist of an address identifier and an address within


the memory area indicated by the address identifier. An address identifier can
be one of the following two basic types:

S An address identifier that indicates the following two data objects:


The memory area in which the instruction finds a value (data object)
with which it can perform a logic operation (for example I for
process input image, see Table 2-5).
The size of a value (data object) with which the instruction will
perform a logic operation (for example B for Byte, W for Word
and D for Double Word, see Table 2-5).

S An address identifier that indicates a memory area but not the size of the
data object in the area (for example an identifier for the T area (timers), C
(counters), or DB or DI (data block) and the number of the timer, counter,
or data block, see Table 2-5).

3-4

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Addressing

Pointers

A pointer identifies the location of a variable. A pointer contains an address


instead of a value. When assigning an actual parameter for the parameter
type Pointer, you provide the memory address. With STEP 7, you can enter
the pointer either in the pointer format or simply as an address (for example
M 50.0). The following example illustrates the pointer format for accessing
data starting at M 50.0.
P#M50.0

Working with
Words or Double
Words as the Data
Object

If you are working with an instruction whose address identifier indicates a


memory area of your programmable controller and a data object that is either
a word or double word in size, remember that the memory location is always
referenced as a byte address. This byte address is the smallest byte number or
the number of the high byte within the word or double word. The address in
the instruction shown in Figure 3-2, for example, references four successive
bytes in the memory area M starting at byte 10 (MB10) through to byte 13
(MB13).

Instruction: L MD10
Address identifier

Figure 3-2

Byte address

Example of a Memory Location Referenced as a Byte Address

Figure 3-3 shows data objects with the following sizes:

S Double word: memory double word MD10


S Word: memory word MW10, MW11 and MW12
S Byte: memory bytes MB10, MB11, MB12 and MB13
If you use absolute addresses that are a word or double word long, make sure
that you avoid any overlapping byte assignments.

MW10
MB10

MW12
MB11

MB12

MB13

MW11
MD10
Figure 3-3

Referencing a Memory Location as a Byte Address

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

3-5

Addressing

3-6

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions


Chapter
Overview

Section

Description

Page

4.1

Overview

4-2

4.2

AND Logic Operation

4-3

4.3

OR Logic Operation

4-4

4.4

AND-before-OR Logic Operation and OR-before-AND


Logic Operation

4-5

4.5

Exclusive OR Logic Operation

4-6

4.6

Insert Binary Input

4-7

4.7

Negate Binary Input

4-8

4.8

Assign

4-9

4.9

Midline Output

4-10

4.10

Save RLO to BR Memory

4-11

4.11

Set Output

4-12

4.12

Reset Output

4-13

4.13

Set Counter Value

4-14

4.14

Up Counter Instruction

4-16

4.15

Down Counter Instruction

4-17

4.16

Pulse Timer Instruction

4-18

4.17

Extended Pulse Timer Instruction

4-20

4.18

On-Delay Timer Instruction

4-22

4.19

Retentive On-Delay Timer Instruction

4-24

4.20

Off-Delay Timer Instruction

4-26

4.21

Positive RLO Edge Detection

4-28

4.22

Negative RLO Edge Detection

4-29

4.23

Address Positive Edge Detection

4-30

4.24

Address Negative Edge Detection

4-31

4.25

Set_Reset Flip Flop

4-32

4.26

Reset_Set Flip Flop

4-33

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-1

Bit Logic Instructions

4.1

Overview

Explanation

Bit logic instructions work with two digits, 1 and 0. These two digits form
the base of a number system called the binary system. The two digits 1 and 0
are called binary digits or simply bits. In conjunction with AND, OR, XOR
and outputs, a 1 stands for logical YES and a 0 for logical NO.
The bit logic instructions interpret the signal states 1 and 0 and combine
them according to the rules of Boolean logic. These combinations produce a
result of 1 or 0 known as the result of logic operation (RLO, see Section 2.2).
The logic operations triggered by the bit logic instructions execute a variety
of functions.

Functions

Bit logic instructions are available for the following functions:

S AND, OR, and XOR: these instructions check the signal state and
produce a result that is either copied to the RLO bit or combined with it.
With AND logic operations, the result of the signal state check is
combined according to the AND truth table (see Table 2-7). With OR
logic operations, the result of the signal state check is combined
according to the OR truth table (see Table 2-8), with exclusive OR logic
operations, according to the exclusive OR truth table (see Table 2-9).

S Assign and Midline Output: these instructions assign the RLO or store it
temporarily.

S The following instructions react to an RLO of 1:


Set Output and Reset Output
Set_Reset Flip Flop and Reset_Set Flip Flop

S Some instructions react to a rising or falling edge so that you can execute
the following functions:
Increment or decrement the value of a counter
Start a timer
Produce an output of 1

S The remaining instructions affect the RLO directly in the following ways:
Negate the RLO
Save the RLO in the binary result bit of the status word
In this chapter, the counter and timer instructions are shown in the
international and SIMATIC forms.

4-2

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

4.2

AND Logic Operation

Description

With the AND instruction, you can check the signal states of two or more
specified addresses at the inputs of an AND box.
If the signal state of all addresses is 1, the condition is satisfied and the
instruction provides the result 1. If the signal state of an address is 0, the
condition is not satisfied and the instruction produces the result 0.
If the AND instruction is the first instruction in a string of logic operations, it
saves the result of its signal state check in the RLO bit.
Every AND instruction that is not the first instruction in the string of logic
operations, combines the result of its signal state check with the value stored
in the RLO bit. These values are combined according to the AND truth table.

Table 4-1

AND Box and Parameters


Parameters

FBD Box
<address>
<address>

Data Type

<address>

BOOL
TIMER
COUNTER

&

Memory Area

Description

I, Q, M, T, C, D, L

The address indicates the bit whose


signal state will be checked.

&

I0.0

Q4.0
=

I0.1

Output Q4.0 is set when the signal state is 1 at input


I0.0 AND I0.1.

Status Word Bits

writes
Figure 4-1

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

AND Logic Operation

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-3

Bit Logic Instructions

4.3

OR Logic Operation

Description

With the OR instruction, you can check the signal states of two or more
specified addresses at the inputs of an OR box.
If the signal state of one of the addresses is 1, the condition is satisfied and
the instruction produces the result 1. If the signal state of all addresses is 0,
the condition is not satisfied and the instruction produces the result 0.
If the OR instruction is the first instruction in a string of logic operations, it
saves the result of its signal state check in the RLO bit.
Each OR instruction that is not the first instruction in the string of logic
operations combines the result of its signal state check with the value stored
in the RLO bit. These values are combined according to the OR truth table.

Table 4-2

OR Box and Parameters


Parameters

FBD Box
<address>
<address>

Data Type

<address>

BOOL
TIMER
COUNTER

>=1

Memory Area

Description

I, Q, M, T, C, D, L

The address specifies the bit whose


signal state will be checked

>=1

I0.0

Q4.0
=

I0.1

Output Q4.0 is set when the signal state is 1 at input I0.0 OR at input
I0.1.

Status Word Bits

writes
Figure 4-2

4-4

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

OR Logic Operation

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

4.4

AND-before-OR Logic Operation and OR-before-AND Logic


Operation

Description

With the AND-before-OR instruction, you can check the result of a signal
state according to the OR truth table.
With an AND-before-OR logic operation the signal state is 1 when at least
one AND logic operation is satisfied.

&

I0.0
I0.1

The signal state is 1 at output Q3.1 when


at least one AND logic operation is satisfied.

>=1

The signal state is 0 at output Q3.1 when


no AND logic operation is satisfied.

&

I0.2

Q3.1
=

I0.3

Status Word Bits

writes
Figure 4-3

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

AND-before-OR Logic Operation

Description

With the OR-before-AND instruction, you can check the result of a signal
state check according to the AND truth table.
With an OR-before-AND logic operation the signal state is 1 when all OR
logic operations are satisfied.

I1.0

>=1

I1.1

The signal state is 1 at output Q3.1 when


both OR logic operations are satisfied.

&

The signal state is 0 at output Q3.1 when


at least one OR logic operation is not satisfied.

>=1

I1.2

Q3.1
=

I1.3

Status Word Bits

writes
Figure 4-4

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

OR-before-AND Logic Operation

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-5

Bit Logic Instructions

4.5

Exclusive OR Logic Operation

Description

With the Exclusive OR instruction, you can check the result of a signal state
check according to the Exclusive OR truth table.
With an Exclusive OR logic operation, the signal state is 1 when the signal
state of one of the two specified addresses is 1.

Table 4-3

Exclusive OR Box and Parameters

FBD Box

Parameters

Data Type

<address>
<address>
<address>

BOOL
TIMER
COUNTER

XOR

Q3.1
=

I0.2

Description

I, Q, M, T, C, D, L

The address specifies the bit whose


signal state will be checked.

The signal state is 1 at output Q3.1 when the signal state is 1 at


either input I0.0 OR at input I0.2 (exclusively, in other
words not at both).

XOR
I0.0

Memory Area

Status Word Bits

writes

Figure 4-5

4-6

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Exclusive OR Logic Operation

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

4.6

Insert Binary Input

Description

Table 4-4

The Insert Binary Input instruction inserts a further binary input to an AND,
OR, or XOR box.
Binary Input Element and Parameters
Parameters

FBD Element

<address>

<address>

I1.0
I1.1
I1.2

Data Type
BOOL
TIMER
COUNTER

Memory Area

Description

I, Q, M, T, C, D, L

The address specifies the bit whose


signal state will be checked

Output Q4.0 is 1 when the signal state at


I1.0 AND I1.1 AND I1.2 is 1.

&
Q4.0
=

Status Word Bits

writes
Figure 4-6

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Insert Binary Input

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-7

Bit Logic Instructions

4.7

Negate Binary Input

Description

The Negate Binary Input instruction negates the RLO.


When you negate the result of logic operation, you must remember certain
rules:

S If the result of logic operation at the first input of an AND or OR box is


negated, there is no nesting.

S If the result of logic operation is negated but not at the first input of an
OR box, the entire binary logic operation before the input is included in
the OR logic operation.

S If the result of logic operation is negated but not at the first input of a
AND box, the entire binary logic operation before the input is included in
the AND logic operation.
Table 4-5

Negate Binary Input Element

FBD Element

Parameters

Data Type

None

I1.0
I1.1

I1.2
I1.3

Memory Area

Description

Output Q4.0 is 1 when:

&

the signal state at I1.0 AND I1.1 is NOT 1


&

AND the signal state at I1.2 AND I1.3 is NOT 1


OR the signal state at I1.4 is NOT 1.

&
>=1
Q4.0
=

I1.4

Status Word Bits

writes
Figure 4-7

4-8

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Negate Binary Input

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

4.8

Assign

Description

The Assign instruction produces the result of logic operation. The box at the
end of a logic operation has the signal 1 or 0 according to the following
criteria:

S The output has the signal 1 when the conditions of the logic operation
before the output box are satisfied

S The output has the signal 0 when the conditions of the logic operation
before the output box are not satisfied.
The FBD logic operation assigns the signal state to the output that is
addressed by the instruction (to achieve the same effect, the signal state of
the RLO bit could also be assigned to the address). If the conditions of the
FBD logic operations are satisfied, the signal state at the output box is 1.
Otherwise the signal state is 0. The Assign instruction is influenced by the
Master Control Relay (MCR).
For more detailed information about the functions of the MCR, refer to
Section 16.4.
You can only place the Assign box at the right-hand end of the string of logic
operations. You can, however, use several Assign boxes.
You can create a negated assignment with the Negate Input instruction.
Table 4-6

Assign Box and Parameters


Parameters

FBD Box
<address>
=

I0.0

<address>

Data Type
BOOL

&

I0.1

Memory Area
I, Q, M, D, L

Description
The address specifies the bit to which
the signal state of the string of logic
operations is assigned.

The signal state at output Q4.0 is 1 when the signal


state is 1 at inputs I0.0 AND I0.1, OR I0.2 is 0.
>=1

I0.2

Q4.0
=
Status Word Bits

writes
Figure 4-8

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Assign

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-9

Bit Logic Instructions

4.9

Midline Output

Description

The Midline Output instruction is an intermediate element that buffers the


RLO. More precisely, this element buffers the bit logic operation of the last
branch to be opened before the Midline Output.
The Midline Output instruction is influenced by the Master Control Relay
(MCR). For more information about the MCR functions, see Section 16.4.
You can create a negated Midline Output by negating the input of the
Midline Output.

Table 4-7

Midline Output Box and Parameters


Parameters

FBD Box
<address>
#

<address>

Data Type
BOOL

Memory Area
I, Q, M, D,

Description

L1

The address specifies the bit to


which the RLO will be assigned.

With the Connector instruction you can only use an address in the L memory area if you declare the address in
VAR_TEMP; you cannot use the L memory area for absolute addresses.

I1.0
I1.1
I1.2
I1.3

M0.0
#

&

M1.1
#

&

&

>=1
DB5.DBX3.2
#

M2.2
#

I1.4

Q4.0
=

The Midline Outputs buffer the following results of the logic operations:
M0.0 buffers the negated

&

RLO of

I1.0
I1.1

M2.2 the RLO of

I1.4

M1.1 the negated

I1.2
I1.3

RLO of

&

DB5.DBX3.2 the negated RLO of the entire


bit logic operation in bit 2 of the 3rd bytes in DB 5.

Status Word Bits

writes
Figure 4-9

4-10

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Midline Output

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

4.10 Save RLO to BR Memory

Description

The Save RLO to BR Memory instruction saves the RLO in the BR bit of the
status word. The first check bit FC is not reset.
For this reason, if there is an AND logic operation in the next network, the
state of the BR bit is included in the logic operation.
Using the Save RLO to BR Memory instruction in conjunction with
checking the BR bit in the same block or on subordinate blocks is not
recommended, because the BR bit can be modified by many instructions
occurring inbetween. It is advisable to use the SAVE instruction before
exiting a block, since the ENO output (=BR bit) is then set to the value of the
RLO bit and you can then check for errors in the block.
With the Save RLO to BR Memory instruction, the RLO of a network can
form part of a logic operation in a subordinate block. The CALL instruction
in the calling block resets the first check bit.

Table 4-8

Save RLO to BR Memory Box and Parameters

FBD Box

Parameters

Data Type

None

SAVE

I1.2
I1.3

Memory Area

Description

The result of logic operation (RLO) is written to the BR bit.

&

SAVE

Status Word Bits

writes
Figure 4-10

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Save RLO to BR Memory

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-11

Bit Logic Instructions

4.11 Set Output

Description

The Set Output instruction is only executed when the RLO is 1. If the RLO is
1, this instruction sets the specified address to 1. If the RLO is 0, the
instruction does not affect the specified address which remains unchanged.
The Set Output instruction is influenced by the Master Control Relay (MCR).
For more detailed information about the MCR, refer to Section 16.4.

Table 4-9

Set Output Box and Parameters

FBD Box

Parameters

<address>

<address>

Data Type
BOOL

Memory Area
I, Q, M, D, L

Description
The address specifies which bit will
be set.

The signal state at output Q4.0 is set to 1 only when:


I0.0
I0.1

S The signal state is 1 at inputs I0.0 AND I0.1

&
>=1

S OR the signal state at input I0.2 is 0.

Q4.0
S

I0.2

If the RLO of the branch is 0, the signal state of Q4.0 is


not changed.

Status Word Bits

writes

Figure 4-11

4-12

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Set Output

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

4.12 Reset Output

Description

The Reset Output instruction is only executed when the RLO is 1. If the RLO
is 1, this instruction resets the specified address to 0. If the RLO is 0, the
instruction does not affect the specified address which remains unchanged.
The Reset Output instruction is influenced by the Master Control Relay
(MCR). For more detailed information about the MCR, refer to Section 16.4.

Table 4-10

Reset Output Box and Parameters

FBD Box

Parameters

<address>

<address>

Data Type
BOOL

Memory Area
I, Q, M, T, C, D, L

TIMER

Description
The address specifies which bit will
be reset.

COUNTER

The signal state at output Q4.0 is reset to 0 only when:


I0.0
I0.1

S The signal state is 1 at inputs I0.0 AND I0.1

&
>=1

S OR the signal state at input I0.2 is 0.

Q4.0
R

I0.2

If the RLO of the branch is 0, the signal state at output


Q4.0 is unchanged.

Status Word Bits

writes

Figure 4-12

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Reset Output

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-13

Bit Logic Instructions

4.13 Set Counter Value

Description

With the Set Counter Value instruction, you assign a default value to the
counter you have specified. This instruction is executed only when there is a
rising edge at the RLO (change from 0 to 1 in the RLO).
You can only place the Set Counter Value box at the right-hand end of the
string of logic operations. You can, however, use several Set Counter Value
boxes.

Table 4-11

Set Counter Value Box and Parameters, with SIMATIC Mnemonics

FBD Box

<address1>
SZ

<address2>

Table 4-12

Memory
Area

Counter
number

COUNTER Z

Address1 specifies the number of the


counter that will be assigned a preset
value.

ZW

WORD

The value that is preset (address2)


can be in the range between 0 and
999. If you enter a constant, the
characters, C# must precede the
value indicating the BCD format, for
example C#100.

E, A, M, D, L
or constant

Description

Set Counter Value Box and Parameters with International Mnemonics

<address1>
SC

4-14

Data Type

ZW

FBD Box

<address2>

Parameters

CV

Parameters

Data Type

Memory
Area

Counter
number

COUNTER C

Address1 specifies the number of the


counter that will be assigned a preset
value.

CV

WORD

The value that is preset (address2)


can be in the range between 0 and
999. If you enter a constant, the
characters, C# must precede the
value indicating the BCD format, for
example C#100.

I, Q, M, D, L
or constant

Description

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

C5
SC

The counter C5 has the value 100 preset when the signal
state of I0.0 changes from 0 to 1 (rising edge in the RLO).
C# specifies that you are entering a value in BCD format.

I0.0
C#100

If there is no rising edge, the value of counter C5 is not


changed.

CV

Status Word Bits

writes
Figure 4-13

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Set Counter Value

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-15

Bit Logic Instructions

4.14 Up Counter Instruction

Description

The Up Counter instruction increments the value of a specified counter by 1


when there is a rising edge at the RLO (change from 0 to 1) and the value of
the counter is less than 999. If there is no rising edge at the RLO, or the
counter has already reached the value 999, it is not incremented.
The Set Counter Value instruction sets the value of the counter (see
Section 4.13).
You can only place the Up Counter box at the right-hand end of the string of
logic operations. You can, however, use several Up Counter boxes.

Table 4-13

Up Counter Boxes and Parameters with SIMATIC and International Mnemonics


Parameters

FBD Boxes
<address>
ZV

Counter
number

Data Type
COUNTER

<address>
CU

Memory Area
Z

Description
The address specifies the number of
the counter that will be incremented.

If the signal state of I0.0 changes from 0 to 1 (rising edge


in the RLO), the value of the counter C10 is incremented
by 1 (unless the value of C10 is 999).

C10
CU
I0.0

If there is no rising edge, the value of C10 remains


unchanged.

Status Word Bits

writes
Figure 4-14

4-16

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Up Counter

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

4.15 Down Counter Instruction

Description

The Down Counter instruction decrements the value of a specified counter by


1 when there is a rising edge at the RLO (change from 0 to 1) and the value
of the counter is higher than 0. If there is no rising edge at the RLO, or if the
counter has already reached the value 0, the value of the counter is not
decremented.
The Set Counter Value instruction sets the value of the counter (see
Section 4.13).
You can only place the Down Counter box at the right-hand end of the string
of logic operations. You can, however, use more than one Down Counter
boxes.

Table 4-14

Down Counter Boxes and Parameters with SIMATIC and International Mnemonics

FBD Boxes

Parameters

<address>
ZR

Data Type

Counter
number

COUNTER

<address>
CD

Memory Area
Z

Description
The address specifies the number of
the counter to be decremented.

If the signal state of input I0.0 changes from 0 to 1 (rising


edge at the RLO), the value of counter C10 is decremented
by 1 (unless the value of C10 is already 0).

C10
CD

If there is no rising edge, the value of C10 is not changed.

I0.0

Status Word Bits

writes
Figure 4-15

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Down Counter

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-17

Bit Logic Instructions

4.16 Pulse Timer Instruction

Description

The Pulse Timer instruction starts a timer with a specified value when there
is a rising edge at the RLO (change from 0 to 1). As long as the RLO is
positive, the timer continues to run for the specified time. A signal state
check for 1 produces 1 as long as the timer is running. If the RLO changes
from 1 to 0 before the time has expired, the timer is stopped. In this case, a
signal state check for 1 produces a result of 0.
The time units used for timers are d (days), h (hours), m (minutes), s
(seconds) and ms (milliseconds).
For more detailed information about the memory area and the components of
a timer, refer to Section 5.1.
You can only place the Pulse Timer box at the right-hand end of the string of
logic operations. You can, however, use more than one Pulse Timer box.

Table 4-15

Pulse Timer Box and Parameters with SIMATIC Mnemonics

FBD Box
<address>
SI
<time
value>

Table 4-16

Memory Area

Description

Timer
number

TIMER

The address specifies the


number of the timer to be
started.

TW

S5TIME

E, A, M, D, L or
constant

Time value (S5TIME format)

Pulse Timer Box and Parameters with International Mnemonics

<address>
SP

4-18

Data Type

TW

FBD Box

<time
value>

Parameters

TV

Parameters

Data Type

Timer
number

TIMER

Memory Area

The address specifies the


number of the timer to be
started.

Description

TV

S5TIME

I, Q, M, D, L or
constant

Time value (S5TIME format)

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

If the signal state of input I0.0 changes from 0 to 1 (rising edge at


the RLO), timer T5 is started. As long as the signal state is 1, the
timer continues to run for the specified time of 2 seconds. If the
signal state at I0.0 changes from 1 to 0 before this time has
expired, the timer is stopped.
As long as the timer is running, the signal state at output Q4.0 is 1.

Network 1:
T5
SP
I0.0
S5T#2s

TV

Examples of timer values:


S5T#2s = 2 seconds

Network 2:

S5T#12m_18s = 12 minutes and 18 seconds

Q4.0
=

T5

Status Word Bits

writes
Figure 4-16

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Pulse Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-19

Bit Logic Instructions

4.17 Extended Pulse Timer Instruction

Description

The Extended Pulse Timer instruction starts a timer with a specified value if
there is a rising edge at the RLO (change from 0 to 1). The timer continues to
run for the specified time even if the RLO changes to 0 before this time has
expired. A signal state check for 1 produces 1 as long as the timer is running.
The timer is restarted with the specified time if the RLO changes from 0 to 1
while the timer is running.
For more detailed information about the memory area and the components of
a timer, refer to Section 5.1.
You can only place the Extended Pulse Timer box at the right-hand end of the
string of logic operations. You can, however, use more than one Extended
Pulse Timer box.

Table 4-17

Extended Pulse Timer Box and Parameters with SIMATIC Mnemonics


Parameters

FBD Box
<address>
SV
<time
value>

Table 4-18

Description

TIMER

The address specifies the


number of the timer to be
started.

TW

S5TIME

E, A, M, D, L or
constant

Time value (S5TIME format)

Extended Pulse Timer Box and Parameters with International Mnemonics


Parameters
<address>
SE

4-20

Memory Area

Timer
number

TW

FBD Box

<time
value>

Data Type

TV

Data Type

Memory Area

Description

Timer
number

TIMER

The address specifies the


number of the timer to be
started.

TV

S5TIME

I, Q, M, D, L or
constant

Time value (S5TIME format)

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

Network 1:

If the signal state of input I0.0 changes from 0 to 1 (rising edge at


the RLO), timer T5 is started. The timer continues to run without
being influenced by a falling edge at the RLO. If the signal state of
input I0.0 changes from 0 to 1 before the specified time has
expired, the timer is retriggered.

T5
SE
I0.0
TV

S5T#2s

As long as the timer is running, the signal state at output Q4.0 is 1.


Network 2:
Q4.0
=

T5

Status Word Bits

writes
Figure 4-17

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Extended Pulse Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-21

Bit Logic Instructions

4.18 On-Delay Timer Instruction

Description

The On-Delay Timer instruction starts a specified timer when there is a rising
edge at the RLO (change from 0 to 1). A signal state check for 1 produces 1
when the specified time has expired without an error occurring and the RLO
is still 1. If the RLO changes from 1 to 0 while the timer is running, the timer
is stopped. In this case, a signal state check for 1 always produces the result
0.
For more detailed information about the address of a timer in memory and
the components of a timer, refer to Section 5.1.
You can only place the On-Delay Timer box at the right-hand end of the
string of logic operations. You can, however, use more than one On-Delay
Timer box.

Table 4-19

On-Delay Timer Box and Parameters with SIMATIC Mnemonics

FBD Box
<address>
SE
<time
value>

Table 4-20

TW

<address>
SD

4-22

Data Type

Memory Area

Description

Timer
number

TIMER

The address specifies the


number of the timer to be
started.

TW

S5TIME

E, A, M, D, L or
constant

Time value (S5TIME format)

On-Delay Timer Box and Parameters with International Mnemonics

FBD Box

<time
value>

Parameters

TV

Parameters

Data Type

Memory Area

Description

Timer
number

TIMER

The address specifies the


number of the timer to be
started.

TV

S5TIME

I, Q, M, D, L or
constant

Time value (S5TIME format)

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

Network 1:
If the signal state of input I0.0 changes from 0 to 1
(rising edge at the RLO), timer T5 is started. When the
time expires, and the signal state is still 1, output Q4.0
has the value 1. If the signal state changes from 1 to 0,
the timer is stopped.

T5
SD
I0.0
S5T#2s

TV

Network 2:
Q4.0
=

T5

Status Word Bits

writes

Figure 4-18

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

On-Delay Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-23

Bit Logic Instructions

4.19 Retentive On-Delay Timer Instruction

Description

The Retentive On-Delay Timer instruction starts the specified timer when
there is a rising edge at the RLO (change from 0 to 1). The timer continues to
run for the specified time if the RLO changes to 0 before the time has
expired. A signal state check for 1 produces the result 1 regardless of the
RLO if the time has expired. If the RLO changes from 0 to 1 while the timer
is running, the timer is restarted with the specified value.
Fore more detailed information about the address of a timer in memory and
the components of a timer, refer to Section 5.1.
You can only place the Retentive On-Delay Timer box at the right-hand end
of the string of logic operations. You can, however, use more than one
Retentive On-Delay Timer box.

Table 4-21

Retentive On-Delay Timer Box and Parameters with SIMATIC Mnemonics


Parameters

FBD Box
<address>
SS
<time
value>

Table 4-22

Description

TIMER

The address specifies the


number of the timer to be
started.

TW

S5TIME

E, A, M, D, L or
constant

Time value (S5TIME format)

On-Delay Timer Box and Parameters with International Mnemonics


Parameters

<address>
SS

4-24

Memory Area

Timer
number

TW

FBD Box

<time
value>

Data Type

TV

Data Type

Memory Area

Description

Timer
number

TIMER

The address specifies the


number of the timer to be
started.

TV

S5TIME

I, Q, M, D, L or
constant

Time value (S5TIME format)

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

Network 1:
If the signal state of input I0.0 changes from 0 to 1 (rising
edge at the RLO), timer T5 is started. The timer continues to
run regardless of whether the signal state at I0.0 changes
from 1 to 0. If the signal state changes from 0 to 1 before the
time has expired, the timer is retriggered.
Output Q4.0 has the value 1 when the time has expired.

T5
SS
I0.0
TV

S5T#2s
Network 2:

Q4.0
=

T5

Status Word Bits

writes
Figure 4-19

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Retentive On-Delay Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-25

Bit Logic Instructions

4.20 Off-Delay Timer Instruction

Description

The Off-Delay Timer instruction starts the specified timer when the RLO has
a falling edge (change from 1 to 0). A signal state check for 1 produces 1
when the RLO is 1 or when the timer is running. The timer is reset when the
RLO changes from 0 to 1 while the timer is running. The time is only
restarted when the RLO changes from 1 to 0.
For more detailed information about the address of a timer in memory and
the components of a timer, refer to Section 5.1.
You can only place the Off-Delay Timer box at the right-hand end of the
string of logic operations. You can, however, use more than one Off-Delay
Timer box.

Table 4-23

Off-Delay Timer Box and Parameters with SIMATIC Mnemonics

FBD Box

Parameters

<address>
SA
<time
value>

Table 4-24

Description

TIMER

The address specifies the


number of the timer to be
started.

TW

S5TIME

E, A, M, D, L or
constant

Time value (S5TIME format)

Off-Delay Timer Box and Parameters with International Mnemonics


Parameters

<address>
SF

4-26

Memory Area

Timer
number

TW

FBD Box

<time
value>

Data Type

TV

Data Type

Memory Area

Description

Timer
number

TIMER

The address specifies the


number of the timer to be
started.

TV

S5TIME

I, Q, M, D, L or
constant

Time value (S5TIME format)

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

Network 1:

T5
SF

The timer is started when the signal state at I0.0 changes from
1 to 0.

I0.0
S5T#2s

If the signal state changes from 0 to 1, the timer is reset.

TV

The signal state at output Q4.0 is 1, when the signal state at


input I0.0 is 1 or the timer is running.

Network 2:
Q4.0
=

T5

Status Word Bits

writes

Figure 4-20

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Off-Delay Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-27

Bit Logic Instructions

4.21 Positive RLO Edge Detection

Description

Table 4-25

The Positive RLO Edge Detection instruction detects a change from 0 to 1


(rising edge) at the specified address and indicates this with an RLO of 1
after the instruction. The current signal state at the RLO is compared with the
signal state of the address (the edge memory bit). If the signal state of the
address is 0 and the RLO is 1 before the instruction, the RLO will be 1
(pulse) after the instruction, in all other cases the RLO is 0. The RLO prior to
the instruction is stored in the address.
Positive RLO Edge Detection Box and Parameter
Parameters

FBD Box
<address>

<address>

Data Type
BOOL

Memory Area
I, Q, M, D, L

The address specifies which edge


memory bit will store the previous
RLO.

I1.0
I1.1
I1.2
I1.3

&

&

I1.4

&

M0.0
P

M1.1
N

Description

The edge memory bit M3.3 stores the


signal state of the previous RLO.

&

>=1

M2.2
P

M3.3
N

Q4.0
=

Status Word Bits

writes

Figure 4-21

4-28

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Positive RLO Edge Detection

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

4.22 Negative RLO Edge Detection

Description

Table 4-26

The Negative RLO Edge Detection instruction detects a change from 1 to 0


(falling edge) at the specified address and indicates this by setting the RLO to
1 after the instruction. The current signal state of the RLO is compared with
the signal state of the address (the edge memory bit). If the signal state of the
address is 1 and the RLO prior to the instruction was 0, the RLO is 1 (pulse)
after the instruction, in all other cases it is 0. The RLO prior to the instruction
is stored in the address.
Negative RLO Edge Detection Box and Parameter
Parameters

FBD Box
<address>

Data Type

<address>

Memory Area

BOOL

I, Q, M, D, L

The address specifies which edge


memory bit will store the previous
RLO.

I1.0
I1.1
I1.2
I1.3

&

&

I1.4

&

M0.0
P

M1.1
N

Description

The edge memory bit M3.3 stores the


signal state of the previous RLO.

&

>=1

M2.2
P

M3.3
N

Q4.0
=

Status Word Bits

writes
Figure 4-22

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Negative RLO Edge Detection

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-29

Bit Logic Instructions

4.23 Address Positive Edge Detection

Description

Table 4-27

The Address Positive Edge Detection instruction compares the signal state of
<address1> with the signal state of the previous signal check that is stored in
the parameter M_BIT. If there has been a change from 0 to 1, output Q has
the value 1, in all other cases it has the value 0.
Address Positive Edge Detection Box and Parameters
Parameters

FBD Box
<address1>
POS

Data Type

Memory Area

<address1>

BOOL

I, Q, M, D, L

Signal to be checked for a positive


(rising) edge.

M_BIT

BOOL

Q, M, D

The M_BIT address specifies the


edge memory bit used to store the
previous signal state of POS. You
should only use the process image
input area I for the M_BIT when
no input module is already using
this address.

BOOL

I, Q, M, D, L

One-shot output.

M_BIT Q

I0.3

Output Q4.0 is 1 when:

POS

M0.0

Description

M_BIT

there is a rising edge at input I0.3


AND the signal state is 1 at input I0.4.
&

Q4.0
=

I0.4

Status Word Bits

writes
Figure 4-23

4-30

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Address Positive Edge Detection

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

4.24 Address Negative Edge Detection

Description

Table 4-28

The Address Negative Edge Detection instruction compares the signal state of
<address1> with the signal state of the previous check that is stored in the
M_BIT parameter. If a change from 1 to 0 occurred, output Q has the value
1, in all other situations it has the value 0.
Address Negative Edge Detection Box and Parameters
Parameters

FBD Box
<address1>
NEG

M_BIT

Data Type

Memory Area

Description

<address1>

BOOL

I, Q, M, D, L

Signal to be checked for a


negative (falling) edge
change.

M_BIT

BOOL

Q, M, D

The M_BIT address


specifies the edge memory
bit in which the previous
signal state of NEG is
stored. Only use the
process input image I
memory area for the
M_BIT when no input
module is already using
this address.

BOOL

I, Q, M, D, L

One-shot output.

I0.3
Output Q4.0 is 1 when:

NEG

there is a falling edge at input I0.3


AND the signal state at input I0.4 is 1.
M0.0

M_BIT

&

Q4.0
=

I0.4

Status Word Bits

writes

Figure 4-24

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Address Negative Edge Detection

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-31

Bit Logic Instructions

4.25 Set_Reset Flip Flop

Description

The Set_Reset Flip Flop instruction executes Set (S) or Reset (R) instructions
only when the RLO is 1. An RLO of 0 has no effect on these instructions, the
address specified in the instruction remains unchanged.
Set_Reset Flip Flop is set when the signal state at input S is 1 and the signal
state at input R is 0. If input S is 0 and input R is 1, the flip flop is reset. If
the RLO at both inputs is 1 the flip flop is reset.
The Set_Reset Flip Flop instruction is influenced by the Master Control
Relay (MCR). For more detailed information about how the MCR functions,
refer to Section 16.4.

Table 4-29

Set_Reset Flip Flop Box and Parameters

FBD Box

Parameters

<address>
SR

<address>

BOOL

I, Q, M, D, L

The address specifies which bit will


be set or reset.

BOOL

I, Q, M, D, L, T, C

Set instruction enabled

BOOL

I, Q, M, D, L, T, C

Reset instruction enabled

BOOL

I, Q, M, D, L

Signal state of <address>

Memory Area

SR
S

&

I0.0
I0.1

Description

If I0.0 is 1 and I0.1 is 0, memory bit M0.0


is set and Q4.0 is 1.
If I0.0 is 0 and I0.1 is 1, the memory bit
M0.0 is reset and Q4.0 is 0.

M0.0

&

I0.0
I0.1

Data Type

If both signal state are 0, there is no


change. If both signal states are 1, the
reset instruction dominates due to the
order of the instructions.
M0.0 is reset and Q 4.0 is 0.

Q4.0
=

Status Word Bits

writes
Figure 4-25

4-32

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Set_Reset Flip Flop

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Bit Logic Instructions

4.26 Reset_Set Flip Flop

Description

The Reset_Set Flip Flop instruction executes instructions such as Set (S) or
Reset (R) only when the RLO is 1. An RLO of 0 does not affect these
instructions, the address specified in the instruction is not changed.
Reset_Set Flip Flop is reset when the signal state at input R is 1 and the
signal state at input S is 0. If input R is 0 and input S is 1, the flip flop is set.
If the RLO at both inputs is 1, the flip flop is set.
The Reset_Set Flip Flop instruction is affected by the Master Control Relay
(MCR). For more detailed information about the way in which the MCR
functions, refer to Section 16.4.

Table 4-30

Reset_Set Flip Flop Box and Parameters

FBD Box

Parameters

Data Type

Memory Area

<address>

<address>

BOOL

I, Q, M, D, L

The address specifies which bit will


be set or reset.

BOOL

I, Q, M, D, L, T, C

Reset instruction enabled

BOOL

I, Q, M, D, L, T, C

Set instruction enabled

BOOL

I, Q, M, D, L

Signal state of <address>

RS
R
S

If I0.0 is 1 and I0.1 is 0, the memory bit M0.0


is reset and output Q4.0 is 0. If I0.0 is 0 and
I0.1 is 1, the memory bit M0.0 is set and
output Q4.0 is 1.

M0.0

&

I0.0
I0.1

Description

RS
R

&

I0.0
I0.1

If both signal states are 0, there is no change.


If both signal states are 1, the Set instruction
dominates due to the order of the
instructions. M 0.0 is set and Q4.0 is 1.

Q4.0
=

Status Word Bits

writes
Figure 4-26

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Reset_Set Flip Flop

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

4-33

Bit Logic Instructions

4-34

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Timer Instructions
Chapter
Overview

Section

Description

Page

5.1

Memory Areas and Components of a Timer

5-2

5.2

Choosing the Right Timer

5-4

5.3

Pulse S5 Timer

5-5

5.4

Extended Pulse S5 Timer

5-7

5.5

On-Delay S5 Timer

5-9

5.6

Retentive On-Delay S5 Timer

5-11

5.7

Off-Delay S5 Timer

5-13

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

5-1

Timer Instructions

5.1

Memory Areas and Components of a Timer

Memory Area

Timers have an area reserved for them in the memory of your CPU. This
memory area reserves one 16-bit word for each timer address. When you
program in FBD, 256 timers are supported. Please refer to your CPUs
technical information to check the number of timer words available.
The following functions access the timer memory area:
S Timer instructions
S Updating of timer words by the clock timing. In the RUN mode, this CPU
function decrements a given time value by one unit at the interval
specified by the time base until the time value is zero.

Time Value

Bits 0 through 9 of the timer word contain the time value in binary code. The
time value specifies a number of units. When the timer is updated, the time
value is decremented by one unit at intervals specified by the time base. The
time value is decremented until it is equal to zero.
You can load a predefined time value with the following syntax.

S S5T#aH_bbM_ccS_dddMS
where: a = hours, bb = minutes, cc = seconds and ddd = milliseconds
The time base is selected automatically, and the value is rounded
down to the next lower number with that time base.
The maximum time value you can enter is 9,990 seconds, or 2H_46M_30S.

Time Base

Bits 12 and 13 of the timer word contain the time base in binary code. The
time base defines the interval at which the time value is decremented by one
unit (see Table 5-1 and Figure 5-1). The smallest time base is 10 ms; the
largest is 10 s.
Table 5-1

Time Base and Binary Code


Time Base

5-2

Binary Code for the Time Base

10 ms

00

100 ms

01

1s

10

10 s

11

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Timer Instructions

Because time values are saved at only one time interval, values that are not
exact multiples of a time interval are truncated. Values with a resolution too
high for the required range are rounded down to within the required range but
not to the desired resolution. The following table shows the possible
resolutions and the corresponding ranges.
Table 5-2

Resolution and Ranges of the Time Base


Resolution

Bit Configuration
in the Timer Cell

Time Base

0.01 seconds

10MS to 9S_990MS

0.1 seconds

100MS to 1M_39S_900MS

1 second

1S to 16M_39S

10 seconds

10S to 2HR_46M_30S

When a timer is started, the contents of the timer cell are used as the time
value. Bits 0 through 11 of the timer cell contain the time value in binary
coded decimal format (BCD format: each group of four bits contains the
binary code for one decimal value). Bits 12 and 13 contain the time base in
binary code (see Table 5-2). Figure 5-1 shows the contents of the timer cell
loaded with timer value 127 with a time base of 1 second.

15...
x

...8
x

0
1

7...
0

...0
0

Time value in BCD (0 to 999)


Time base
1 second
Irrelevant: These bits are ignored when the timer is started.
Figure 5-1

Reading the Time


and the Time Base

Contents of the Timer Cell for Timer Value 127, Time Base 1 Second

Each timer box provides two outputs, BI and BCD, for which you can specify
a word location. The BI output provides the time value in binary format, the
time base is not displayed. The BCD output provides the time base and the
time value in binary coded decimal (BCD) format.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

5-3

Timer Instructions

5.2

Choosing the Right Timer


The following figure provides an overview of the five types of timers
described in this chapter. This overview is intended to help you choose the
right timer for your timing job.

Input signal

I0.0

Output signal
(Pulse timer)

Q4.0 S_PULSE
t
The maximum time that the output signal remains at 1 is the
same as the programmed time value t. The output signal
stays at 1 for a shorter period if the input signal changes to 0.

Output signal
(Extended pulse
timer)

Q4.0 S_PEXT

Output signal
(On-delay timer)

Q4.0 S_ODT

t
The output signal remains at 1 for the programmed length of
time, regardless of how long the input signal stays at 1.

t
The output signal changes to 1 only when the programmed
time has elapsed and the input signal is still 1.

Output signal
(Retentive
on-delay timer)

Q4.0 S_ODTS

Output signal
(Off-delay timer)

Q4.0 S_OFFDT

t
The output signal changes from 0 to 1 only when the
programmed time has elapsed, regardless of how long the
input signal stays at 1.

t
The output signal changes to 1 when the input signal changes
to 1 or while the timer is running. The time is started when the
input signal changes from 1 to 0.

Figure 5-2

5-4

Choosing the Right Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Timer Instructions

5.3

Pulse S5 Timer

Description

The Pulse S5 Timer instruction starts a specified timer if there is a rising edge
(a change in signal state from 0 to 1) at the Start (S) input. A signal change is
always necessary to start a timer. The timer continues to run for the time
specified at the Time Value (TV) input until the programmed time elapses, as
long as the signal state at input TV is 1. While the timer is running, a signal
state check for 1 at output Q produces a result of 1. If there is a change from
1 to 0 at the S input before the time has elapsed, the timer is stopped. Then a
signal state check for 1 at output Q produces a result of 0.
While the timer is running, a change from 0 to 1 at the Reset (R) input of the
timer resets the timer. This change also resets the time and the time base to
zero. A signal state of 1 at the R input of the timer has no effect if the timer
is not running.
The current time value can be scanned at outputs BI and BCD. The time
value at BI is in binary format; at BCD it is in binary coded decimal format.

Table 5-3

Pulse S5 Timer Box and Parameters with SIMATIC Mnemonics

FBD Box

Parameters

Data Type

Memory Area

Nr.

TIMER

Timer identification number. The range


depends on the CPU.

BOOL

E, A, M, D, L, T, Z

Start input

TW

S5TIME

E, A, M, D, L or
constant

Preset time value (range 0 to 9999)

BOOL

E, A, M, D, L, T, Z

Reset input

DUAL

WORD

E, A, M, D, L

Time remaining (value in integer format)

DEZ

WORD

E, A, M, D, L

Time remaining (value in BCD format)

BOOL

E, A, M, D, L

Status of the timer

TNr.
T Nr.
S IMPULS
S_IMPULS
S

DUAL

TW

DEZ

Table 5-4

Pulse S5 Timer Box and Parameters with International Mnemonics

FBD Box

Parameters

Data Type

Memory Area

no.

TIMER

Timer identification number. The range


depends on the CPU.

BOOL

I, Q, M, D, L, T, C

Start input

TV

S5TIME

I, Q, M, D, L or
constant

Preset time value (range 0 to 9999)

BOOL

I, Q, M, D, L, T, C

Reset input

BI

WORD

I, Q, M, D, L

Time remaining (value in integer format)

BCD

WORD

I, Q, M, D, L

Time remaining (value in BCD format)

BOOL

I, Q, M, D, L

Status of the timer

T no.
S PULSE
S_PULSE
S
TV
R

Description

BI
BCD
Q

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Description

5-5

Timer Instructions

Example

Figure 5-3 illustrates the Pulse S5 Timer instruction, describes the status word
bits, and shows the characteristics of the instruction.

If the signal state of input I0.0 changes from 0 to 1 (if


there is a rising edge in the RLO), timer T5 is started.
The timer continues to run with the specified time of
two seconds (2s) as long as input I0.0 is 1. If the
signal state of input I0.0 changes from 1 to 0 before
the time elapses, the timer is stopped. If the signal
state of input I0.1 changes from 0 to 1 while the timer
is running, the timer is reset. The signal state of
output Q4.0 is 1 as long as the timer is running.

T5
S_PULSE
I0.0

S5T# 2s

TV

I0.1

BI
BCD
Q

Q4.0
=

Examples of other preset time values:


Available units: h (hours), m (minutes), s (seconds),
ms (milliseconds)
S5T#4s > 4 seconds
S5T#1h_15m > 1 hour and 15 minutes
S5T#2h_46m_30s>2 hours, 46 minutes, and
30 seconds

Status Word Bits

writes

BR

CC1

CC0

OV

OS

OR
x

STA
x

RLO
x

FC
1

Timing Diagram
t

RLO at input S
RLO at input R
Timer running
RLO at output Q
Negated RLO at
output Q

Figure 5-3

5-6

t = programmed time

Pulse S5 Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Timer Instructions

5.4

Extended Pulse S5 Timer

Description

The Extended Pulse S5 Timer instruction starts a specified timer if there is a


rising edge (change in signal state from 0 to 1) at the Start (S) input. A signal
change is always necessary to start a timer. The timer continues to run for the
time specified at the Time Value (TV) input, even if the signal state at the S
input changes to 0 before the time has elapsed. A signal state check for 1 at
output Q produces a result of 1 as long as the timer is running. The timer is
restarted with the specified time if the signal state at input S changes from 0
to 1 while the timer is running.
A change from 0 to 1 at the Reset (R) input of the timer while the timer is
running resets the timer. This change also resets the time and the time base to
zero.
The current time value can be scanned at the outputs BI and BCD. The time
value at BI is in binary format; at BCD it is in binary coded decimal format.

Table 5-5

Extended Pulse S5 Timer Box and Parameters with SIMATIC Mnemonics

FBD Box

Parameters

Data Type

Memory Area

Nr.

TIMER

Timer identification number. The range


depends on the CPU.

BOOL

E, A, M, D, L, T, Z

Start input

TW

S5TIME

E, A, M, D, L or
constant

Preset time value (range 0 to 9999)

BOOL

E, A, M, D, L, T, Z

Reset input

DUAL

WORD

E, A, M, D, L

Time remaining (value in integer format)

DEZ

WORD

E, A, M, D, L

Time remaining (value in BCD format)

BOOL

E, A, M, D, L

Status of the timer

T Nr.
S_VIMP
_
S

DUAL

TW

DEZ

Table 5-6

Extended Pulse S5 Timer Box and Parameters with International Mnemonics

FBD Box
T no.
S_PEXT
S
TV
R

Description

BI
BCD
Q

Parameters

Data Type

no.

TIMER

Timer identification number. The range


depends on the CPU.

BOOL

I, Q, M, D, L, T, C

Start input

TV

S5TIME

I, Q, M, D, L or
constant

Preset time value (range 0 to 9999)

BOOL

I, Q, M, D, L, T, C

Reset input

BI

WORD

I, Q, M, D, L

Time remaining (value in integer format)

BCD

WORD

I, Q, M, D, L

Time remaining (value in BCD format)

BOOL

I, Q, M, D, L

Status of the timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Memory Area

Description

5-7

Timer Instructions

Example

Figure 5-4 illustrates the Extended Pulse S5 Timer instruction, describes the
status word bits, and shows the characteristics of the instruction.

If the signal state of input I0.0 changes from 0 to 1


(rising edge in the RLO), timer T5 is started. The
timer continues to run for the specified time of two
seconds (2s) regardless of a falling edge at input S. If
the signal state of input I0.0 changes from 0 to 1
before the time has elapsed, the timer is restarted. If
the signal state of input I0.1 changes from 0 to 1
while the timer is running, the timer is reset. The
signal state of output Q4.0 is 1 as long as the timer is
running.

T5
S_PEXT
I0.0

S5T# 2s

TV

I0.1

BI
BCD
Q

Q4.0
=

Status Word Bits

writes

BR

CC1

CC0

OV

OS

OR
x

STA
x

RLO
x

FC
1

Timing Diagram

RLO at input S
RLO at input R
Timer running
RLO at output Q
Negated RLO at
output Q
t = programmed time

Figure 5-4

5-8

Extended Pulse S5 Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Timer Instructions

5.5

On-Delay S5 Timer

Description

The On-Delay S5 Timer instruction starts a specified timer if there is a rising


edge (change in signal state from 0 to 1) at the Start (S) input. A signal
change is always necessary to start a timer. The timer continues to run for the
time specified at the Time Value (TV) input as long as the signal state at
input S is 1. A signal state check for 1 at output Q produces a result of 1
when the time has elapsed without error and when the signal state at input S
is still 1. When the signal state at input S changes from 1 to 0 while the timer
is running, the timer is stopped. In this case, a signal state check for 1 at
output Q always produces the result 0.
A change from 0 to 1 at the Reset (R) input of the timer while the timer is
running resets the timer. This change also resets the time and the time base to
zero. The timer is also reset if the signal state is 1 at the R input while the
timer is not running.
The current time value can be scanned at the outputs BI and BCD. The time
value at BI is in binary format; at BCD it is in binary coded decimal format.

Table 5-7

On-Delay S5 Timer Box and Parameters with SIMATIC Mnemonics

FBD Box

Parameters

Data Type

Memory Area

Nr.

TIMER

Timer identification number. The range


depends on the CPU.

BOOL

E, A, M, D, L, T, Z

Start input

TW

S5TIME

E, A, M, D, L or
constant

Preset time value (range 0 9999)

BOOL

E, A, M, D, L, T, Z

Reset input

DUAL

WORD

E, A, M, D, L

Time remaining (value in integer format)

DEZ

WORD

E, A, M, D, L

Time remaining (value in BCD format)

BOOL

E, A, M, D, L

Status of the timer

TNr.
S_EVERZ
DUAL

S
TW

DEZ
Q

Table 5-8

On-Delay S5 Timer Box and Parameters with International Mnemonics

FBD Box

Parameters

Data Type

Memory Area

no.

TIMER

Timer identification number. The range


depends on the CPU.

BOOL

I, Q, M, D, L, T, C

Start input

TV

S5TIME

I, Q, M, D, L or
constant

Preset time value (range 0 9999)

BOOL

I, Q, M, D, L, T, C

Reset input

BI

WORD

I, Q, M, D, L

Time remaining (value in integer format)

BCD

WORD

I, Q, M, D, L

Time remaining (value in BCD format)

BOOL

I, Q, M, D, L

Status of the timer

T no.
S_ODT
S
TV
R

Description

BI
BCD
Q

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Description

5-9

Timer Instructions

Example

Figure 5-5 illustrates the On-Delay S5 Timer instruction, describes the bits in
the status word and shows the characteristics of the instruction.

If the signal state of input I0.0 changes from 0 to 1


(rising edge in the RLO), timer T5 is started. If the
specified time of two seconds (2s) elapses and
the signal state of input I0.0 is still 1, the signal
state of output Q4.0 is 1. If the signal state of
input I0.0 changes from 1 to 0, the timer is
stopped and output Q4.0 is 0. If the signal state of
input I0.1 changes from 0 to 1 while the timer is
running, the timer is restarted.

T5
S_ODT
I0.0

S5T# 2s

TV

I0.1

BI
BCD
Q

Q4.0
=

Status Word Bits

writes

BR

CC1

CC0

OV

OS

OR
x

STA
x

RLO
x

FC
1

Timing Diagram
t

RLO at input S
RLO at input R
Timer running
RLO at output Q
Negated RLO at
output Q
t = programmed time
Figure 5-5

5-10

On-Delay S5 Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Timer Instructions

5.6

Retentive On-Delay S5 Timer

Description

The Retentive On-Delay S5 Timer instruction starts a specified timer if there


is a rising edge (change in signal state from 0 to 1) at the Start (S) input. A
signal change is always necessary to start a timer. The timer continues to run
for the time specified at the Time Value (TV) input, even if the signal state at
input S changes to 0 before the timer has expired. A signal state check for 1
at output Q produces a result of 1 when the time has elapsed, regardless of
the signal state at input S when the reset input (R) remains at 0. The timer is
restarted with the specified time if the signal state at input S changes from 0
to 1 while the timer is running.
A change from 0 to 1 at the Reset (R) input of the timer resets the timer
regardless of the RLO at the S input.
The current time value can be scanned at the outputs BI and BCD. The time
value at BI is in binary format; at BCD it is in binary coded decimal format.

Table 5-9

Retentive On-Delay S5 Timer Box and Parameters with SIMATIC Mnemonics

FBD Box
TNr.
S SEVERZ
S_SEVERZ
S

DUAL

TW

DEZ
Q

Table 5-10

T no.
S ODTS
S_ODTS

TV
R

Data Type

Memory Area

Description

Nr.

TIMER

Timer identification number. The range


depends on the CPU.

BOOL

E, A, M, D, L, T, Z

Start input

TW

S5TIME

E, A, M, D, L or
constant

Preset time value (range 0 9999)

BOOL

E, A, M, D, L, T, Z

Reset input

DUAL

WORD

E, A, M, D, L

Time remaining (value in integer format)

DEZ

WORD

E, A, M, D, L

Time remaining (value in BCD format)

BOOL

E, A, M, D, L

Status of the timer

Retentive On-Delay S5 Timer Box and Parameters with International Mnemonics

FBD Box

Parameters

BI
BCD
Q

Parameters

Data Type

no.

TIMER

Timer identification number. The range


depends on the CPU.

BOOL

I, Q, M, D, L, T, C

Start input

TV

S5TIME

I, Q, M, D, L or
constant

Preset time value (range 0 9999)

BOOL

I, Q, M, D, L, T, C

Reset input

BI

WORD

I, Q, M, D, L

Time remaining (value in integer format)

BCD

WORD

I, Q, M, D, L

Time remaining (value in BCD format)

BOOL

I, Q, M, D, L

Status of the timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Memory Area

Description

5-11

Timer Instructions

Example

Figure 5-6 illustrates the Retentive On-Delay S5 Timer instruction, describes


the status word bits, and shows the characteristics of the instruction.

If the signal state of input I0.0 changes from 0 to


1 (rising edge in the RLO), timer T5 is started.
The timer continues to run regardless of a signal
change at input I0.0 from1 to 0. If the signal
state of input I0.0 changes from 0 to 1 before
the time has elapsed, the timer is restarted. If
the signal state of input I0.1 changes from 0 to 1
while the timer is running, the timer is restarted.
The signal state of output Q4.0 is 1 if the time
has elapsed and the signal state at I 0.1
remains 0.

T5
S_ODTS
BI

I0.0

S5T# 2s

TV

I0.1

BCD
Q

Q4.0
=

Status Word Bits

writes

BR

CC1

CC0

OV

OS

OR
x

STA
x

RLO
x

FC
1

Timing Diagram

RLO at input S
RLO at input R
Timer running
RLO at output Q
Negated RLO at
output Q
t = programmed time
Figure 5-6

5-12

Retentive On-Delay S5 Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Timer Instructions

5.7

Off-Delay S5 Timer

Description

The Off-Delay S5 Timer instruction starts a specified timer if there is a falling


edge (change in signal state from 1 to 0) at the Start (S) input. A signal
change is always necessary to start a timer. The result of a signal state check
for 1 at output Q is 1 when the signal state at the S input is 1 or when the
timer is running. The timer is reset when the signal state at input S changes
from 0 to 1 while the timer is running. The timer is not restarted until the
signal state at input S changes again from 1 to 0.
A change from 0 to 1 at the Reset (R) input of the timer while the timer is
running resets the timer.
The actual time value can be scanned at the outputs BI and BCD. The time
value at BI is in binary format; at BCD it is in binary coded decimal format.

Table 5-11

Off-Delay S5 Timer Box and Parameters with SIMATIC Mnemonics

FBD Box

Parameters

Data Type

Memory Area

Nr.

TIMER

Timer identification number. The range


depends on the CPU.

BOOL

E, A, M, D, L, T, Z

Start input

TW

S5TIME

E, A, M, D, L or
constant

Preset time value (range 0 9999)

BOOL

E, A, M, D, L, T, Z

Reset input

DUAL

WORD

E, A, M, D, L

Time remaining (value in integer format)

DEZ

WORD

E, A, M, D, L

Time remaining (value in BCD format)

BOOL

E, A, M, D, L

Status of the timer

TNr.
S_AVERZ
DUAL

S
TW

DEZ
Q

Table 5-12

Off-Delay S5 Timer Box and Parameters with International Mnemonics

FBD Box

Parameters

Data Type

Memory Area

no.

TIMER

Timer identification number. The range


depends on the CPU.

BOOL

I, Q, M, D, L, T, C

Start input

TV

S5TIME

I, Q, M, D, L or
constant

Preset time value (range 0 9999)

BOOL

I, Q, M, D, L, T, C

Reset input

BI

WORD

I, Q, M, D, L

Time remaining (value in integer format)

BCD

WORD

I, Q, M, D, L

Time remaining (value in BCD format)

BOOL

I, Q, M, D, L

Status of the timer

T no.
S_OFFDT
S
TV
R

Description

BI
BCD
Q

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Description

5-13

Timer Instructions

Example

Figure 5-7 illustrates the Off-Delay S5 Timer instruction, describes the status
word bits, and shows the characteristics of the instruction.

T5
S_OFFDT
I0.0

S5T# 2s

TV

I0.1

If the signal state at input I0.0 changes from 1 to 0,


the timer is started. Output Q4.0 is 1 when I0.0 is 1 or
the timer is running. If the signal state at I0.1 changes
from 0 to 1, while the timer is running, the timer is
reset.

BI
BCD
Q

Q4.0
=

Status Word Bits

writes

BR

CC1

CC0

OV

OS

OR
x

STA
x

RLO
x

FC
1

Timing Diagram
t

RLO at input S
RLO at input R
Timer running
RLO at output Q
Negated RLO at
output Q
t = programmed time
Figure 5-7

5-14

Off-Delay S5 Timer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Counter Instructions
Chapter
Overview

Section

Description

Page

6.1

Memory Address and Components of a Counter

6-2

6.2

Up-Down Counter

6-3

6.3

Up Counter

6-5

6.4

Down Counter

6-7

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

6-1

Counter Instructions

6.1

Memory Address and Components of a Counter

Memory Area

Counters have an area reserved for them in the memory of your CPU. This
memory area reserves one 16-bit word for each counter address. When you
program in FBD, 256 counters are supported.
The counter instructions are the only functions that can access the counter
memory area.

Count Value

Bits 0 through 9 of the counter word contain the count value in binary code.
The count value is taken from the accumulator and entered in the counter
word when a counter is set. The range of the count value is 0 to 999. You can
increment/decrement the count value within this range using the Up-Down
Counter, Up Counter, and Down Counter instructions.

Bit Configuration
in the Counter

A counter is set to a required value by loading a number between 0 and 999


as the count value, for example 127, in the following format:
C# 127
The C# stands for binary coded decimal format (BCD format: each group of
four bits contains the binary code for one decimal value).
Bits 0 through 11 of the counter contain the count value in binary coded
decimal format . Figure 6-1 shows the contents of the counter after you have
loaded the count value 127 and the contents of the counter cell after the
counter has been set.
15 14 13 12

11 10 9

0
1

irrelevant

Count value in BCD (0 to 999)


15 14 13 12

11 10 9

irrelevant

Figure 6-1

6-2

Binary count value

Contents of the Counter Cell after the Counter has been Set with Count
Value 127

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Counter Instructions

6.2

Up-Down Counter

Description

A rising edge (change in signal state from 0 to 1) at input S of the Up-Down


Counter instruction sets the counter with the value at the Preset Value (PV)
input. The counter is incremented by 1 if the signal state at input CU changes
from 0 to 1 (rising edge) and the value of the counter is less than 999. The
counter is decremented by 1 if the signal state at input CD changes from 0 to
1 (rising edge) and the value of the counter is higher than 0. If there is a
rising edge at both count inputs, both operations are executed and the count
remains the same. The counter is reset if there is a rising edge at input R.
Resetting the counter sets the count value to 0.
A signal state check for 1 at output Q produces a result of 1 when the count is
greater than 0; the check produces a result of 0 when the count is equal to 0.

Table 6-1

Up-Down Counter Box and Parameters with SIMATIC Mnemonics

FBD Box

Parameters

Data Type

Memory Area

Description

Nr.

COUNTER

Counter identification number. The


range depends on the CPU.

ZV

BOOL

E, A, M, D, L

ZV input: Up Counter

ZV

ZR

BOOL

E, A, M, D, L

ZR input: Down Counter

ZR

BOOL

E, A, M, D, L, T, Z Input for presetting the counter

ZW

WORD

E, A, M, D, L

Z-Nr
Z-Nr.
ZAEHLER

S
ZW
R

DUAL
DEZ
Q

or constant

Count value in the range between 0


and 999 or
Count value entered as C#<value> in
BCD format

BOOL

E, A, M, D, L, T, Z Reset input

DUAL

WORD

E, A, M, D, L

Current count value (integer format)

DEZ

WORD

E, A, M, D, L

Current count value (BCD format)

BOOL

E, A, M, D, L

Status of the counter

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

6-3

Counter Instructions

Table 6-2

Up-Down Counter Box and Parameters with International Mnemonics


Parameters

FBD Box

Data Type

Memory Area

Description

no.

COUNTER

Counter identification number. The


range depends on the CPU.

CU

BOOL

I, Q, M, D, L

CU input: Up Counter

CD

BOOL

I, Q, M, D, L

CD input: Down Counter

CU

BOOL

I, Q, M, D, L, C

Input for presetting the counter

CD

PV

WORD

I, Q, M, D, L
or

Count value in the range between 0


and 999

constant

or

C no.
S CUD
S_CUD

CV
S
PV CV_BCD
R
Q

Count value entered as C#<value> in


BCD format
R

BOOL

I, Q, M, D, L, C

Reset input

CV

WORD

I, Q, M, D, L

Current count value (integer format)

CV_BCD

WORD

I, Q, M, D, L

Current count value (BCD format)

BOOL

I, Q, M, D, L

Status of the counter

C10
S_CUD
I0.0

CU

I0.1

CD

I0.2

C#55

PV CV_BCD

I0.3

A change in signal state from 0 to 1 at


input I0.2 sets counter C10 with the value
55. If the signal state of input I0.0
changes from 0 to 1, the value of counter
C10 is incremented by 1, except when
the value of counter C10 is already 999.
If input I0.1 changes from 0 to 1, counter
C10 is decremented by 1, except when
the value of counter C10 is already 0. If
I0.3 changes from 0 to 1, the value of
C10 is set to 0.
Q4.0 is 1, when C 10 is not equal to 0.

CV

Q4.0
=

Status Word Bits

writes

Figure 6-2

6-4

BR

CC1

CC0

OV

OS

OR
x

STA
x

RLO
x

FC
1

Up-Down Counter

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Counter Instructions

6.3

Up Counter

Description

A rising edge (change in signal state from 0 to 1) at input S of the Up


Counter instruction sets the counter with the value at the Preset Value (PV)
input. With a rising edge at input CU, the count value is incremented by 1
when the count value is less than 999. The counter is reset by a rising edge at
input R. Resetting the counter sets the count value to 0.
A signal state check for 1 at output Q produces a result of 1 when the count is
greater than 0. The check produces a result of 0 when the count is equal to 0.

Table 6-3

Up Counter Box and Parameters with SIMATIC Mnemonics


Parameter

FBD Box

Z-Nr.
Z
Nr
Z VORW
Z_VORW
ZV

ZW

Table 6-4

Counter identification number. The


range depends on the CPU.

ZV

BOOL

E, A, M, D, L

ZV input: Up Counter

BOOL

E, A, M, D, L, T, Z Input for presetting the counter

ZW

WORD

E, A, M, D, L

Count value in the range between 0


and 999

or

or

constant

Count value entered as C#<value> in


BCD format

BOOL

E, A, M, D, L, T, Z Reset input

DUAL

WORD

E, A, M, D, L

Current count value (integer format)

DEZ

WORD

E, A, M, D, L

Current count value (BCD format)

BOOL

E, A, M, D, L

Status of the counter

Up Counter Box and Parameters with International Mnemonics


Parameters

FBD Box
C no.
S_CU
S CU
CU
CV

Data Type

Memory Area

Description

no.

COUNTER

Counter identification number. The


range depends on the CPU.

CU

BOOL

I, Q, M, D, L

CU input: Up Counter

BOOL

I, Q, M, D, L, T, C Input for presetting the counter

PV

WORD

I, Q, M, D, L

Count value in the range between 0


and 999

or

or

constant

Count value entered as C#<value> in


BCD format

PV CV_BCD
R

Description

COUNTER

DEZ

Memory Area

Nr.

DUAL

Data Type

Q
R

BOOL

I, Q, M, D, L, T, C Reset input

CV

WORD

I, Q, M, D, L

Current count value (integer format)

CV_BCD

WORD

I, Q, M, D, L

Current count value (BCD format)

BOOL

I, Q, M, D, L

Status of the counter

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

6-5

Counter Instructions

C10
S_CU
I0.0

CU

I0.2

C#901

PV CV_BCD

I0.3

A change in signal state from 0 to 1 at


input I0.2 sets counter C10 with the value
901. If the signal state of I0.0 changes
from 0 to 1, the value of counter C10 is
incremented by 1, unless the value of
C10 is equal to 999. If I0.3 changes from
0 to 1, the value of C 10 is set to 0. The
signal state of output Q 4.0 is 1 if C10 is
not equal to 0.

CV

Q4.0
=

Status Word Bits

writes

Figure 6-3

6-6

BR

CC1

CC0

OV

OS

OR
x

STA
x

RLO
x

FC
1

Up Counter

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Counter Instructions

6.4

Down Counter

Description

A rising edge (change in signal state from 0 to 1) at input S of the Down


Counter instruction sets the counter with the value at the Preset Value input
(PV). With a rising edge at input CD, the counter is decremented by 1 when
the count value is greater than 0. The counter is reset by rising edge at input
R.
A signal state check for 1 at output Q produces a result of 1 when the count is
greater than 0; the check produces a result of 0 when the count is equal to 0.

Table 6-5

Down Counter Box and Parameters with SIMATIC Mnemonics


Parameter

FBD Box
Z-Nr.
Z RUECK
Z_RUECK
ZR
DUAL

S
ZW

Counter identification number. The


range depends on the CPU.

ZR

BOOL

E, A, M, D, L

ZR input: Down Counter

BOOL

E, A, M, D, L, T, Z Input for presetting the counter

ZW

WORD

E, A, M, D, L

Count value in the range between 0


and 999

or

or

constant

Count value entered as C#<value> in


BCD format

BOOL

E, A, M, D, L, T, Z Reset input

DUAL

WORD

E, A, M, D, L

Current count value (integer format)

DEZ

WORD

E, A, M, D, L

Current count value (BCD format)

BOOL

E, A, M, D, L

Status of the counter

Down Counter Box and Parameters with International Mnemonics


Parameter

FBD Box
C no.
S_CD
S CD
CD
CV

Data Type

Memory Area

Description

no.

COUNTER

Counter identification number. The


range depends on the CPU.

CD

BOOL

I, Q, M, D, L

CD input: Down Counter

BOOL

I, Q, M, D, L, T, C Input for presetting the counter

PV

WORD

I, Q, M, D, L

Count value in the range between 0


and 999

or

or

constant

Count value entered as C#<value> in


BCD format

PV CV_BCD
R

Description

COUNTER

Table 6-6

Memory Area

Nr.

DEZ

Data Type

Q
R

BOOL

I, Q, M, D, L, T, C Reset input

CV

WORD

I, Q, M, D, L

Current count value (integer format)

CV_BCD

WORD

I, Q, M, D, L

Current count value (BCD format)

BOOL

I, Q, M, D, L

Status of the counter

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

6-7

Counter Instructions

Z10
S_CD
I0.0

CD

I0.2

C#901

PV

I0.3

A change in signal state from 0 to 1 at input I0.2


sets counter C10 with the value 89. If the signal
state of input I0.0 changes from 0 to 1, the value
of counter C10 is decreased by 1, unless the
value of counter C 10 is equal to 0. The signal
state of output Q 4.0 is 1 if counter C10 is not
equal to 0. If I0.3 changes from 0 to 1, the value
of C 10 is set to 0.

CV
BCD
Q

Q4.0
=

Status Word Bits

writes

Figure 6-4

6-8

BR

CC1

CC0

OV

OS

OR
x

STA
x

RLO
x

FC
1

Down Counter

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Integer Math Instructions


Chapter
Overview

Section

Description

Page

7.1

Add Integer

7-2

7.2

Add Double Integer

7-3

7.3

Subtract Integer

7-4

7.4

Subtract Double Integer

7-5

7.5

Multiply Integer

7-6

7.6

Multiply Double Integer

7-7

7.7

Divide Integer

7-8

7.8

Divide Double Integer

7-9

7.9

Return Fraction Double Integer

7-10

7.10

Evaluating the Bits of the Status Word with Integer Math


Instructions

7-11

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

7-1

Integer Math Instructions

7.1

Add Integer

Description

Table 7-1

A signal state of 1 at the Enable (EN) input activates the Add Integer
instruction. This instruction adds inputs IN1 and IN2. The result can be
scanned at O. If the result is outside the permissible range for an integer, the
OV and OS bit of the status word are 1 and the ENO is 0.
Add Integer Box and Parameters
Parameters

FBD Box

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

ADD_II
ADD
EN

IN1

INT

I, Q, M, D, L
or constant

First value for addition

IN1

OUT

IN2

INT

Second value for addition

IN2

ENO

I, Q, M, D, L
or constant

OUT

INT

I, Q, M, D, L

Result of addition

ENO

BOOL

I, Q, M, D, L

Enable output

I 0.0

ADD_I
EN

MW0

IN1

OUT

MW2

IN2

ENO

A signal state of 1 at input I 0.0 activates the


ADD_I box. The result of the addition MW0 +
MW2 is entered in memory word MW10. If
the result is outside the permitted range for
an integer or the signal state of input I 0.0 is
0, output Q 4.0 is set to 0 and the instruction
is not executed.

MW10
Q 4.0
=

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 7-1

7-2

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Add Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Integer Math Instructions

7.2

Add Double Integer

Description

Table 7-2

A signal state of 1 at the Enable (EN) input activates the Add Double Integer
instruction. This instruction adds inputs IN1 and IN2. The result can be
scanned at O. If the result is outside the permissible range for a double
integer, the OV and the OS bit of the status word are 1 and the ENO is 0.
Add Double Integer Box and Parameters
Parameters

FBD Box

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

ADD_DI
ADD
DI
EN

IN1

DINT

I, Q, M, D, L or
constant

First value for addition

IN1

OUT

IN2

DINT

Second value for addition

IN2

ENO

I, Q, M, D, L or
constant

OUT

DINT

I, Q, M, D, L

Result of addition

ENO

BOOL

I, Q, M, D, L

Enable output

ADD_DI
EN

I 0.0
MD0

IN1

OUT

MD4

IN2

ENO

MD10
Q 4.0
=

A signal state of 1 at input I 0.0 activates the


ADD_DI box. The result of the addition MD0 +
MD4 is entered in memory double word
MD10. If the result is outside the permitted
range for a double integer or the signal state
of input I 0.0 is 0, output Q 4.0 is set to 0 and
the instruction is not executed.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 7-2

BR
x

CC1
x

CC0
x

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Add Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

7-3

Integer Math Instructions

7.3

Subtract Integer

Description

Table 7-3

A signal state of 1 at the Enable (EN) input activates the Subtract Integer
instruction. This instruction subtracts input IN2 from IN1. The result can be
scanned at O. If the result is outside the permitted range for an integer, the
OV and the OS bit of the status word are 1 and the ENO is 0.
Subtract Integer Box and Parameters

FBD Box

Parameters

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

SUB_II
SUB
EN

IN1

INT

I, Q, M, D, L or
constant

Minuend (value from which second value


is subtracted)

IN1

OUT

IN2

INT

IN2

ENO

I, Q, M, D, L or
constant

Subtrahend (value subtracted from the


first value)

OUT

INT

I, Q, M, D, L

Result of subtraction

ENO

BOOL

I, Q, M, D, L

Enable output

I 0.0

SUB_I
EN

MW0

IN1

OUT

MW2

IN2

ENO

MW10
Q 4.0
=

A signal state of 1 at input I 0.0 activates the


SUB_I box. The result of the subtraction MW0
MW2 is entered in memory word MW10. If
the result is outside the permitted range for an
integer or the signal state of input I 0.0 is 0,
output Q 4.0 is set to 0 and the instruction is
not executed.

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 7-3

7-4

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Subtract Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Integer Math Instructions

7.4

Subtract Double Integer

Description

Table 7-4

A signal state of 1 at the Enable (EN) input activates the Subtract Double
Integer instruction. This instruction subtracts input IN2 from IN1. The result
can be scanned at O. If the result is outside the permitted range for a double
integer, the OV and the OS bit of the status word are 1 and the ENO is 0.
Subtract Double Integer Box and Parameters
Parameters

FBD Box

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

SUB_DI
SUB
DI
EN

IN1

DINT

I, Q, M, D, L or
constant

Minuend (value from which second


value is subtracted)

IN1

OUT

IN2

DINT

IN2

ENO

I, Q, M, D, L or
constant

Subtrahend (value subtracted from


the first value)

OUT

DINT

I, Q, M, D, L

Result of subtraction

ENO

BOOL

I, Q, M, D, L

Enable output

I 0.0

SUB_DI
EN

MD0

IN1

OUT

MD4

IN2

ENO

MD10
Q 4.0
=

A signal state of 1 at input I 0.0 activates the


SUB_DI box. The result of the subtraction
MD0 MD4 is entered in memory double word
MD10. If the result is outside the permitted
range for a double integer or the signal state of
input I 0.0 is 0, output Q 4.0 is set to 0 and the
instruction is not executed.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 7-4

BR
x

CC1
x

CC0
x

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Subtract Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

7-5

Integer Math Instructions

7.5

Multiply Integer

Description

Table 7-5

A signal state of 1 at the Enable (EN) input activates the Multiply Integer
instruction. This instruction multiplies input IN1 by IN2. The result is a
32-bit integer that can be scanned at O. If the result is outside the permitted
range for a 16-bit integer, the OV and the OS bit of the status word are 1 and
the ENO is 0.
Multiply Integer Box and Parameters
Parameters

FBD Box

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

MUL_II
MUL
EN

IN1

INT

I, Q, M, D, L or
constant

Multiplicand (value that is multiplied


by the second value)

IN1

OUT

IN2

INT

IN2

ENO

I, Q, M, D, L or
constant

Multiplier (value by which the first


value is multiplied)

OUT

DINT

I, Q, M, D, L

Result of the multiplication

ENO

BOOL

I, Q, M, D, L

Enable output

I 0.0

MUL_I
EN

MW0

IN1

OUT

MW2

IN2

ENO

MD10
Q 4.0
=

A signal state of 1 at input I 0.0 activates the


MUL_I box. The result of the multiplication
MW0 x MW2 is entered in memory double word
MD10. If the result is outside the permitted
range for a 16-bit integer or the signal state of
input I 0.0 is 0, output Q 4.0 is set to 0 and the
instruction is not executed.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 7-5

7-6

BR
x

CC1
x

CC0
x

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Multiply Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Integer Math Instructions

7.6

Multiply Double Integer

Description

Table 7-6

A signal state of 1 at the Enable (EN) input activates the Multiply Double
Integer instruction. This instruction multiplies inputs IN1 and IN2. The result
can be scanned at O. If the result is outside the permitted range for a double
integer, the OV and the OS bit of the status word are 1 and the ENO is 0.
Multiply Double Integer Box and Parameters
Parameters

FBD Box

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

MUL_DI
MUL
DI
EN

IN1

DINT

I, Q, M, D, L or
constant

Multiplicand (value that is multiplied


by the second value)

IN1

OUT

IN2

DINT

IN2

ENO

I, Q, M, D, L or
constant

Multiplier (value by which the first


value is multiplied)

OUT

DINT

I, Q, M, D, L

Result of the multiplication

ENO

BOOL

I, Q, M, D, L

Enable output

I 0.0

MUL_DI
EN

MD0

IN1

OUT

MD4

IN2

ENO

MD10
Q 4.0
=

A signal state of 1 at input I 0.0 activates the


MUL_DI box. The result of the multiplication
MD0 x MD4 is entered in memory double word
MD10. If the result is outside the permitted
range for a double integer or the signal state of
input I 0.0 is 0, output Q 4.0 is set to 0 and the
instruction is not executed.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 7-6

BR
x

CC1
x

CC0
x

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Multiply Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

7-7

Integer Math Instructions

7.7

Divide Integer

Description

Table 7-7

A signal state of 1 at the Enable (EN) input activates the Divide Integer
instruction. This instruction divides input IN1 by IN2. The integer quotient
(truncated result) can be scanned at O. The remainder cannot be scanned. If
the quotient is outside the permitted range for an integer, the OV and the OS
bit of the status word are 1 and the ENO is 0.
Divide Integer Box and Parameters

FBD Box

Parameters

DIV I
DIV_I

Data Type

OUT

IN2

ENO

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN1

INT

I, Q, M, D, L or
constant

Dividend

IN2

INT

I, Q, M, D, L or
constant

Divisor

OUT

INT

I, Q, M, D, L

Result of division

ENO

BOOL

I, Q, M, D, L

Enable output

EN
IN1

Memory Area

I 0.0

DIV_I
EN

MW0

IN1

OUT

MW2

IN2

ENO

MW10
Q 4.0
=

A signal state of 1 at input I 0.0 activates the


DIV_I box. The quotient of dividing MW0 by
MW2 is entered in memory word MW10. If the
quotient is outside the permitted range for an
integer or the signal state of input I 0.0 is 0,
output Q 4.0 is set to 0 and the instruction is
not executed.

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 7-7

7-8

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Divide Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Integer Math Instructions

7.8

Divide Double Integer

Description

Table 7-8

A signal state of 1 at the Enable (EN) input activates the Divide Double
Integer instruction. This instruction divides input IN1 by IN2. The quotient
(truncated result) can be scanned at O. The Divide Double Integer instruction
stores the quotient as a single 32-bit value in DINT format. This instruction
does not produce a remainder. If the quotient is outside the permitted range
for a double integer, the OV and the OS bit of the status word are 1 and the
ENO is 0.
Divide Double Integer Box and Parameters
Parameters

FBD Box

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

DIV_DI
DIV
DI
EN

IN1

DINT

I, Q, M, D, L or
constant

Dividend

IN1

OUT

IN2

DINT

ENO

I, Q, M, D, L or
constant

Divisor

IN2

OUT

DINT

I, Q, M, D, L

Result of division

ENO

BOOL

I, Q, M, D, L

Enable output

I 0.0

DIV_DI
EN

MD0

IN1

OUT

MD4

IN2

ENO

MD10
Q 4.0
=

A signal state of 1 at input I 0.0 activates the


DIV_DI box. The quotient of dividing MD0 by
MD4 is entered in memory double word
MD10. If the quotient is outside the permitted
range for a double integer or the signal state
of input I 0.0 is 0, output Q 4.0 is set to 0 and
the instruction is not executed.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 7-8

BR
x

CC1
x

CC0
x

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Divide Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

7-9

Integer Math Instructions

7.9

Return Fraction Double Integer

Description

Table 7-9

A signal state of 1 at the Enable (EN) input activates the Return Fraction
Double Integer instruction. This instruction divides input IN1 by IN2. The
remainder (fraction) can be scanned at O. If the result is outside the permitted
range for a double integer, the OV and the OS bit of the status word are 1 and
the ENO is 0.
Return Fraction Double Integer Box and Parameters

FBD Box

Parameters

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

MOD
EN

IN1

DINT

I, Q, M, D, L or
constant

Dividend

IN1

OUT

IN2

DINT

ENO

I, Q, M, D, L or
constant

Divisor

IN2

OUT

DINT

I, Q, M, D, L

Remainder

ENO

BOOL

I, Q, M, D, L

Enable output

I 0.0

MOD
EN

MD0

IN1

OUT

MD4

IN2

ENO

MD10
Q 4.0
=

A signal state of 1 at input I 0.0 activates the


MOD box. The remainder (fraction) of
dividing MD0 by MD4 is stored in memory
double word MD10. If the result is outside
the permitted range for a double integer or
the signal state of input I 0.0 is 0, output Q
4.0 is set to 0 and the instruction is not
executed.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 7-9

7-10

BR
x

CC1
x

CC0
x

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Return Fraction Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Integer Math Instructions

7.10 Evaluating the Bits of the Status Word with Integer Math
Instructions

Description

The integer math instructions influence the following bits in the status word:

S CC1 and CC0


S OV
S OS
A dash (-) in the table means that the bit is not affected by the result of the
instruction.
Table 7-10

Signal State of the Status Word Bits (Result in Valid Range)


Status Word Bits

Valid Range of the Result


Integers (16 and 32 bits)

CC1

CC0

OV

OS

0 (zero)

16 bits: -32 768 v result t 0 (negative number)


32 bits: -2 147 483 648 v result t 0 (negative number)

16 bits: 32 767 w result u0 (positive number)


32 bits: 2 147 483 647 w result u0 (positive number)

Table 7-11

Signal State of the Status Word Bits (Result not in Valid Range)
Invalid Range for the Result

Status Word Bits

Integers (16 and 32 bits)

CC1

CC0

OV

OS

32 767 (positive number)


2 147 483 647 (positive number)

16 bits: result t -32 768 (negative number)


32 bits: result t -2 147 483 648 (negative number)

16 bits: result u
32 bits: result u

Table 7-12

Signal State of the Status Word Bits (Math Instructions with Integers
(32 Bits) +D, /D and MOD)
Operation

Status Word Bits


CC1

CC0

OV

OS

+D: result = -4 294 967 296

/D or MOD: division by 0

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

7-11

Integer Math Instructions

7-12

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Floating-Point Math Instructions


Chapter
Overview

Section

Description

8
Page

8.1

Overview

8-2

8.2

Add Real

8-3

8.3

Subtract Real

8-4

8.4

Multiply Real

8-5

8.5

Divide Real

8-6

8.6

Evaluating the Bits of the Status Word with Floating-Point


Instructions

8-7

8.7

Forming the Absolute Value of a Floating-Point Number

8-8

8.8

Forming the Square (SQR) of a Floating-Point Number

8-9

8.9

Forming the Square Root (SQRT) of a Floating-Point


Number

8.10

Forming the Natural Logarithm of a Floating-Point Number

8-11

8.11

Forming the Exponential Value of a Floating-Point Number

8-12

8.12

Forming Trigonometric Functions of Angles as


Floating-Point Numbers

8-13

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

8-10

8-1

Floating-Point Math Instructions

8.1

Overview
You can use the floating-point math instructions to perform the following
math operations using two 32-bit IEEE floating-point numbers:

S Add
S Subtract
S Multiply
S Divide
The IEEE 32-bit floating-point numbers belong to the data type known as
REAL. Using floating-point math, you can carry out the following operations
with one 32-bit IEEE floating-point number:

S Form the absolute value (ABS) of a floating-point number


S Form the square (SQR) or square root (SQRT) of a floating-point number
S Form the natural logarithm (LN) of a floating-point number
S Form the exponential value of a floating-point number (EXP) to
base e (= 2.71828...)

S Form the following trigonometric functions of an angle, represented as a


32-bit floating-point number:
Form the sine of a floating-point number (SIN) and form the arc sine
of a floating-point number (ASIN)
Form the cosine of a floating-point number (COS) and form the arc
cosine of a floating-point number (ACOS)
Form the tangent of a floating-point number (TAN) and form the arc
tangent of a floating-point number (ATAN)

8-2

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Floating-Point Math Instructions

8.2

Add Real

Description

A signal state of 1 at the Enable input (EN) activates the Add Real
instruction. This instruction adds inputs IN1 and IN2. The result can be
scanned at output OUT. If either of the inputs or the result is not a
floating-point number, the OV bit and OS bit are set to 1 and ENO is set to 0.
For more detailed information about evaluating the bits in the status word,
refer to Section 8.6.

Table 8-1

Add Real Box and Parameters

FBD Box

Parameters

ADD_R
ADD
R
EN
IN1

OUT

IN2

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN1

REAL

I, Q, M, D, L or
constant

First number to be added

IN2

REAL

I, Q, M, D,or
constant L

Second number to be added

OUT

REAL

I, Q, M, D, L

Result of addition

ENO

BOOL

I, Q, M, D, L

Enable output

I0.0

ADD_R
EN

MD0

IN1

OUT

MD4

IN2

ENO

A signal state of 1 at input I0.0 activates the


ADD_R box. The result of the addition MD0
+ MD4 is entered in memory double word
MD10. If either of the inputs or the result is
not a floating-point number and if the signal
state of I0.0 is 0, output Q4.0 is set to 0 and
the instruction is not executed.

MD10
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 8-1

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Add Real

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

8-3

Floating-Point Math Instructions

8.3

Subtract Real

Description

A signal state of 1 at the Enable input (EN) activates the Subtract Real
instruction. This instruction subtracts input IN2 from IN1. The result can be
scanned at output OUT. If either of the inputs or the result is not a
floating-point number, the OV bit and the OS bit are set to 1 and ENO is set
to 0.
For more detailed information about evaluating the bits in the status word,
refer to Section 8.6.

Table 8-2

Subtract Real Box and Parameters


Parameters

FBD Box
SUB_R
SUB
R
EN
IN1

OUT

IN2

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN1

REAL

I, Q, M, D, L or
constant

Minuend (from which the second


value is subtracted)

IN2

REAL

I, Q, M, D, L or
constant

Subtrahend (that is subtracted


from the first value)

OUT

REAL

I, Q, M, D, L

Result of subtraction

ENO

BOOL

I, Q, M, D, L

Enable output

I0.0

SUB_R
EN

MD0

IN1

OUT

MD4

IN2

ENO

A signal state of 1 at input I0.0 activates the


SUB_R box. The result of the subtraction
MD0 MD4 is entered in memory double
word MD10. If either of the inputs or the
result is not a floating-point number and if
the signal state of I0.0 is 0, output Q4.0 is
set to 0 and the instruction is not executed.

MD10
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x
Figure 8-2

8-4

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Subtract Real

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Floating-Point Math Instructions

8.4

Multiply Real

Description

A signal state of 1 at the Enable input (EN) activates the Multiply Real
instruction. This instruction multiplies input IN1 by IN2. The result can be
scanned at output OUT. If either of the inputs or the result is not a
floating-point number, the OV bit and the OS bit are set to 1 and ENO is set
to 0.
For more detailed information about evaluating the bits in the status word,
refer to Section 8.6.

Table 8-3

Multiply Real Box and Parameters


Parameters

FBD Box
MUL_R
MUL
R
EN
IN1

OUT

IN2

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN1

REAL

I, Q, M, D, L or
constant

Multiplicand (value to be
multiplied)

IN2

REAL

I, Q, M, D, L or
constant

Multiplier (value by which first


value is multiplied)

OUT

REAL

I, Q, M, D, L

Result of multiplication

ENO

BOOL

I, Q, M, D, L

Enable output

I0.0

MUL_R
EN

MD0

IN1

OUT

MD4

IN2

ENO

A signal state of 1 at input I0.0 activates the


MUL_R box. The result of the multiplication
MD0 x MD4 is entered in memory double
word MD10. If either of the inputs or the
result is not a floating-point number and if the
signal state of I0.0 is 0, output Q4.0 is set to
0 and the instruction is not executed.

MD10
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 8-3

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Multiply Real

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

8-5

Floating-Point Math Instructions

8.5

Divide Real

Description

A signal state of 1 at the Enable input (EN) activates the Divide Real
instruction. This instruction divides input IN1 by IN2. The result can be
scanned at output OUT. If either of the inputs or the result is not a
floating-point number, the OV bit and the OS bit are set to 1 and ENO is set
to 0.
For more detailed information about evaluating the bits in the status word,
refer to Section 8.6.

Table 8-4

Divide Real Box and Parameters

FBD Box

Parameters

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

DIV_R
DIV
R
EN

IN1

REAL

I, Q, M, D, L or
constant

Dividend (value to be divided by


second value)

IN1

OUT

IN2

REAL

IN2

ENO

I, Q, M, D, L or
constant

Divisor (value by which first


value is divided)

OUT

REAL

I, Q, M, D, L

Result of division

ENO

BOOL

I, Q, M, D, L

Enable output

I0.0

DIV_R
EN

MD0

IN1

OUT

MD4

IN2

ENO

A signal state of 1 at input I0.0 activates the


DIV_R box. The result of dividing MD0 by
MD4 is entered in memory double word
MD10. If either of the inputs or the result is
not a floating-point number and if the signal
state of I0.0 is 0, output Q4.0 is set to 0 and
the instruction is not executed.

MD10
Q4.0
=
Status Word Bits

Instruction is executed (EN = 1):


writes

Figure 8-4

8-6

BR
x

CC1
x

CC0
x

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Divide Real

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Floating-Point Math Instructions

8.6

Evaluating the Bits of the Status Word with Floating-Point


Instructions

Description

Floating-point instructions affect the following bits in the status word:

S CC1 and CC0


S OV
S OS
A dash () in the table means that the bit is not affected by the result of the
instruction.
Table 8-5

Signal State of the Status Word Bits for Results of Instructions with
Floating-Point Numbers (Result in the Valid Range)
Valid Range for Result

Instruction with Floating-Point Numbers (32


Bits)

Status Word Bits


CC1

CC0

OV

OS

+0, 0 (zero)

3.402823E+38 < result < 1.175494E38


(negative number)

+1.175494E38 < result < 3.402823E+38


(positive number)

Table 8-6

Signal State of the Status Word Bits for Results of Instructions with
Floating-Point Numbers (Result outside the Valid Range)
Invalid Range for Result

Instruction with Floating-Point Numbers (32


Bits)

Status Word Bits


CC1

CC0

OV

OS

1.175494E38 < result < 1.401298E45


(negative number) below minimum

+1.401298E45 < result < +1.175494E38


(positive number) below minimum

result < 3.402823E+38


(negative number) above maximum

result > 3.402823E+38


(positive number) above maximum

result < 3.402823E+38


or result > +3.402823E+38
not a floating-point number

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

8-7

Floating-Point Math Instructions

8.7

Forming the Absolute Value of a Floating-Point Number

Description

Table 8-7

With the Form the Absolute Value of a Floating-Point Number instruction,


you can form the absolute value of floating-point number.
ABS Box and Parameters
Parameters

FBD Box

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

ABS
EN OUT

IN

REAL

I, Q, M, D, L or
constant

Input value: floating-point number

IN

OUT

REAL

I, Q, M, D, L

Output value: absolute value of the


floating-point number

ENO

BOOL

I, Q, M, D, L

Enable output

ENO

If I0.0 = 1, the absolute value of MD8 is


output at MD12.

ABS
I0.0

EN

OUT

MD8

IN

ENO

MD8 = +6.234 x 103 results in


MD12 = 6.234 x 103.

MD12
Q4.0
=

Output Q4.0 is 0 if the conversion is not


executed (ENO = EN = 0).

Status Word Bits


Instruction is executed (EN = 1):
writes
Figure 8-5

8-8

BR
X

CC1

CC0

OV

OS

OR
0

STA
X

RLO
X

FC
1

Forming the Absolute Value of a Floating-Point Number

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Floating-Point Math Instructions

8.8

Forming the Square (SQR) of a Floating-Point Number

Description

With the Form the Square of a Floating-Point Number instruction, you can
square a floating-point number. If either of the inputs or the result is not a
floating-point number, the OV bit and OS bit are set to 1 and ENO is set to 0.

Parameter

Table 8-8 shows the SQR box and describes the parameters.
Table 8-8

SQR Box and Parameters

FBD Box

Parameters

SQR
EN OUT
IN

MD0

EN

OUT

IN

ENO

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Number

OUT

REAL

I, Q, M, D, L

Square of the
number

ENO

BOOL

I, Q, M, D, L

Enable output

ENO

A signal state of 1 at input I0.0 activates the


SQR box. The result of SQR (MD0) is
entered in the memory double word MD10. If
MD0 is less than 0 or if either of the inputs or
the result is not a floating-point number and if
the signal state of I0.0 is 0, output Q4.0 is set
to 0.

SQR
I0.0

Data
Type

MD10
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 8-6

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Forming the Square of a Floating-Point Number

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

8-9

Floating-Point Math Instructions

8.9

Forming the Square Root (SQRT) of a Floating-Point Number

Description

With the Form the Square Root of a Floating-Point Number instruction, you
can extract the square root of a floating-point number. This instruction
returns a positive result, if the value at the address is greater than 0. If
either of the inputs or the result is not a floating-point number, the OV bit
and OS bit are set to 1 and ENO is set to 0.

Parameter

Table 8-9 shows the SQRT box and describes the parameters.

Table 8-9

SQRT Box and Parameters

FBD Box

SQRT
OUT
EN
IN

Parameters

MD0

EN

OUT

IN

ENO

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Number

OUT

REAL

I, Q, M, D, L

Square root of
the number

ENO

BOOL

I, Q, M, D, L

Enable output

ENO

A signal state of 1 at input I0.0 activates the


SQRT box. The result of SQRT (MD0) is
entered in memory double word MD10. If
MD0 is less than 0 or if either of the inputs or
the result is not a floating-point number and if
the signal state of I0.0 is 0, output Q4.0 is set
to 0.

SQRT
I0.0

Data
Type

MD10
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 8-7

8-10

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Forming the Square Root of a Floating-Point Number

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Floating-Point Math Instructions

8.10 Forming the Natural Logarithm of a Floating-Point Number

Description

With the Form the Natural Logarithm of a Floating-Point Number


instruction, you can form the natural logarithm of a floating-point number. If
either of the inputs or the result is not a floating-point number, the OV bit
and OS bit are set to 1 and ENO is set to 0.
Table 8-10

LN Box and Parameters


Parameters

FBD Box

LN
OUT
EN
IN

EN

OUT

MD0

IN

ENO

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Number

OUT

REAL

I, Q, M, D, L

Natural
logarithm of the
number

ENO

BOOL

I, Q, M, D, L

Enable output

ENO

A signal state of 1 at input I0.0 activates the


LN box. The result of LN (MD0) is entered in
memory double word MD10. If MD0 is less
than 0 or if either of the inputs or the result is
not a floating-point number and if the signal
state of I0.0 is 0, output Q4.0 is set to 0.

LN
I0.0

Data
Type

MD10
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 8-8

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Forming the Natural Logarithm of a Floating-Point Number

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

8-11

Floating-Point Math Instructions

8.11 Forming the Exponential Value of a Floating-Point Number

Description

With the Form the Exponential Value of a Floating-Point Number


instruction, you can form the exponential value of a floating-point number to
base e (= 2.71828...). If either of the inputs or the result is not a
floating-point number, the OV bit and OS bit are set to 1 and ENO is set to 0.
Table 8-11

EXP Box and Parameters


Parameters

FBD Box

EXP
EN
OUT
IN

ENO

EN

OUT

MD0

IN

ENO

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Number

OUT

REAL

I, Q, M, D, L

Exponent of
the number

ENO

BOOL

I, Q, M, D, L

Enable output

A signal state of 1 at input I0.0 activates the


EXP box. The result of EXP (MD0) is entered
in memory double word MD10. If either of the
inputs or the result is not a floating-point
number and if the signal state of E 0.0 is 0,
output Q4.0 is set to 0.

EXP
I0.0

Data
Type

MD10
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 8-9

8-12

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Forming the Exponential Value of a Floating-Point Number

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Floating-Point Math Instructions

8.12 Forming Trigonometric Functions of Angles as Floating-Point


Numbers

Description

With the following instructions, you can form trigonometric functions of


angles represented as 32-bit IEEE floating-point numbers.
Instruction

Meaning

SIN

Form the sine of a floating-point number of an angle specified in


radians.

ASIN

Form the arc sine of a floating-point number . The result is an angle


specified in radians. The value is in the following range:
-p / 2 v arc sine v + p / 2, where p = 3.14...

COS

Form the cosine of a floating-point number of an angle specified in


radians.

ACOS

Form the arc cosine of a floating-point number . The result is an angle


specified in radians. The value is in the following range:
0 v arc cosinev + p, where p = 3.14...

TAN

Form the tangent of a floating-point number of an angle specified in


radians.

ATAN

Form the arc tangent of a floating-point number . The result is an angle


specified in radians. The value is in the following range:
-p / 2 v arc tangent v + p / 2, where p = 3.14...

Parameter

Tables 8-12 through 8-17 show the SIN, ASIN, COS, ACOS, TAN and ATAN
boxes and describe the parameters.
Table 8-12

SIN Box and Parameters

FBD Box

SIN
EN OUT
IN

ENO

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Parameters

Data
Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Number

OUT

REAL

I, Q, M, D, L

Sine of the
number

ENO

BOOL

I, Q, M, D, L

Enable output

8-13

Floating-Point Math Instructions

Table 8-13

ASIN Box and Parameters

FBD Box

ASIN
EN
OUT
IN

Table 8-14

ENO

COS
EN
OUT

Table 8-15

ENO

ACOS
EN
OUT

Table 8-16

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Number

OUT

REAL

I, Q, M, D, L

Arc sine of the


number

ENO

BOOL

I, Q, M, D, L

Enable output

Parameters

Data
Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Number

OUT

REAL

I, Q, M, D, L

Cosine of the
number

ENO

BOOL

I, Q, M, D, L

Enable output

Parameters

Data
Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Number

OUT

REAL

I, Q, M, D, L

Arc cosine of
the number

ENO

BOOL

I, Q, M, D, L

Enable output

TAN Box and Parameters

TAN
OUT
EN

8-14

Description

EN

ENO

FBD Box

IN

Memory Area

ACOS Box and Parameters

FBD Box

IN

Data
Type

COS Box and Parameters

FBD Box

IN

Parameters

Parameters

Data
Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Number

OUT

REAL

I, Q, M, D, L

Tangent of the
number

ENO

BOOL

I, Q, M, D, L

Enable output

ENO

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Floating-Point Math Instructions

Table 8-17

ATAN Box and Parameters


Parameters

FBD Box

ATAN
EN
OUT
IN

ENO

MD0

EN
IN

OUT

Description

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Number

OUT

REAL

I, Q, M, D, L

Arc tangent of
the number

ENO

BOOL

I, Q, M, D, L

Enable output

A signal state of 1 at input I0.0 activates the


SIN box. The result of SIN (MD0) is entered in
memory double word MD10. If either of the
inputs or the result is not a floating-point
number and if the signal state of I0.0 is 0,
output Q4.0 is set to 0.

MD10
Q4.0
=

ENO

Memory Area

EN

SIN
I0.0

Data
Type

Status Word Bits


Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 8-10

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Forming the Sine of a Floating-Point Number

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

8-15

Floating-Point Math Instructions

8-16

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Comparison Instructions
Chapter
Overview

Section

Description

Page

9.1

Compare Integer

9-2

9.2

Compare Double Integer

9-3

9.3

Compare Real

9-4

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

9-1

Comparison Instructions

9.1

Compare Integer

Description

The Compare Integer instruction compares two values on the basis of 16-bit
floating-point numbers. This instruction compares inputs IN1 and IN2
according to the type of comparison you select from the list box. The
following table lists the available types of comparison.
If the comparison is true, the result of logic operation (RLO) of the
comparison is 1. Otherwise, it is 0. You cannot negate the comparison result
itself, but you can achieve the same effect as negation by using the opposite
compare function.
Table 9-1

Types of Comparison for Integers


Relational Operator

Type of Comparison

Table 9-2

IN1 is equal to IN2.

==

IN1 is not equal to IN2.

<>

IN1 is greater than IN2.

>

IN1 is less than IN2.

<

IN1 is greater than or equal to IN2.

>=

IN1 is less than or equal to IN2.

<=

Compare Integer Box and Parameters (Example using Equal)


Parameters

FBD Box
CMP
== I
IN1

Data Type

Memory Area

Description

IN1

INT

I, Q, M, D, L or
constant

First value to compare

IN2

INT

I, Q, M, D, L or
constant

Second value to compare

Box output

BOOL

I, Q, M, D, L

Result of comparison

IN2

Q4.0 is set when:

MW0

CMP
== I
IN1

MW2

IN2

MW0 is equal to MW2 AND the signal state


is 1 at input I0.0

&
I0.0

Q4.0
S
Status Word Bits

Comparison is true:
writes
Figure 9-1

9-2

BR
x

CC1
x

CC0
x

OV
0

OS

OR
0

STA
1

RLO
x

FC
1

Compare Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Comparison Instructions

9.2

Compare Double Integer

Description

The Compare Double Integer instruction compares two values on the basis of
32-bit floating-point numbers. This instruction compares inputs IN1 and IN2
according to the type of comparison you select from the list box. The
following table lists the available types of comparison.
If the comparison is true, the result of logic operation (RLO) of the
comparison is 1. Otherwise, it is 0. You cannot negate the comparison result
itself, but you can achieve the same effect as negation by using the opposite
compare function.
Table 9-3

Types of Comparison for Double Integers


Relational Operator

Type of Comparison

Table 9-4

IN1 is equal to IN2.

==

IN1 is not equal to IN2.

<>

IN1 is greater than IN2.

>

IN1 is less than IN2.

<

IN1 is greater than or equal to IN2.

>=

IN1 is less than or equal to IN2.

<=

Compare Double Integer Box and Parameters (Example using Not Equal)

FBD Box
CMP
<> D
IN1
IN2

Parameters

Data Type

IN1

MD4

IN2

Description

IN1

DINT

I, Q, M, D, L or
constant

First value to compare

IN2

DINT

I, Q, M, D, L or
constant

Second value to compare

Box output

BOOL

I, Q, M, D, L

Result of comparison

Q4.0 is set when:

CMP
<> D
MD0

Memory Area

&

S MD0 is not equal to MD4

I0.0

S AND the signal state at

Q4.0
S

at input I0.0 is 1

Status Word Bits


Comparison is true:
BR
writes

Figure 9-2

CC1
x

CC0
x

OV
0

OS

OR
0

STA
x

RLO
x

FC
1

Compare Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

9-3

Comparison Instructions

9.3

Compare Real

Description

The Compare Real instruction compares two values on the basis of


floating-point numbers. This instruction compares inputs IN1 and IN2
according to the type of comparison you select from the list box. The
following table lists the available types of comparison.
If the comparison is true, the result of logic operation (RLO) of the
comparison is 1. Otherwise, it is 0. You cannot negate the comparison result
itself, but you can achieve the same effect as negation by using the opposite
compare function.
Table 9-5

Types of Comparison for Floating-Point Numbers


Relational Operator

Type of Comparison

Table 9-6

IN1 is equal to IN2.

==

IN1 is not equal to IN2.

<>

IN1 is greater than IN2.

>

IN1 is less than IN2.

<

IN1 is greater than or equal to IN2.

>=

IN1 is less than or equal to IN2.

<=

Compare Real Box and Parameters (Example using Less Than)

FBD Box
CMP
<R
IN1
IN2

Parameters

Data Type

IN1

REAL

I, Q, M, D, L or
constant

First value to compare

IN2

REAL

I, Q, M, D, L or
constant

Second value to compare

Box output

BOOL

I, Q, M, D, L

Result of comparison

IN1

MD4

IN2

Description

Q4.0 is set when:

CMP
<R
MD0

Memory Area

&

S MD0 is less than MD4

I0.0

S AND the signal state at

Q4.0

input I0.0 is 1

Status Word Bits


Comparison is true:
BR
CC1
writes
Figure 9-3

9-4

CC0

OV

OS

OR

STA

RLO

FC

Compare Real
Function Block Diagram (FBD) for S7-300 and S7-400
C79000-G7076-C566-01

Move and Conversion Instructions


Chapter
Overview

Section

Description

10
Page

10.1

Assign Value

10-2

10.2

BCD to Integer

10-3

10.3

Integer to BCD

10-4

10.4

Integer to Double Integer

10-5

10.5

BCD to Double Integer

10-6

10.6

Double Integer to BCD

10-7

10.7

Double Integer to Real

10-8

10.8

Ones Complement Integer

10-9

10.9

Ones Complement Double Integer

10-10

10.10

Twos Complement Integer

10-11

10.11

Twos Complement Double Integer

10-12

10.12

Negate Real Number

10-13

10.13

Round to Double Integer

10-14

10.14

Truncate Double Integer Part

10-15

10.15

Ceiling

10-16

10.16

Floor

10-17

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

10-1

Move and Conversion Instructions

10.1 Assign Value

Description

With the Assign Value instruction, you can assign specific values to variables.
The value specified at the IN input is copied to the address specified at the
OUT output. ENO has the same signal state as EN.
With the MOVE box, the Assign Value instruction can copy all data types
with lengths of 8, 16, or 32 bits. User-defined data types such as arrays or
structures must be be copied with the system function SFC20 BLKMOV
(see the Reference Manual /235/).
The Assign Value instruction is affected by the Master Control Relay (MCR).
For more information on how the MCR functions, see Section 16.5.

Table 10-1

Assign Value Box and Parameters


Parameters

FBD Box

MOVE
EN

OUT

IN

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

All data types with a


length of 8, 16 or
32 bits

I, Q, M, D, L or
constant

Source value

OUT

All data types with a


length of 8, 16 or
32 bits

I, Q, M, D, L

Destination address

ENO

BOOL

I, Q, M, D, L

Enable output

The instruction is executed, when input I0.0 is


1. The content of MW10 is copied to data word
12 of the open DB.

MOVE
I0.0

EN

OUT

MW10

IN

ENO

DBW12
Q4.0
=

If the instruction is executed, Q4.0 is set to 1.

Status Word Bits


Instruction is executed (EN = 1):
writes
Figure 10-1

BR
1

CC0

OV

OS

OR
0

STA
1

RLO
1

FC
1

Assign Value

Assigning Values
to Variables

10-2

CC1

For information about integrated system functions that can be used as move
instructions and that can assign a specific value to a variable or can copy
variables of varying types, refer to the Reference Manual /235/.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Move and Conversion Instructions

10.2 BCD to Integer

Description

The BCD to Integer instruction reads the content of the input parameter IN as
a three-digit number in binary coded decimal format (BCD, " 999) and
converts this number to an integer value. The output parameter OUT contains
the result.
ENO always has the same signal state as EN.
If any of the individual decimal numbers in the BCD number is in the invalid
range between 10 and 15, a BCD error occurs when the conversion is
attempted, causing the following reaction:

S The CPU changes to the STOP mode. BCD conversion error is entered
in the diagnostic buffer with event ID number 2521.

S If OB121 is programmed, it is called.


For more detailed information about programming OB121, refer to the
Reference Manual /235/.
Table 10-2

BCD to Integer Box and Parameters


Parameters

FBD Box
BCD I
BCD_I
EN

OUT

IN

ENO

Data Type

Memory Area

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

WORD

I, Q, M, D, L or
constant

Number in BCD format

OUT

INT

I, Q, M, D, L

Integer value of the BCD number

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal


state of I0.0 is 1. The content of memory
word MW10 is read as a three-digit
number in BCD format and converted to
an integer. The result is stored in memory
word MW12. If the conversion is executed,
the signal state of output Q4.0 is 1 (ENO =
EN).

BCD_I
I0.0

EN

MW10

IN

Description

OUT

MW12
Q4.0
=

ENO

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-2

BR
1

CC1

CC0

OV

OS

OR
0

STA
1

RLO
1

FC
1

BCD to Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

10-3

Move and Conversion Instructions

10.3 Integer to BCD

Description

Table 10-3

The Integer to BCD instruction reads the content of the input parameter IN as
an integer value and converts this value to a three-digit number in binary
coded decimal format (BCD, " 999). The output parameter OUT contains
the result. If an overflow occurs, ENO is set to 0.
Integer to BCD Box and Parameters
Parameters

FBD Box
I BCD
I_BCD
EN

OUT

IN

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

INT

I, Q, M, D,or
constant L

Integer

OUT

WORD

I, Q, M, D, L

BCD value of the integer

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal


state of I0.0 is 1. The content of memory
word MW10 is read as an integer and
converted to a three-digit number in BCD
format. The result is stored in memory
word MW12. If an overflow occurs, the
signal state of output Q4.0 is 0. If the
signal state at input EN is 0 (meaning
that the conversion is not executed), the
signal state of output Q4.0 is also 0.

I_BCD
I0.0

EN

OUT

MW10

IN

ENO

MW12
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-3

10-4

BR
x

CC1

CC0

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Integer to BCD

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Move and Conversion Instructions

10.4 Integer to Double Integer

Description

Table 10-4

The Integer to Double Integer instruction reads the content of the input
parameter IN as an integer and converts the integer to a double integer. The
output parameter OUT contains the result. ENO always has the same signal
state as EN.
Integer to Double Integer Box and Parameters
Parameters

FBD Box
II_DI
DI
EN OUT
IN

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

INT

I, Q, M, D, L or
constant

Value to be converted

OUT

DINT

I, Q, M, D, L

Result

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal


state of I0.0 is 1. The content of memory
word MW10 is read as an integer and
converted to a double integer. The result is
stored in memory double word MD12. If the
conversion is executed, the signal state of
output Q4.0 is 1 (ENO = EN).

I_DI
I0.0

EN

OUT

MW10

IN

ENO

MD12
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-4

BR
1

CC1

CC0

OV

OS

OR
0

STA
1

RLO
1

FC
1

Integer to Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

10-5

Move and Conversion Instructions

10.5 BCD to Double Integer

Description

The BCD to Double Integer instruction reads the content of the input
parameter IN as a seven-digit number in binary coded decimal format (BCD,
" 9,999,999) and converts this number to a double integer value. The output
parameter OUT contains the result.
ENO always has the same signal state as EN.
If any of the individual decimal numbers in the BCD number is in the invalid
range between 10 and 15, a BCD error occurs when the conversion is
attempted, causing the following reaction:

S The CPU changes to the STOP mode. BCD conversion error is entered
in the diagnostic buffer with event ID number 2521.

S If OB121 is programmed, it is called.


For more detailed information about programming OB121, refer to the
Reference Manual /235/.
Table 10-5

BCD to Double Integer Box and Parameters


Parameters

FBD Box
BCD DI
BCD_DI
EN

OUT

IN

ENO

Data Type

Memory Area

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

DWORD

I, Q, M, D, L or
constant

Number in BCD format

OUT

DINT

I, Q, M, D, L

Double integer value of the BCD


number

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal


state of I0.0 is 1. The content of memory
double word MD8 is read as a seven-digit
number in BCD format and converted to a
double integer. The result is stored in MD12.
If the conversion is executed, the signal
state of output Q4.0 is 1 (ENO = EN).

BCD_DI
I0.0
MD8

Description

EN

OUT

IN

ENO

MD12
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-5

10-6

BR
1

CC1

CC0

OV

OS

OR
0

STA
1

RLO
1

FC
1

BCD to Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Move and Conversion Instructions

10.6 Double Integer to BCD

Description

Table 10-6

The Double Integer to BCD instruction instruction reads the content of the
input parameter IN as a double integer value and converts this value to a
seven-digit number in BCD format (" 9 999 999). The output parameter
OUT contains the result. If an overflow occurs, ENO is set to 0.
Double Integer to BCD Box and Parameters
Parameters

FBD Box
DI BCD
DI_BCD
EN

OUT

IN

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

DINT

I, Q, M, D, L or
constant

Double integer

OUT

DWORD

I, Q, M, D, L

BCD value of the double integer

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal


state of I0.0 is 1. The content of memory
double word MD8 is read as a double
integer and converted to a seven-digit
number in BCD format. The result is stored
in MD12. If an overflow occurs, the signal
state of output Q4.0 is 0. If the signal state at
input EN is 0 (meaning that the conversion is
not executed), the signal state of output
Q4.0 is also 0.

DI_BCD
I0.0

EN

OUT

MD8

IN

ENO

MD12
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
writes
Figure 10-6

BR
x

CC1

CC0

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Double Integer to BCD

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

10-7

Move and Conversion Instructions

10.7 Double Integer to Real

Description

Table 10-7

The Double Integer to Real instruction reads the content of the input
parameter IN as a double integer value and converts this value to a real
number. The output parameter OUT contains the result. ENO always has the
same signal state as EN.
Double Integer to Real Box and Parameters
Parameters

FBD Box
DI R
DI_R
EN
IN

OUT
ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

DINT

I, Q, M, D, L or
constant

Value to be converted

OUT

REAL

I, Q, M, D, L

Result

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal


state of I0.0 is 1. The contents of memory
double word MD8 is read as an integer
and converted to a real number. The result
is stored in memory double word MD12. If
the conversion is not executed, the signal
state of output Q4.0 is 0 (ENO=EN).

DI_R
I0.0

EN

OUT

MD8

IN

ENO

MD12

Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-7

10-8

BR
1

CC1

CC0

OV

OS

OR
0

STA
1

RLO
1

FC
1

Double Integer to Real

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Move and Conversion Instructions

10.8 Ones Complement Integer

Description

Table 10-8

The Ones Complement Integer instruction reads the content of the input
parameter IN and performs the Boolean word logic instruction Exclusive Or
Word (see Section 11.6) masked by FFFFH, so that the value of every bit is
inverted. The output parameter OUT contains the result. ENO always has the
same signal state as EN.
Ones Complement Integer Box and Parameters
Parameters

FBD Box
INV I
INV_I
EN

OUT

IN

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

INT

I, Q, M, D, L or
constant

Input value

OUT

INT

I, Q, M, D, L

Ones complement of the integer

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal


state of I0.0 is 1. The value of every bit in
MW8 is inverted.
MW8 = 01000001 10000001
MW10 = 10111110 01111110
The conversion is not executed when the
signal state of I0.0 is 0 and Q4.0 is 0 (ENO
= EN).

INV_I
I0.0

EN

OUT

MW8

IN

ENO

MW10
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-8

BR
1

CC1

CC0

OV

OS

OR
0

STA
1

RLO
1

FC
1

Ones Complement Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

10-9

Move and Conversion Instructions

10.9 Ones Complement Double Integer

Description

Table 10-9

The Ones Complement Double Integer instruction reads the content of the
input parameter IN and performs the Boolean word logic operation Exclusive
Or Word (see Section 11.6) masked by FFFF FFFFH, so that the value of
every bit is inverted. The output parameter OUT contains the result. ENO
always has the same signal state as EN.
Ones Complement Double Integer Box and Parameters
Parameters

FBD Box
INV DI
INV_DI
EN

OUT

IN

ENO

Data Type

EN

MD8

IN

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

DINT

I, Q, M, D, L or
constant

Input value

OUT

DINT

I, Q, M, D, L

Ones complement of the double


integer

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal state of


I0.0 is 1. The value of every bit of memory double
word MD8 is inverted:

INV_DI
I0.0

Memory Area

OUT

MD12

MD8 = F0FF FFF0 MD12 = 0F00 000F

Q4.0
=

ENO

The conversion is not executed when I0.0 is 0 and


Q4.0 is 0 (ENO = EN).

Status Word Bits

Instruction is executed (EN = 1):


writes

Figure 10-9

10-10

BR
1

CC1

CC0

OV

OS

OR
0

STA
1

RLO
1

FC
1

Ones Complement Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Move and Conversion Instructions

10.10 Twos Complement Integer

Description

Table 10-10

The Twos Complement Integer instruction reads the content of the input
parameter IN and changes the sign (for example, from a positive value to a
negative value). The output parameter OUT contains the result. The signal
state of EN is and ENO is always the same except when the signal state of
EN is 1 and an overflow occurs. In this case, the signal state of ENO is 0.
Twos Complement Integer Box and Parameters
Parameters

FBD Box
NEG I
NEG_I
EN

OUT

IN

ENO

Data Type

Memory Area

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

INT

I, Q, M, D, L or
constant

Input value

OUT

INT

I, Q, M, D, L

Twos complement of the integer

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal state


of I0.0 is 1. The value of memory word MW8
is output at OUT to memory word MW10 with
the opposite sign:

NEG_I
I0.0

EN

MW8

IN

Description

OUT

MW10

Example:MW8 = +10 MW10 = 10

Q4.0
=

ENO

If the signal state of EN is 1 and an overflow


occurs, ENO is 0 and the signal state of Q4.0
is 0. If the conversion is not executed,
Q4.0 is 0 (ENO = EN).

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-10

BR
x

CC1
x

CC0
x

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Twos Complement Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

10-11

Move and Conversion Instructions

10.11 Twos Complement Double Integer

Description

Table 10-11

The Twos Complement Double Integer instruction reads the content of the
input parameter IN and changes the sign (for example, from a positive value
to a negative value). The output parameter OUT contains the result. The
signal state of EN is and ENO is always the same except when the signal
state of EN is 1 and an overflow occurs. In this case, the signal state of ENO
is 0.
Twos Complement Double Integer Box and Parameters

FBD Box

Parameter

NEG DI
NEG_DI
EN

OUT

IN

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

DINT

I, Q, M, D, L or
constant

Input value

OUT

DINT

I, Q, M, D, L

Twos complement of the double


integer

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal state of I0.0


is 1. The value of memory double word MD8 is
output at OUT to memory double word MD10 with
the opposite sign:

NEG_DI
I0.0

EN

OUT

MD8

IN

ENO

MD12
Example:MD8 = +60 000 MW10 = 60 000

Q4.0
=

If the signal state of EN is 1 and an overflow occurs,


ENO is 0 and the signal state of Q4.0 is 0. If the
conversion is not executed, Q4.0 is 0 (ENO = EN).
Status Word Bits
Instruction is executed (EN = 1):
BR
CC1
CC0
writes
x
x
x

Figure 10-11

10-12

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Twos Complement Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Move and Conversion Instructions

10.12 Negate Real Number

Description

Table 10-12

The Negate Real Number instruction reads the content of the input parameter
IN and inverts the sign bit (the instruction changes the sign of the number. for
example, from 0 for plus to 1 for minus). The bits of the exponent and
mantissa remain the same. The output parameter OUT provides the result.
ENO always has the same signal state as EN except when the signal state of
EN is 1 and an overflow occurs. In this case, the signal state of ENO is 0.
Negate Real Number Box and Parameters

FBD Box

Parameters

NEG R
NEG_R
EN

OUT

IN

ENO

Data Type

EN

OUT

MD8

IN

ENO

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Input value

OUT

REAL

I, Q, M, D, L

The result is the negated input value.

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal state of


I0.0 is 1. The value of memory double word MD8
is output at OUT to memory double word MD12
with the opposite sign as shown in the following
example:

NEG_R
I0.0

Memory Area

MD12
Q4.0
=

MD8 = + 6.234 x 103 MD12 = 6.234 x 103


If the conversion is not executed, the signal state
of output Q4.0 is 0 (ENO = EN).

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-12

BR
x

CC1

CC0

OV

OS

OR
0

STA
x

RLO
x

FC
1

Negate Real Number

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

10-13

Move and Conversion Instructions

10.13 Round to Double Integer

Description

Table 10-13

The Round to Double Integer instruction reads the content of the input
parameter IN as a real number and converts this number to a double integer.
The result is the nearest integer and is contained in output parameter OUT. If
the fraction is x.5, the number is rounded to the even number (for example:
2.5 > 2, 1.5 > 2). If an overflow occurs, ENO is set to 0. If the input value
is not a real number, the OV bit and the OS bit have the value 1 and ENO has
the value 0.
Round to Double Integer Box and Parameters

FBD Box

Parameters

ROUND
EN

OUT

IN

ENO

Data Type

EN

OUT

MD8

IN

ENO

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Value to be rounded

OUT

DINT

I, Q, M, D, L

IN rounded to the next double


integer

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if I0.0 is 1. The


content of memory double word MD8 is read
as a real number and converted to a double
integer. The result of this round-to-nearest
function is stored in memory double word
MD12. If an overflow occurs, the signal state
of output Q4.0 is 0. If the signal state at input
EN is 0 (meaning that the conversion is not
executed), the signal state of output Q4.0 is
also 0.

ROUND
I0.0

Memory Area

MD12
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-13

10-14

BR
x

CC1

CC0

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Round to Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Move and Conversion Instructions

10.14 Truncate Double Integer Part

Description

Table 10-14

The Truncate Double Integer Part instruction reads the content of the input
parameter IN as a real number and converts this number to a double integer
(for example 1.5 becomes 1). The result is the integer component of the real
number). The output parameter OUT contains the result. If an overflow
occurs, ENO is set to 0. If the input value is not a real number, the OV bit
and the OS bit have the value 1 and ENO has the value 0.
Truncate Double Integer Part Box and Parameters

FBD Box

Parameters

TRUNC
EN

OUT

IN

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Value to be truncated

OUT

DINT

I, Q, M, D, L

Integer component of IN

ENO

BOOL

I, Q, M, D, L

Enable output

The conversion is executed if the signal


state of I0.0 is 1. The content of memory
double word MD8 is read as a real number
and converted to a double integer
according to the round to zero principle.
The integer component is the result and is
stored in memory double word MD12. If an
overflow occurs, the signal state of output
Q4.0 is 0. If the signal state at input EN is 0
(meaning that the conversion is not
executed), the signal state of output Q4.0 is
also 0.

TRUNC
I0.0

EN

OUT

MD8

IN

ENO

MD12
Q4.0
=

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-14

BR
x

CC1

CC0

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Truncate Double Integer Part

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

10-15

Move and Conversion Instructions

10.15 Ceiling

Description

Table 10-15

The Ceiling instruction reads the content of the input parameter IN as a real
number and converts this number to a double integer (for example: +1.2 >
+2; 1.5 > 1). The result is the lowest integer which is greater than or
equal to the specified real number. The output parameter OUT contains the
result. If an overflow occurs, ENO is 0. If the input value is not a real
number, the OV bit and the OS bit have the value 1 and ENO has the value 0.
Ceiling Box and Parameters

FBD Box

Parameters

CEIL
EN

OUT

IN

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Value to be converted

OUT

DINT

I, Q, M, D, L

Result

ENO

BOOL

I, Q, M, D, L

Enable output

CEIL
I0.0

EN

OUT

MD8

IN

ENO

MD12
Q4.0
=

The conversion is executed if I0.0 is 1.The


content of memory double word MD8 is read as
a real number and converted to a double
integer by rounding to the next higher (or equal)
whole number. The result is stored in memory
double word MD12. If an overflow occurs, the
signal state of output Q4.0 is 0. If the signal
state at input EN is 0 (meaning that the
conversion is not executed), the signal state of
output Q4.0 is also 0.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-15

10-16

BR
x

CC1

CC0

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Ceiling

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Move and Conversion Instructions

10.16 Floor

Description

Table 10-16

The Floor instruction reads the content of the input parameter IN as a real
number and converts this number to a double integer. The result is the
highest integer which is lower than or equal to the specified real number. The
output parameter OUT contains the result. If an overflow occurs, ENO is set
to 0. If the input value is not a real number, the OV bit and the OS bit have
the value 1 and ENO has the value 0.
Floor Box and Parameters

FBD Box

Parameters

FLOOR
EN

OUT

IN

ENO

Data Type

MD8

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN

REAL

I, Q, M, D, L or
constant

Value to be converted

OUT

DINT

I, Q, M, D, L

Result

ENO

BOOL

I, Q, M, D, L

Enable output

FLOOR
I0.0

Memory Area

EN

OUT

IN

ENO

MD12
Q4.0
=

The conversion is executed if I0.0 is 1. The


content of memory double word MD8 is read as
a real number and converted to a double
integer by rounding to the next lower (or equal)
whole number. The result is stored in memory
double word MD12. If an overflow occurs, the
signal state of output Q4.0 is 0. If the signal
state at input EN is 0 (meaning that the
conversion is not executed), the signal state of
output Q4.0 is also 0.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 10-16

BR
x

CC1

CC0

OV
x

OS
x

OR
0

STA
x

RLO
x

FC
1

Floor

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

10-17

Move and Conversion Instructions

10-18

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

11

Word Logic Instructions


Chapter
Overview

Section

Description

Page

11.1

Overview

11-2

11.2

(Word) AND Word

11-3

11.3

(Word) AND Double Word

11-4

11.4

(Word) OR Word

11-5

11.5

(Word) OR Double Word

11-6

11.6

(Word) Exclusive OR Word

11-7

11.7

(Word) Exclusive OR Double Word

11-8

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

11-1

Word Logic Instructions

11.1 Overview

What Are
Word Logic
Instructions?

Word logic instructions compare pairs of words (16 bits) and double words
(32 bits) bit by bit, according to Boolean logic. The following instructions
are available for performing word logic operations:

S (Word) AND Word: This instruction combines two words bit by bit,
according to the AND truth table.

S (Word) AND Double Word: This instruction combines two double words
bit by bit, according to the AND truth table.

S (Word) OR Word: This instruction combines two words bit by bit,


according to the OR truth table.

S (Word) OR Double Word: This instruction combines two double words bit
by bit, according to the OR truth table.

S (Word) Exclusive OR Word: This instruction combines two words bit by


bit, according to the Exclusive OR truth table.

S (Word) Exclusive OR Double Word: This instruction combines two


double words bit by bit, according to the Exclusive OR truth table.

11-2

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Word Logic Instructions

11.2 (Word) AND Word

Description

The (Word) AND Word instruction is activated by signal state 1 at the Enable
input (EN) and combines the two digital values at inputs IN1 and IN2 bit by
bit according to the AND truth table. The values are interpreted as pure bit
patterns. The result can be scanned at output OUT. ENO has the same signal
state as EN.
The value of the result at output OUT relative to 0 affects the CC1 bit of the
status word as follows:

S If the result at output OUT is not equal to 0, the CC1 bit of the status
word is set to 1 .

S If the result at output OUT is 0, the CC1 bit of the status word is set to 0.
Table 11-1

(Word) AND Word Box and Parameters


Parameters

FBD Box
WAND W
WAND_W

Data Type

OUT

IN2

ENO

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN1

WORD

I, Q, M, D, L or
constant

First value of the logic operation

IN2

WORD

I, Q, M, D, L or
constant

Second value of the logic operation

OUT

WORD

I, Q, M, D, L

Result of the logic operation

ENO

BOOL

I, Q, M, D, L

Enable output

EN
IN1

Memory Area

I0.0

WAND_W
EN

MW0

IN1

OUT

2# 0000000000001111

IN2

ENO

MW2

Q4.0
=

The instruction is activated when the


signal state of I0.0 is 1. Only bits 0 to 3
are relevant, all other bits of MW0 are
masked.
IN1 =
0101010101010101
IN2 =
0000000000001111
OUT =
0000000000000101
Q4.0 is 1 if the instruction is executed.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 11-1

BR
1

CC1
x

CC0
0

OV
0

OS

OR
x

STA
1

RLO
1

FC
1

(Word) AND Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

11-3

Word Logic Instructions

11.3 (Word) AND Double Word

Description

The (Word) AND Double Word instruction is activated by signal state 1 at the
Enable input (EN) and combines the two digital values at inputs IN1 and IN2
bit by bit according to the AND truth table. The values are interpreted as
pure bit patterns. The result can be scanned at output OUT. ENO has the
same signal state as EN.
The value of the result at output OUT relative to 0 affects the CC1 bit of the
status word as follows:

S If the result at output OUT is not equal to 0, the CC1 bit of the status
word is set to 1 .

S If the result at output OUT is 0, the CC1 bit of the status word is set to 0.
Table 11-2

(Word) AND Double Word Box and Parameters


Parameter

FBD Box

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

WAND_DW
WAND
DW
EN

IN1

DWORD

I, Q, M, D, L or
constant

First value of the logic operation

IN1

OUT

IN2

DWORD

Second value of the logic operation

IN2

ENO

I, Q, M, D, L or
constant

OUT

DWORD

I, Q, M, D, L

Result of the logic operation

ENO

BOOL

I, Q, M, D, L

Enable output

The instruction is activated when I0.0 is 1. Only bits 0


to 11 are relevant, all other bits of MD4 are masked.
IN1 = 0101010101010101 0101010101010101
IN2 = 0000000000000000 0000111111111111
OUT = 0000000000000000 0000010101010101

WAND_DW
I0.0

EN

MD0

IN1

OUT

DW#16#FFF

IN2

ENO

MD4
Q4.0
=

Q4.0 is 1 if the instruction is executed.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 11-2

11-4

BR
1

CC1
x

CC0
0

OV
0

OS

OR
x

STA
1

RLO
1

FC
1

(Word) AND Double Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Word Logic Instructions

11.4 (Word) OR Word

Description

The (Word) OR Word instruction is activated by signal state 1 at the Enable


input (EN) and combines the two digital values at inputs IN1 and IN2 bit by
bit according to the OR truth table. The values are interpreted as pure bit
patterns. The result can be scanned at output OUT. ENO has the same signal
state as EN.
The value of the result at output OUT relative to 0 affects the CC1 bit of the
status word as follows:

S If the result at output OUT is not equal to 0, the CC1 bit of the status
word is set to 1 .

S If the result at output OUT is 0, the CC1 bit of the status word is set to 0.
Table 11-3

(Word) OR Word Box and Parameters


Parameters

FBD Box
WOR W
WOR_W

Data Type

OUT

IN2

ENO

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN1

WORD

I, Q, M, D, L or
constant

First value of the logic operation

IN2

WORD

I, Q, M, D,or
constant L

Second value of the logic operation

OUT

WORD

I, Q, M, D, L

Result of the logic operation

ENO

BOOL

I, Q, M, D, L

Enable output

EN
IN1

Memory Area

The instruction is activated when I0.0 is 1. The


bits in MW0 and in the constant are ORed and
bits 0 to 3 set to 1, all other bits of MW0 are
entered unchanged in MW2

WOR_W
I0.0

EN

MW0

IN1

OUT

2#0000000000001111

IN2

ENO

MW2

Q4.0
=

IN1 =
IN2 =
OUT =

0101010101010101
0000000000001111
0101010101011111

Q4.0 is 1 if the instruction is executed.

Status Word Bits


Instruction is executed (EN = 1):
writes
Figure 11-3

BR
1

CC1
x

CC0
0

OV
0

OS

OR
x

STA
1

RLO
1

FC
1

(Word) OR Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

11-5

Word Logic Instructions

11.5 (Word) OR Double Word

Description

The (Word) OR Double Word instruction is activated by signal state 1 at the


Enable input (EN) and combines the two digital values at inputs IN1 and IN2
bit by bit according to the OR truth table. The values are interpreted as pure
bit patterns. The result can be scanned at output OUT. ENO has the same
signal state as EN.
The value of the result at output OUT relative to 0 affects the CC1 bit of the
status word as follows:

S If the result at output OUT is not equal to 0, the CC1 bit of the status
word is set to 1 .

S If the result at output OUT is 0, the CC1 bit of the status word is set to 0.
Table 11-4

(Word) OR Double Word Box and Parameters


Parameters

FBD Box
WOR DW
WOR_DW

Data Type

OUT

IN2

ENO

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN1

DWORD

I, Q, M, D, L or
constant

First value of the logic operation

IN2

DWORD

I, Q, M, D, L or
constant

Second value of the logic operation

OUT

DWORD

I, Q, M, D, L

Result of the logic operation

ENO

BOOL

I, Q, M, D, L

Enable output

EN
IN1

Memory Area

WOR_DW
I0.0

EN

MD0

IN1

OUT

DW#16#FFF

IN2

ENO

MD4

Q4.0
=

The instruction is activated when I0.0 is 1. The bits in


MD0 and in the constant are ORed and bits 0 to 11
set to 1, all other bits of MD0 are entered unchanged
in MD4
IN1 = 0101010101010101 0101010101010101
IN2 = 0000000000000000 0000111111111111
OUT = 0101010101010101 0101111111111111
Q4.0 is 1 if the instruction is executed.

Status Word Bits


Instruction is executed (EN = 1):
writes
Figure 11-4

11-6

BR
1

CC1
x

CC0
0

OV
0

OS

OR
x

STA
1

RLO
1

FC
1

(Word) OR Double Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Word Logic Instructions

11.6 (Word) Exclusive OR Word

Description

The (Word) Exclusive OR Word instruction is activated by signal state 1 at the


Enable input (EN) and combines the two digital values at inputs IN1 and IN2
bit by bit according to the EXCLUSIVE OR truth table. The values are
interpreted as pure bit patterns. The result can be scanned at output OUT.
ENO has the same signal state as EN.
The value of the result at output OUT relative to 0 affects the CC1 bit in the
status word as follows:

S If the result at output OUT is not equal to 0, the CC1 bit in the status
word is set to 1.

S If the result at output OUT is 0, the CC1 bit in the status word is set to 0.
Table 11-5

(Word) Exclusive OR Word Box and Parameters


Parameters

FBD Box

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

WXOR_W
WXOR
W
EN

IN1

WORD

I, Q, M, D, L or
constant

First value of the logic operation

IN1

OUT

IN2

WORD

ENO

I, Q, M, D, L or
constant

Second value of the logic operation

IN2

OUT

WORD

I, Q, M, D, L

Result of the logic operation

ENO

BOOL

I, Q, M, D, L

Enable output

I0.0

WXOR_W
EN

MW0

IN1

OUT

2#0000000000001111

IN2

ENO

The instruction is activated when input I0.0


is 1.

MW2

Q4.0
=

IN1 =
IN2 =
OUT =

0101010101010101
0000000000001111
0101010101011010

Q4.0 is 1 if the instruction is executed.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 11-5

BR
1

CC1
x

CC0
0

OV
0

OS

OR
x

STA
1

RLO
1

FC
1

(Word) Exclusive OR Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

11-7

Word Logic Instructions

11.7 (Word) Exclusive OR Double Word

Description

The (Word) Exclusive OR Double Word instruction is activated by signal state


1 at the Enable input (EN) and combines the two digital values at inputs IN1
and IN2 bit by bit according to the EXCLUSIVE OR truth table. The values
are interpreted as pure bit patterns. The result can be scanned at output OUT.
ENO has the same signal state as EN.
The value of the result at output OUT relative to 0 affects the CC1 bit in the
status word as follows:

S If the result at output OUT is not equal to 0, the CC1 bit in the status
word is set to 1.

S If the result at output OUT is 0, the CC1 bit in the status word is set to 0.
Table 11-6

(Word) Exclusive OR Double Word Box and Parameters


Parameters

FBD Box
WXOR DW
WXOR_DW

Data Type

OUT

IN2

ENO

Description

EN

BOOL

I, Q, M, D, L, T, C

Enable input

IN1

DWORD

I, Q, M, D, L or
constant

First value of the logic operation

IN2

DWORD

I, Q, M, D, L or
constant

Second value of the logic operation

OUT

DWORD

I, Q, M, D, L

Result of the logic operation

ENO

BOOL

I, Q, M, D, L

Enable output

EN
IN1

Memory Area

The instruction is activated when input I0.0 is 1.


WXOR_DW
EN

I0.0
MD0

IN1

OUT

DW#16#FFF

IN2

ENO

MD4

Q4.0
=

IN1 = 0101010101010101 0101010101010101


IN2 = 0000000000000000 0000111111111111
OUT = 0101010101010101 0101101010101010
Q4.0 is 1 if the instruction is executed.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 11-6

11-8

BR
1

CC1
x

CC0
0

OV
0

OS

OR
x

STA
1

RLO
1

FC
1

(Word) Exclusive OR Double Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

12

Shift and Rotate Instructions


Chapter
Overview

Section

Description

12.1

Shift Instructions

12.2

Rotate Instructions

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Page
12-2
12-10

12-1

Shift and Rotate Instructions

12.1 Shift Instructions

Description

You can use the Shift instructions to move the contents of input IN bit by bit
to the left or the right (see Section 2.3). Shifting n bits to the left multiplies
the contents of input IN by 2 to the power n (2n); shifting n bits to the right
divides the contents of input IN by 2 to the power n (2n). For example, if you
shift the binary equivalent of the decimal value 3 to the left by 3 bits, you
obtain the binary equivalent of the decimal value 24. If you shift the binary
equivalent of the decimal value 16 to the right by 2 bits, you obtain the
binary equivalent of the decimal value 4.
The number that you supply for input parameter N indicates the number of
bits by which the value is shifted. The bit places that are vacated by the Shift
instruction are either padded with zeros or with the signal state of the sign bit
(0 stands for positive and 1 stands for negative). The signal state of the bit
that is shifted last is loaded into the CC1 bit of the status word (see
Section 2.3). The CC0 and OV bits of the status word are reset to 0. You can
use jump instructions to evaluate the CC1 bit.
The following Shift instructions are available:

S Shift Left Word, Shift Left Double Word


S Shift Right Word, Shift Right Double Word
S Shift Right Integer, Shift Right Double Integer
Shift Left Word

A signal state of 1 at the Enable input (EN) activates the Shift Left Word
instruction. This instruction shifts bits 0 to 15 of input IN bit by bit to the
left.
Input N specifies the number of bits by which to shift the value. If N is
higher than 16, the command writes 0 to output OUT and sets the CC0 and
OV bits of the status word to 0. The bit positions at the right are padded with
zeros. The result of the shift operation can be scanned at output OUT.
The operation triggered by this instruction always resets the CC0 and OV bits
of the status word to 0 if the value of N is not equal to 0. ENO has the same
signal state as EN.

12-2

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Shift and Rotate Instructions

Parameters:

15...

IN

...8

0 0 0 0

1 1 1 1

7...

...0

0 1 0 1

0 1 0 1

0 1 0 0

0 0 0 0

6 places
0 0 0 0 1

OUT

1 1 0 1

0 1 0 1

These six bits


are lost.

The vacated places


are padded with
zeros.

Figure 12-1

Shifting the Bits of Input IN Six Bits to the Left

Table 12-1

Shift Left Word Box and Parameters

FBD Box

Parameters

SHL_W
EN
IN

OUT

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, L, D, T, C

Enable input

IN

WORD

I, Q, M, L, D

Value to be shifted

WORD

I, Q, M, L, D

Number of bit positions by which


the value will be shifted

OUT

WORD

I, Q, M, L, D

Result of the shift instruction

ENO

BOOL

I, Q, M, L, D

Enable output

I0.0

SHL_W
EN

MW0

IN

OUT

MW2

ENO

The instruction is activated if the signal


state of I0.0 is 1.

MW4

Memory word MW0 is shifted to the left by


the number of bits specified in memory
word MW2.

Q4.0
S

The result is entered in memory word


MW4.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 12-2

BR
x

CC1
x

CC0
x

OV
x

OS

OR
x

STA
x

RLO
x

FC
1

Shift Left Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

12-3

Shift and Rotate Instructions

Shift Left Double


Word

A signal state of 1 at the Enable input (EN) activates the Shift Left Double
Word instruction. This instruction shifts bits 0 to 31 of input IN bit by bit to
the left. Input N specifies the number of bits by which the value will be
shifted. If N is greater than 32, the command writes 0 to output OUT and sets
the CC0 and OV bits of the status word to 0. The vacated bit positions at the
right are padded with zeros. The result of the shift operation can be scanned
at output OUT.
The operation triggered by this instruction always resets the CC0 and OV bits
of the status word to 0 if the value of N is not equal to 0. ENO has the same
signal state as EN.

Table 12-2

Shift Left Double Word Box and Parameters


Parameters

FBD Box
SHL_DW
SHL
DW
EN
IN

OUT

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, L, D, T, C

Enable input

IN

DWORD

I, Q, M, L, D

Value to be shifted

WORD

I, Q, M, L, D

Number of bit positions by which


the value will be shifted

OUT

DWORD

I, Q, M, L, D

Result of the shift instruction

ENO

BOOL

I, Q, M, L, D

Enable output

The instruction is activated if the signal


state of I0.0 is 1.
SHL_DW
I0.0

EN

MD0

IN

OUT

MW4

ENO

MD10

Memory double word MD0 is shifted to


the left by the number of bits specified
in memory word MW4.
Q4.0
S

The result is entered in memory


double word MD10.

Status Word Bits


Instruction is executed (EN = 1):
writes
Figure 12-3

12-4

BR
x

CC1
x

CC0
x

OV
x

OS

OR
x

STA
x

RLO
x

FC
1

Shift Left Double Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Shift and Rotate Instructions

Shift Right Word

A signal state of 1 at the Enable input (EN) activates the Shift Right Word
instruction. This instruction shifts bits 0 to 15 of input IN bit by bit to the
right. Bits 16 to 31 are not affected. Input N specifies the number of bits by
which the value will be shifted. If N is greater than 16, the command writes 0
to output OUT and resets the CC0 and OV bits of the status word to 0. The
vacated bit positions at the left are padded with zeros. The result of the shift
operation can be scanned at output OUT.
The operation triggered by this instruction always resets the CC0 and OV bits
of the status word to 0 if N is not equal to zero. ENO has the same signal
state as EN.

Table 12-3

Shift Right Word Box and Parameters


Parameters

FBD Box
SHR_W
SHR
W
EN
IN

OUT

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, L, D, T, C

Enable input

IN

WORD

I, Q, M, L, D

Value to be shifted

WORD

I, Q, M, L, D

Number of bit positions by which


the value will be shifted

OUT

WORD

I, Q, M, L, D

Result of the shift instruction

ENO

BOOL

I, Q, M, L, D

Enable output

The instruction is activated if the signal


state of I0.0 is 1.

SHR_W
I0.0

EN

MW0

IN

OUT

MW2

ENO

MW4

Memory word MW0 is shifted to the right


by the number of bits specified in memory
word MW2.

Q4.0
S

The result is entered in memory word


MW4.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 12-4

BR
x

CC1
x

CC0
x

OV
x

OS

OR
x

STA
x

RLO
x

FC
1

Shift Right Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

12-5

Shift and Rotate Instructions

Shift Right Double


Word

A signal state of 1 at the Enable input (EN) activates the Shift Right Double
Word instruction. This instruction shifts bits 0 to 31 of input IN bit by bit to
the right. Input N specifies the number of bits by which the value will be
shifted. If N is higher than 32, the command writes 0 to output OUT and
resets the CC0 and OV bits of the status word to 0. The vacated bit positions
at the left are padded with zeros. The result of the shift operation can be
scanned at output OUT.
The operation triggered by this instruction always resets the CC1 and OV bits
of the status word to 0 if N is not equal to zero. ENO has the same signal
state as EN.

Parameters:

31...

...16 15...

...0

1111 1111 0101 0101 1010 1010 1111 1111

IN
N

3 places

OUT

0001 1111 1110 1010 1011 0101 0101 1111 111


The vacated bit
positions are padded
with zeros.

These three
bits are lost.

Figure 12-5

Shifting Bits of Input IN Three Bits to the Right

Table 12-4

Shift Right Double Word Box and Parameters

FBD Box
SHR_DW
SHR
DW
EN

12-6

IN

OUT

ENO

Parameters

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, L, D, T, C

Enable input

IN

DWORD

I, Q, M, L, D

Value to be shifted

WORD

I, Q, M, L, D

Number of bit positions by which


the value will be shifted

OUT

DWORD

I, Q, M, L, D

Result of the shift instruction

ENO

BOOL

I, Q, M, L, D

Enable output

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Shift and Rotate Instructions

The instruction is activated if the signal


state of I0.0 is 1.
SHR_DW
I0.0

EN

MD0

IN

OUT

MW4

ENO

Memory double word MD0 is shifted to


the right by the number of bits specified
in memory word MW4.

MD10

Q4.0
S

The result is entered in MD10.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 12-6

BR
x

CC1
x

CC0
x

OV
x

OS

OR
x

STA
x

RLO
x

FC
1

Shift Right Double Word

Shift Right Integer

A signal state of 1 at the Enable input (EN) activates the Shift Right Integer
instruction. This instruction shifts bits 0 to 15 of input IN bit by bit to the
right. Input N specifies the number of bits by which the value will be shifted.
If N is higher than 16, the command behaves as if N were 16. The bit
positions at the left are padded according to the signal state of bit 15 (the sign
of an integer number). They are filled with zeros if the number is positive,
and with ones if it is negative. The result of the shift operation can be
scanned at output OUT.
The operation triggered by this instruction always resets the CC0 and OV bits
of the status word to 0 if N is not equal to zero. ENO has the same signal
state as EN.

Parameters:

15...

IN

Sign bit

OUT

1 0

...8

7...

...0
0

4 places
1

The vacated bit


positions are padded
with the signal state of
the sign bit.

Figure 12-7

These four bits


are lost.

Shifting Bits of Input IN Four Bits to the Right with Sign

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

12-7

Shift and Rotate Instructions

Table 12-5

Shift Right Integer Box and Parameters


Parameters

FBD Box
SHR_II
SHR
EN
IN

OUT

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, L, D, T, C

Enable input

IN

INT

I, Q, M, L, D

Value to be shifted

WORD

I, Q, M, L, D

Number of bit positions by which


the value will be shifted

OUT

INT

I, Q, M, L, D

Result of the shift instruction

ENO

BOOL

I, Q, M, L, D

Enable output

The instruction is activated if the signal


state of I0.0 is 1.
SHR_I
I0.0

EN

MW0

IN

OUT

MW2

ENO

MW4

Memory word MW0 is shifted to the right


by the number of bits specified in memory
word MW2.
Q4.0
S

The result is entered in memory word


MW4.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 12-8

12-8

BR
x

CC1
x

CC0
x

OV
x

OS

OR
x

STA
x

RLO
x

FC
1

Shift Right Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Shift and Rotate Instructions

Shift Right Double


Integer

A signal state of 1 at the Enable input (EN) activates the Shift Right Double
Integer instruction. This instruction shifts the entire contents of input IN bit
by bit to the right. Input N specifies the number of bits by which the value
will be shifted. If N is higher than 32, the command behaves as if N were 32.
The bit positions at the left are padded according to the signal state of bit 31
(the sign of a double integer number). They are filled with zeros if the
number is positive, and with ones if it is negative. The result of the shift
operation can be scanned at output OUT.
The operation triggered by this instruction always resets the CC0 and OV bits
of the status word to 0 if N is not equal to zero. ENO has the same signal
state as EN.

Table 12-6

Shift Right Double Integer Box and Parameters

FBD Box

Parameters

SHR_DI
EN
IN

OUT

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, L, D, T, C

Enable input

IN

DINT

I, Q, M, L, D

Value to be shifted

WORD

I, Q, M, L, D

Number of bit positions by which


the value will be shifted

OUT

DINT

I, Q, M, L, D

Result of the shift instruction

ENO

BOOL

I, Q, M, L, D

Enable output

The instruction is activated if the signal


state of I0.0 is 1.
SHR_DI
I0.0

EN

MD0

IN

OUT

MW4

ENO

Memory double word MD0 is shifted to


the right by the number of bits specified
in memory word MW4.
MD10

Q4.0
S

The result is entered in memory double


word MD10.

Status Word Bits


Instruction is executed (EN = 1):
writes
Figure 12-9

BR
x

CC1
x

CC0
x

OV
x

OS

OR
x

STA
x

RLO
x

FC
1

Shift Right Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

12-9

Shift and Rotate Instructions

12.2 Rotate Instructions

Description

You can use the Rotate instructions to rotate the entire contents of input IN
bit by bit to the left or to the right. The vacated bit positions are filled with
the signal states of the bits that are shifted out of input IN.
The number that you specify for input parameter N is the number of bits by
which the value will be rotated.
Depending on the instruction, rotation uses the CC1 bit of the status word
(see Section 2.3). The CC0 bit of the status word is reset to 0.
The following Rotate instructions are available:

S Rotate Left Double Word


S Rotate Right Double Word
Rotate Left Double
Word

A signal state of 1 at the Enable input (EN) activates the Rotate Left Double
Word instruction. This instruction rotates the entire contents of input IN bit
by bit to the left. Input N specifies the number of bits by which to rotate. If N
is higher than 32, the double word is rotated ((N1) modulo 32) +1) places.
The bit positions at the right are filled with the signal states of the bits
rotated. The result of the rotate operation can be scanned at output OUT.
The operation triggered by this instruction always resets the CC0 and OV bits
of the status word to 0 if N is not equal to zero. ENO has the same signal
state as EN.

31...

Parameters:

...16 15...

1111 0000 1010 1010 0000 1111 0000 1111

IN

3 places

OUT

111

1000 0101 0101 0000 0111 1000 0111 1111

The signal states of the three


bits that are shifted out are
inserted in the vacated
positions.

Figure 12-10

12-10

...0

These three bits are lost.

Rotating Bits of Input IN Three Bits to the Left

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Shift and Rotate Instructions

Table 12-7

Rotate Left Double Word Box and Parameters


Parameters

FBD Box
ROL_DW
ROL
DW
EN
IN

OUT

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, L, D, T, C

Enable input

IN

DWORD

I, Q, M, L, D

Value to be rotated

WORD

I, Q, M, L, D

Number of bit positions by which


the value will be rotated

OUT

DWORD

I, Q, M, L, D

Result of the rotate instruction

ENO

BOOL

I, Q, M, L, D

Enable output

The instruction is activated if the signal


state of I0.0 is 1.
ROL_DW
I0.0

EN

MD0

IN

OUT

MW4

ENO

MD10

Memory double word MD0 is rotated to the


left by the number of bits specified in
memory word MW4.
Q4.0
S

The result is entered in memory double


word MD10.

Status Word Bits


Instruction is executed (EN = 1):
writes
Figure 12-11

BR
x

CC1
x

CC0
x

OV
x

OS

OR
x

STA
x

RLO
x

FC
1

Rotate Left Double Word

Rotate Right
Double Word

A signal state of 1 at the Enable input (EN) activates the Rotate Right Double
Word instruction. This instruction rotates the entire contents of input IN bit
by bit to the right. Input N specifies the number of bits by which the value
will be rotated. The value of N can be between 0 and 31. If N is higher than
32, the double word is rotated ((N1) modulo 32) +1) places. The bit
positions at the left are filled with the signal states of the bits rotated. The
result of the rotate operation can be scanned at output OUT.
The operation triggered by this instruction always resets the CC0 and OV bits
of the status word to 0 if N is not equal to zero. ENO has the same signal
state as EN.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

12-11

Shift and Rotate Instructions

Parameters:

31...

...16 15...

...0

1010 1010 0000 1111 0000 1111 0101 0101

IN

3 places

1011 0101 0100 0001 1110 0001 1110 1010 101

OUT

The signal states of


the three bits that are
shifted out are inserted
in the vacated places.

Figure 12-12

Rotating Bits of Input IN Three Bits to the Right

Table 12-8

Rotate Right Double Word Box and Parameters


Parameters

FBD Box
ROR_DW
ROR
DW
EN
IN

OUT

ENO

Data Type

Memory Area

Description

EN

BOOL

I, Q, M, L, D, T, C

Enable input

IN

DWORD

I, Q, M, L, D

Value to be rotated

WORD

I, Q, M, L, D

Number of bit positions by which


the value will be rotated

OUT

DWORD

I, Q, M, L, D

Result of the rotate instruction

ENO

BOOL

I, Q, M, L, D

Enable output

The instruction is activated if the signal


state of I0.0 is 1.
ROR_DW
I0.0

EN

MD0

IN

OUT

MW4

ENO

MD10

Memory double word MD0 is rotated to


the right by the number of bits specified in
memory word MW4.
Q4.0
S

The result is entered in memory double


word MD10.

Status Word Bits


Instruction is executed (EN = 1):
writes

Figure 12-13

12-12

BR
x

CC1
x

CC0
x

OV
x

OS

OR
x

STA
x

RLO
x

FC
1

Rotate Right Double Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

13

Data Block Instructions


Chapter
Overview

Section
13.1

Description
Open Data Block

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Page
13-2

13-1

Data Block Instructions

13.1 Open Data Block

Description

Table 13-1

You can use the Open Data Block instruction to open an existing data block
as a shared data block (DB) or instance data block (DI). The number of the
data block is transferred to the DB or DI register. The subsequent DB and DI
commands access the corresponding blocks depending on the register
contents.

Open Data Block Box and Parameters with SIMATIC Mnemonics

FBD Box

Parameters

Data Type

<DB number> or
<DI number>

Number of the
DB or DI

BLOCK_DB

Memory Area
DB, DI

AUF

Table 13-2

Description
Number of the DB or DI;
Range depends on the
CPU.

Open Data Block Box and Parameters with International Mnemonics

FBD Box

Parameter

<DB number> or
<DI number>

Number of the
DB or DI

Data Type

Memory Area

BLOCK_DB

DB, DI

Description
Number of the DB or DI;
Range depends on the
CPU.

OPN

Network 1
DB10 is the currently opened data block. The
scan at DBX0.0 therefore refers to bit 0 of
data byte 0 of data block DB10. The signal
state of this bit is assigned to output Q 4.0.

DB10
OPN
Network 2
Q 4.0
DBX 0.0

=
Status Word Bits

writes

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

The instruction does not change the bits in the status word.
Figure 13-1

13-2

Open Data Block

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

14

Jump Instructions
Chapter
Overview

Section

Description

Page

14.1

Overview

14-2

14.2

Unconditional Jump in a Block

14-3

14.3

Conditional Jump in a Block

14-4

14.4

Jump-If-Not

14-5

14.5

Jump Label

14-6

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

14-1

Jump Instructions

14.1 Overview

Jump Label as
Address

The address of a Jump instruction is a label. A label consists of a maximum


of four characters. The first character must be a letter; the other characters
can be letters or numbers (for example, SEG3). The jump label indicates the
destination to which you want the program to jump.
You enter the label above the jump box (see Figure 14-1).

Jump Label as
Destination

The destination label must be at the beginning of a network. You enter the
destination label at the beginning of the network by selecting LABEL from
the FBD list box. An empty box appears. In the box, you type the name of
the label (see Figure 14-1).

Network1
SEG3
JMP

Network 2
Q4.0
I0.1

.
.
.
Network X
SEG3

I0.4

Figure 14-1

14-2

Q4.1
R

Jump Label as Address and Destination

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Jump Instructions

14.2 Unconditional Jump in a Block

Description

The Unconditional Jump in a Block instruction corresponds to a go to label


instruction. None of the instructions between the jump operation and the
label is executed.
You can use this instruction in all logic blocks, for example in organization
blocks (OBs), function blocks (FBs) and functions (FCs).
There must not be any logic operation before the Unconditional Jump in a
Block box.

Table 14-1

Unconditional Jump in a Block Box and Parameters

FBD Box

Parameters

Data Type

Name of a jump
label

<address>

Memory Area

Description
The address specifies the label to
which the program will jump
unconditionally.

JMP

Network 1
CAS1
JMP

??.?

The jump is always executed. None of the instructions between


the jump instruction and the label is executed.

.
.
.
Network X
CAS1
Q4.1
R

I0.4

Status Word Bits

writes

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

The instruction does not change the bits in the status word.
Figure 14-2

Unconditional Jump: Jump to Label

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

14-3

Jump Instructions

14.3 Conditional Jump in a Block

Description

The Conditional Jump in a Block instruction corresponds to a go to label


instruction if the RLO is 1. The FBD element Unconditional Jump is also
used for this operation, however it is made conditional by the preceding logic
operation. The conditional jump is only executed when the result of this logic
operation is 1. None of the instructions between the jump operation and the
label is executed.
You can use this instruction in all logic blocks, for example in organization
blocks (OBs), function blocks (FBs) and functions (FCs).

Table 14-2

Conditional Jump in a Block Box and Parameters


Parameters

Data Type

Name of a
jump label

FBD Box
<address>
JMP

Memory Area

Description
The address specifies the label to
which the program will jump if the
RLO is 1.

Network 1
CAS1
JMP

I0.0

If the signal state of input I0.0 is 1, the jump to label CAS1


is executed. The instruction to reset output Q4.0 is not
executed, even if the signal state of input I0.3 is 1.

Network 2
Q4.0
R

I0.3

Network 3
CAS1
Q4.1
R

I0.4

Status Word Bits

writes

Figure 14-3

14-4

BR

CC1

CC0

OV

OS

OR
0

STA
1

RLO
1

FC
0

Conditional Jump: Jump in the Block If 1

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Jump Instructions

14.4 Jump-If-Not

Description

The Jump-If-Not instruction corresponds to a go to label instruction that is


executed if the RLO is 0.
You can use this instruction in all logic blocks, for example in organization
blocks (OBs), function blocks (FBs) and functions (FCs).

Table 14-3

Jump-If-Not Box and Parameters

FBD Box

Parameters

Data Type

Name of a jump
label

<address>
JMPN

Memory Area

Description
The address specifies the label to
which the program will jump if the
RLO is 0.

Network 1
CAS1
JMPN

I0.0

If the signal state of input I0.0 is 0, the jump to label CAS1


is executed. The instruction to reset output Q4.0 is not
executed, even if the signal state of input I0.3 is 1.

Network 2
None of the instructions between the jump operation and
the label is executed.

Q4.0
R

I0.3

Network 3
CAS1
Q4.1
R

I0.4

Status Word Bits

writes

Figure 14-4

BR

CC1

CC0

OV

OS

OR
0

STA
1

RLO
1

FC
0

Jump-If-Not

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

14-5

Jump Instructions

14.5 Jump Label

Description

The jump label is the identifier for the destination of a jump instruction. A
jump label must exist for every jump or jump-if-not instruction (JMP or
JMPN).

Format

Description
4 characters:

LABEL

first character must be a letter


remaining characters can be letters or numbers

Network 1
CAS1
JMP

I0.0

If I0.0 = 1, the jump to label CAS1 is executed.


Due to the jump, the operation Reset output at Q 4.0 is not
executed even if I0.3 = 1.

Network 2
Q4.0
R

I0.3

Network 3
CAS1

I0.4

Figure 14-5

14-6

Q4.1
R

Jump Label

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

15

Status Bit Instructions


Chapter
Overview

Section

Description

Page

15.1

Overview

15-2

15.2

Exception Bit Binary Result

15-3

15.3

Result Bits

15-4

15.4

Exception Bit Unordered

15-6

15.5

Exception Bit Overflow

15-7

15.6

Exception Bit Overflow Stored

15-8

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

15-1

Status Bit Instructions

15.1 Overview

Description

The status bit instructions are bit logic instructions (see Chapter 4) that work
with the bits of the status word (see Section 2.3). Each of these instructions
reacts to one of the following conditions that is indicated by one or more bits
of the status word:

S The binary result bit is set (has a signal state of 1).


S The result of a math function is relative to 0 in one of the following ways:
Greater than 0 (>0)
Less than 0 (<0)
Greater than or equal to 0 (>=0)
Less than or equal to 0 (<=0)
Equal to 0 (==0)
Not equal to 0 (<>0)

S The result of a math function is unordered (invalid).


S A math function produced an overflow.
In an AND operation, the status bit instructions combine the result of their
signal state checks with the previous result of logic operation according to
the And truth table (see Section 2.2 and Table 2-7). In an OR operation, the
OR truth table is used (see Section 2.2 and Table 2-8).
In this section, the Exception Bit Binary Result element, which checks the
signal state of the BR (Binary Result) bit of the status word, is shown in its
international and SIMATIC form.

Status Word

The status word is a register in the memory of your CPU that contains bits
that you can reference in the address of bit and word logic instructions.
Figure 15-1 shows the structure of the status word. For more information on
the individual bits of the status word, see Section 2.3.
215...

Figure 15-1

Parameters

15-2

...29

28

27

26

25

BR

CC1

CC0

OV

24
OS

23

22

21

20

OR

STA

RLO FC

Structure of the Status Word

The FBD elements described in the following sections do not have any
selectable parameters.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Status Bit Instructions

15.2 Exception Bit Binary Result

Description

You can use the Exception Bit Binary Result instruction to check the signal
state of the BR bit (Binary Result) of the status word (see Section 2.3). In an
AND operation, the result of the check is combined with the previous RLO
according to the AND truth table (see Section 2.2 and Table 2-7). In an OR
operation, the OR truth table is used (see Section 2.2 and Table 2-8).

FBD Box

Figure 15-2 shows the Exception Bit Binary Result box with SIMATIC and
international short names.

SIMATIC element

International element

BIE

Figure 15-2

I0.0

&
BR

Figure 15-3

Exception Bit Binary Result Box

>=1

I0.2

BR

Q4.0
S

Output Q4.0 is set if the signal state at input


I0.0 is 1 OR the signal state at input I0.2 is 0,
and, in addition to this RLO, the signal state
of the BR bit is 1.

Exception Bit Binary Result

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

15-3

Status Bit Instructions

15.3 Result Bits

Description

You can use the Result Bit instructions to determine the relationship of the
result of a math function to zero, in other words, whether the result is >0, <0,
>=0, <=0, ==0, or <>0 (see Table 15-1). The condition code bits of the status
word (CC 1 and CC 0, see Section 2.3) are evaluated. If the comparison
condition indicated in the address is fulfilled, the result of this signal state
check is 1.
In an AND operation, this instruction combines the result of its check with
the previous result of logic operation (RLO) according to the AND truth table
(see Section 2.2 and Table 2-7). In an OR operation, this instruction
combines the result of its check with the previous RLO according to the OR
truth table (see Section 2.2 and Table 2-8).

Table 15-1

Result Bits Boxes

FBD Element

Description

>0

The Result Bit instruction for greater than 0 determines whether or not the result of a
math instruction is greater than 0. It checks the combination in the condition code bits
CC1 and CC0 in the status word to determine the relationship of a result to 0.

<0

The Result Bit instruction for less than 0 determines whether or not the result of a math
instruction is less than 0. It checks the combination in the condition code bits CC1 and
CC0 in the status word to determine the relationship of a result to 0.

>=0

The Result Bit instruction for greater than or equal to 0 determines whether or not the
result of a math instruction greater than or equal to 0. It checks the combination in the
condition code bits CC1 and CC0 in the status word to determine the relationship of a
result to 0.

<=0

The Result Bit instruction for less than or equal to 0 determines whether or not the result
of a math instruction is less than or equal to 0. It checks the combination in the condition
code bits CC1 and CC0 in the status word to determine the relationship of a result to 0.

== 0

The Result Bit instruction for equal to 0 determines whether or not the result of a math
instruction is equal to 0. It checks the combination in the condition code bits CC1 and
CC0 in the status word to determine the relationship of a result to 0.

<>0

The Result Bit instruction for not equal to 0 determines whether or not the result of a
math instruction is not equal to 0. It checks the combination in the condition code bits
CC1 and CC0 in the status word to determine the relationship of a result to 0.

15-4

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Status Bit Instructions

1)

If the signal state at input I0.0 is 1, the SUB_I box


is activated. If the value of input word IW0 is
greater than the value of input word IW2, the
result of the math function IW0 IW2 is greater
than 0.

SUB_I
I0.0

EN

IW0

IN1

OUT

IW2

IN2

ENO

MW10
&
Q4.0
S

>0

1) Output Q4.0 is set if the function is executed


correctly and the result is less than or equal to 0.
If the signal state of input I0.0 is 0 (not activated),
the signal state of both EN and ENO is 0.

2)
SUB_I
I0.0

EN

IW0

IN1

OUT

IW2

IN2

ENO

If the signal state of EN is 1 (activated) and an


error occurs while the instruction is being
executed, the signal state of ENO is 0.

2) Output Q4.0 is set if the function is executed


correctly and the result is less than or equal to 0.
If the signal state of input I0.0 is 0 (not activated),
the signal state of both EN and ENO is 0.

MW10
&
Q4.0
S

Status Word Bits

writes
Figure 15-4

BR

CC1

CC0

OV

OS

OR
x

STA
x

RLO
x

FC
1

Result Bit for Greater than 0 and Negated Result Bit for Greater than 0

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

15-5

Status Bit Instructions

15.4 Exception Bit Unordered

Description

You can use the Exception Bit Unordered instruction to check whether or not
the result of a floating-point math function is unordered (in other words,
whether one of the values in the math function is not a valid floating-point
number). The condition code bits of the status word (CC 1 and CC 0, see
Section 2.3) are evaluated. If the result of the math function is unordered
(UO) the signal state check produces a result of 1. If the combination in CC 1
and CC 0 does not indicate unordered, the result of the signal state check is
0.
In an AND operation, this instruction combines the result of its check with
the previous result of logic operation (RLO, see Section 2.3) according to the
AND truth table (see Section 2.2 and Table 2-7). In an OR operation, the OR
truth table is used (see Section 2.2 and Table 2-8).

FBD Box
UO

Figure 15-5

Exception Bit Unordered Box

Network 1:

I0.0

DIV_R
EN

ID0

IN1

OUT

ID4

IN2

ENO

MD10

Network 2:
UO

Figure 15-6

15-6

Q4.0
S

Q4.1
S

If the signal state at input I0.0 is 1, the DIV_R


box is activated. If the value of either input
double word ID0 or ID4 is not a valid
floating-point number, the floating-point math
function is unordered.
If the signal state of EN is 1 (activated) and
an error occurs while the instruction is being
executed, the signal state of ENO is 0.
Output Q4.0 is set if the function DIV_R is
executed, but one of the values in the math
function is not a valid floating-point number. If
the signal state of input I0.0 is 0 (not
activated), the signal state of both EN and
ENO is 0.

Exception Bit Unordered

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Status Bit Instructions

15.5 Exception Bit Overflow

Description

You can use the Exception Bit Overflow instruction to detect an overflow
(OV) in the last math function. If, after the system executes a math function,
the result is outside the permitted negative range or outside the permitted
positive range, the OV bit in the status word (see Section 2.3) is set. The
instruction checks the signal state of this bit. This bit is reset if the math
functions were free of errors
In an AND operation, this instruction combines the result of its check with
the previous result of logic operation according to the AND truth table (see
Section 2.2 and Table 2-7). In an OR operation, the OR truth table is used
(see Section 2.2 and Table 2-8).

FBD Box
OV

Figure 15-7

If the signal state at input I0.0 is 1, the SUB_I box is


activated. If the result of the math function input word IW0
minus input word IW2 is outside the permitted range for an
integer, the OV bit in the status word is set.

Network 1:
SUB_I
I0.0

EN

IW0

IN1

OUT

IW2

IN2

ENO

Exception Bit Overflow Box

MW10

The result of a signal state check at OV is 1. Output Q4.0


is set if the check at OV is 1 and the RLO of network 2 is 1
(if the RLO prior to output Q4.0 is 1).
If the signal state of input I0.0 is 0 (not activated), the
signal state of both EN and ENO is 0. If the signal state of
EN is 1 (activated) and the result of the math function is
out of range, the signal state of ENO is 0.

Network 2:
&

I0.1
I0.2

>=1
I0.3

M 3.3

Network 3:
OV

Figure 15-8

Q4.0
S

Exception Bit Overflow

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

15-7

Status Bit Instructions

15.6 Exception Bit Overflow Stored

Description

You can use the Exception Bit Overflow Stored instruction to recognize a
previous overflow (overflow stored, OS) in a math function. If, after the
system executes a math function, the result is outside the permitted negative
range or outside the permitted positive range, the OS bit in the status word
(see Section 2.3) is set. The instruction checks the signal state of this bit.
Unlike the OV (overflow) bit, the OS bit remains set even if later math
functions were executed free of errors (see Section 15.5).
In an AND operation, this instruction combines the result of its check with
the previous result of logic operation according to the AND truth table (see
Section 2.2 and Table 2-7). In an OR operation, the OR truth table is used
(see Section 2.2 and Table 2-8).

FBD Box
OS

Figure 15-9

15-8

Exception Bit Overflow Stored Box

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Status Bit Instructions

Network 1:
MUL_I
I0.0

EN

IW0

IN1

OUT

IW2

IN2

ENO

MD8

If the signal state at input I0.0 is 1, the MUL_I box is


activated. If the signal state at input I0.1 is 1, the ADD_I box
is activated. If the result of one of the math functions is
outside the permissible range for an integer, the OS bit in the
status word is set.
The result of a signal state check at OS is 1 and output Q4.0
is set.
Network 1: if the signal state of input I0.0 is 0 (not activated),
the signal state of both EN and ENO is 0. If the signal state of
EN is 1 (activated) and the result of the math function is out
of range, the signal state of ENO is 0.

Network 2:
ADD_I
I0.1

EN

IW0

IN1

OUT

IW2

IN2

ENO

MW12

Network 2: if the signal state of input I0.1 is 0 (not activated),


the signal state of both EN and ENO is 0. If the signal state of
EN is 1 (activated) and the result of the math function is out
of range, the signal state of ENO is 0.

Network 3:
OS

Figure 15-10

Q4.0
S

Exception Bit Overflow Stored

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

15-9

Status Bit Instructions

15-10

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Program Control Instructions


Chapter
Overview

Section

Description

16
Page

16.1

Calling an FC/SFC without Parameters

16-2

16.2

Calling an FB, FC, SFB, SFC, and Multiple Instances

16-4

16.3

Return

16-7

16.4

Master Control Relay Instructions

16-8

16.5

Master Control Relay Activate/Deactivate

16-10

16.6

Master Control Relay On/Off

16-13

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

16-1

Program Control Instructions

16.1 Calling an FC/SFC without Parameters

Description

With the Call FC/SFC without Parameters instruction, you can call a
function (FC) or a system function (SFC) that has no parameters. The call is
conditional or unconditional depending on the preceding logic operation (see
the example).
In the code section of a function (FC), you cannot specify any parameter of
the type BLOCK_FC as the address for a conditional call. You can, however,
specify a parameter of the type BLOCK_FC as the address in a function
block (FB).
A conditional call is executed only if the RLO is 1. If a conditional call is not
executed, the RLO after the call instruction is 0. If the instruction is
executed, the following functions are performed:

S The address required to return to the calling block is saved.


S The data block registers are saved (data block and instance data block).
S The previous local data area is replaced by the current local data area.
S The MA bit (active MCR bit) is written to the block stack (BSTACK).
S The new local data area is created for the called FC or SFC.
Program execution is then continued in the called block.
For more detailed information about transferring parameters, refer to the
STEP 7 Online Help.
Table 16-1

Calling an FC/SFC without Parameters Box

FBD Box Parameters

Data Type

Memory
Area

<Number>
CALL

16-2

Number

BLOCK_FC

Description
Number of the FC or SFC (for example FC10 or
SFC59). The SFCs that are available depend on
your CPU.
A conditional call with a parameter of the data
type BLOCK_FC as the address is only possible
in an FB and not in an FC.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Program Control Instructions

DB10
OPN
MCRA
FC10
CALL

I0.0

Q4.0
=
MCRD

I0.1

FC11
CALL

If the unconditional call for FC10 is executed, the CALL instruction performs the following
functions:

S Saves the address required to return to the current FB.


S Saves the selectors for DB10 and for the instance data block of the FB.
S Pushes the MA bit, set to 1 in the MCRA instruction, to the block stack (BSTACK) and
resets this bit to 0 for the called FC10
Program execution continues in FC10. If you want to use the MCR function in FC10, you must
reactivate it there. When FC10 is completed, program execution returns to the calling FB. The
MA bit is restored. DB10 and the instance data block of the user-defined FB are the current
DBs again, regardless of which DBs were used by FC10.
After the return jump from FC10, the signal state of input I0.0 is assigned to output Q4.0. The
call for FC11 is a conditional call. It is executed only if the signal state of input I0.1 is 1. If the call
is executed, the function is the same as for calling FC10.

Status Word Bits


Unconditional call
writes

Conditional call
writes

Figure 16-1

BR

CC1

CC0

OV

OS
0

OR
0

STA
1

RLO

FC
0

BR

CC1

CC0

OV

OS
0

OR
0

STA
1

RLO
1

FC
0

Calling an FC/SFC without Parameters

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

16-3

Program Control Instructions

16.2 Calling an FB, FC, SFB, SFC, and Multiple Instances

Description

You can call function blocks (FBs), functions (FCs), system function blocks
(SFBs), and system functions (SFCs), and multiple instances by selecting
them from the Program Elements list box. They are at the end of the list of
instruction families under the following names:

S FB Blocks
S FC Blocks
S SFB Blocks
S SFC Blocks
S Multiple Instances
S Libraries
When you select one of these blocks, a box appears on your screen with the
number or symbolic name of the function or function block and the
parameters that belong to it.
The block that you call must have been compiled and must already exist in
your program file, in the library, or on the CPU.
If the call FB, FC, SFB, SFC, and multiple instances instruction is executed,
it performs the following functions:

S It saves the address required to return to the calling block.


S It saves both data block registers (data block and instance data block).
S It replaces the previous local data area with the current local data area.
S It shifts the MA bit (active MCR bit) to the block stack (BSTACK).
S It creates the new local data area for the called FC or SFC.
Note
When the DB and DI registers are saved, it is possible that they do not point
to the data blocks that you opened. Because of the copy mechanisms for
transferring parameters, especially where function blocks are concerned, the
compiler sometimes overwrites the DB register. See the STEP 7 Online Help
for more details.

Execution of the program then continues in the called block.

16-4

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Program Control Instructions

Enable Output

The Enable output (ENO) of an FBD box corresponds to the BR bit of the
status word (see Section 2.3). When you write a function block or function
that you want to call from FBD regardless of whether you write the FB or FC
in STL, LAD or FBD, keep in mind the BR bit. You save the RLO in the BR
bit with the SAVE instruction according to the following criteria:

S Save an RLO of 1 in the BR bit when the FB or FC is executed without


error.

S Save an RLO of 0 in the BR bit when an error occurs in the execution of


the FB or FC.
You should program these instructions at the end of the FB or FC so that
these are the last instructions that are executed in the block.

Warning
Unintentionally resetting the BR bit to 0
When writing FBs and FCs in FBD, if you do not handle the BR bit as
described above, one FB or FC may overwrite the BR bit of another FB
or FC.
To avoid this problem, store the RLO at the end of each FB or FC as
described above.

Effect of the Call


on the Bits of the
Status Word

Conditional:
writes
Unconditional: writes

Figure 16-2

Figure 16-2 shows the effects of a conditional and an unconditional call of a


block on the bits of the status word (see Section 2.3).

BR
x

CC1

CC0

OV

OS
0
0

OR
0
0

STA
1
x

RLO
x
x

FC
x
x

Effect of a Block Call on the Bits of the Status Word

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

16-5

Program Control Instructions

Parameters

The parameters that have been defined in the VAR section of the block will
be displayed in the FBD box. Supplying parameters differs depending on the
type of block as follows:

S For a function (FC), you must supply actual parameters for all of the
formal parameters.

S The entry of actual parameters is optional with function blocks (FBs).


You must, however, attach an instance data block (instance DB) to the
FB. If an actual parameter has not been attached to a formal parameter,
the FB works with the values that exist in its instance DB.

S With multiple instances, you do not need to specify the instance DB since
the box that is called has already been assigned the DB number (for more
information about declaring multiple instances, refer to STEP 7 Online
Help
For structured IN/OUT parameters and parameters of the types Pointer and
Array, you must make an actual parameter available (at least during the
first call).
Every actual parameter that you make available when calling a function
block must have the same data type as its formal parameter.
For information on how to program a function or how to work with its
parameters, see the STEP 7 Online Help.
Table 16-2 shows a box for calling FBs, FCs, SFBs, SFCs and describes the
parameters common to the box for all these blocks. The block number
appears automatically at the top of the block (number of the FB, FC, SFB, or
SFC, for example, FC10).
Table 16-2

Box and Parameters for Calling FBs, FCs, SFBs, SFCs

FBD Box
DB no.
Block no.
EN
IN
OUT
IN/OUT ENO

Parameters

Data Type

Memory Area

Description

DB no.

BLOCK_DB

Data block number. This


information is only necessary for
calling FBs.

EN

BOOL

I, Q, M, D, L, T, C

Enable input

ENO

BOOL

I, Q, M, D, L

Enable output

DB13
Calls FB10 (using
instance DB13)

FB10
Actual addresses,
the values of which
are copied into
instance data block
DB13 before
processing FB10.

I 1.0

EN
Start

I 1.1

Stop

MW20

Length

ENO
Run

M2.1

The value of this parameter is


copied from DB13 into M 2.1 after
processing FB10.

Formal parameters of the FB


Figure 16-3

16-6

Call FB as Box

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Program Control Instructions

16.3 Return

Description

Table 16-3

You can use the Return instruction to exit blocks. You can exit a block
conditionally.
Box Return
Parameters

FBD Box
RET

None

I0.0

Data Type

Memory Area

RET

Description

If the signal state of input I0.0 is 1, the block is


exited.

Status Word Bits


Conditional Return (Return if RLO = 1)
writes

Figure 16-4

BR

CC1

CC0

OV

OS
0

OR
0

STA
1

RLO
1

FC
0

Return

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

16-7

Program Control Instructions

16.4 Master Control Relay Instructions

Definition of the
Master Control
Relay

The Master Control Relay (MCR, see also Section 16.5) is used to activate
and deactivate signal flow. A deactivated signal flow corresponds to an
instruction sequence that writes a zero value instead of the calculated value,
or to an instruction sequence that leaves the existing memory value
unchanged. Operations triggered by the instructions shown in Table 16-4 are
dependent on the MCR.
The Assign and Midline Output instructions write a 0 to the memory if the
MCR is 0. The Set Output and Reset Output instructions leave the existing
value unchanged (see Table 16-5).

Table 16-4

Instructions Influenced by an MCR Zone


FBD Box

Description

Midline Output

4.9

Assign

4.8

Set Output

4.11

Reset Output

4.12

Set_Reset Flip Flop

4.25

Set_Reset Flip Flop

4.26

Assign a Value

10.1

SR
RS
MOVE

Table 16-5

Instructions Dependent on MCR and How They React to Its Signal State

Signal State of
MCR

Assign, Midline Output


=
#

16-8

Section in This Manual

Writes 0

Set or Reset Output


S

SR

RS

Does not write

Assign a Value

MOVE

Writes 0

(Imitates a relay that falls to its (Imitates a latching relay that


quiet state when power is
remains in its current state
turned off)
when power is turned off)

(Imitates a component that


produces a value of 0 when
power is turned off)

Normal execution

Normal execution

Normal execution

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Program Control Instructions

Important Notes on Using MCR Functions


Take care with blocks in which the Master Control Relay was activated with
MCRA:

S If the MCR is deactivated, the value 0 is written by all assignments in


program segments between (MCR<) and (MCR>)!

S The MCR is deactivated if the RLO was =0 before an MCR< instruction.

Danger
PLC in STOP or undefined runtime characteristics!
The compiler also uses write access to local data behind the temporary variables defined in VAR_TEMP for calculating addresses. This means the following command sequences will set the PLC to STOP or lead to undefined
runtime characteristics:
Formal parameter access
S Access to components of complex FC parameters of the type STRUCT,
UDT, ARRAY, STRING
S Access to components of complex FB parameters of the type STRUCT,
UDT, ARRAY, STRING from the IN_OUT area in a version 2 block.
S Access to parameters of a version 2 function block if its address is
greater than 8180.0.
S Access in a version 2 function block to a parameter of the type
BLOCK_DB opens DB0. Any subsequent data access sets the CPU to
STOP. T 0, C 0, FC0, or FB0 are also always used for TIMER,
COUNTER, BLOCK_FC, and BLOCK_FB.
Parameter passing

S Calls in which parameters are transferred.


KOP/FUP
S T branches and midline outputs in Ladder or FBD starting with RLO = 0.

Remedy
Free the above commands from their dependence on the MCR:
1. Deactivate the Master Control Relay using the Master Control Relay
Deactivate instruction before the statement or network in question.
2. Activate the Master Control Relay again using the Master Control Relay
Activate instruction after the statement or network in question.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

16-9

Program Control Instructions

16.5 Master Control Relay Activate/Deactivate

MCR Activate

Table 16-6

Master Control Relay Activate Box

FBD Box
MCRA

MCR Deactivate

Table 16-7

With the Activate Master Control Relay, instruction, you make subsequent
commands dependent on the MCR. After entering this command, you can
program the MCR zones with these instructions (see Section 16.6). When
your program activates an MCR area, all MCR actions depend on the content
of the MCR stack (see Figure B-4).

Parameters
None

Data Type

Memory Area

Description
Activates the MCR function

With the Deactivate Master Control Relay instruction, subsequent commands


are no longer dependent on the MCR. After this instruction, you cannot
program any more MCR zones. When your program deactivates an MCR
area, the MCR is always energized irrespective of the entries in the MCR
stack.

Master Control Relay Deactivate Box

FBD Box
MCRD

Parameters
None

Data Type

Memory Area

Description
Deactivates the MCR function

The MCR stack and the bit that controls its dependency (the MA bit) relate to
individual levels and must be saved and fetched every time you change the
sequence level. They are preset at the beginning of every sequence level
(MCR input bits 1 to 8 are set to 1, the MCR stack pointer is set to 0 and the
MA bit is set to 0).
The MCR stack is transferred from block to block and the MA bit is saved
and set to 0 every time a block is called. It is fetched back at the end of the
block.
The MCR can be implemented in such a way that it optimizes the run time of
code-generating CPUs. The reason for this is that the dependency of the
MCR is not passed on by the block; it must be explicitly activated by an
MCR instruction. A code-generating CPU recognizes this instruction and
generates the additional code necessary for the evaluation of the MCR stack
until it recognizes an MCR instruction or reaches the end of the block. With
instructions outside the MCRA/MCRD range, there is no increase of the run
time.
The instructions MCRA and MCRD must always be used in pairs within your
program.

16-10

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Program Control Instructions

OB1

MCRA

FBx

FCy

MCRA

MCRD

MCRA

Call FCy

Call FBx

MCRD

BEU

MCRA

BEU

Operations not dependent on the MCR bit


Operations dependent on the MCR bit
BEU

Figure 16-5

BEU is an STL instruction.


You will find more details in the STL Manual /232/
Activating and Deactivating an MCR Area

The operations programmed between MCRA and MCRD depend on the


signal state of the MCR bit. Operations programmed outside an
MCRA-MCRD sequence do not depend on the signal state of the MCR bit. If
an MCRD instruction is missing, the operations programmed between the
instructions MCRA and BEU depend on the MCR bit.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

16-11

Program Control Instructions

MCRA
I0.0

MCR<

I0.3

Q4.0
S

I0.4

Q4.1
=
MCR>
MCRD

The MCRA instruction activates the MCR function until the next MCRD. The instructions
between MCR< and MCR> are processed dependent on the MA bit (here I0.0):

S If the signal state of input I0.0 is 1:

Output Q4.0 is set to 1 if the signal state of input I0.3 is 1.


Output Q4.0 remains unchanged if the signal state of input I0.3 is 0.
The signal state of input I0.4 is assigned to output Q4.1.

S If the signal state of input I0.0 is 0:

Output Q4.0 remains unchanged regardless of the signal state of input I0.3.
Output Q4.1 is 0 regardless of the signal state of input I0.4.
Status Word Bits

writes
Figure 16-6

BR

CC1

CC0

OV

OS

OR

STA

RLO

FC

Master Control Relay (Activate and Deactivate)

You must program the dependency of the functions (FCs) and function blocks
(FBs) in the blocks yourself. If this function or function block is called from
an MCRA/MCRD sequence, not all instructions within this sequence are
automatically dependent on the MCR bit. To achieve this, use the instruction
MCRA of the block called.

Warning
Risk of personal injury and damage to equipment:
Never use the instruction MCR as an EMERGENCY OFF or safety device
for personnel.
MCR is not a substitute for a hardwired master control relay.

16-12

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Program Control Instructions

16.6 Master Control Relay On/Off

MCR On

Table 16-8

The Master Control Relay On (MCR<) instruction triggers an operation that


saves the RLO in the MCR stack and opens an MCR zone. The instructions
shown in Table 16-4 are influenced by this RLO saved in the MCR stack
when the MCR zone is opened. The MCR stack works like a LIFO (Last In,
First Out) buffer. Only eight entries are possible. If the stack is already full,
the Master Control Relay On instruction produces an MCR stack error
(MCRF).
Master Control Relay On Box

FBD Box
MCR<

MCR Off

Table 16-9

Parameters
None

Data Type

Memory Area

Description
Opens an MCR zone

The Master Control Relay Off (MCR>) instruction closes the MCR zone that
was opened last. The instruction does this by removing the RLO entry from
the MCR stack. The RLO was saved there by the Master Control Relay On
instruction. The entry released at the other end of the LIFO (Last In, First
Out) MCR stack is set to 1. If the stack is already empty, the Master Control
Relay Off instruction produces an MCR stack error (MCRF).
Master Control Relay Off

FBD Box
MCR>

Parameters
None

Data Type

Memory Area

Description
Closes the MCR zone that was
opened last

The MCR is controlled by a stack which is one bit wide and eight entries
deep (see Figure 16-7). The MCR is activated as long as all eight entries in
the stack are equal to 1. The MCR< instruction copies the RLO to the MCR
stack. The MCR> instruction removes the last entry from the stack and sets
the released stack address to 1. If an error occurs, for example, if there are
more than eight MCR> instructions in succession, or you attempt to execute
the instruction MCR> when the stack is empty, the MCRF error message is
activated. The monitoring of the MCR stack is based on the stack pointer
(MSP: 0 = empty, 1 = one entry, 2 = two entries, ..., 8 = eight entries).

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

16-13

Program Control Instructions

RLO Shifted bit


#
"

MSP !

RLO
RLO

RLO

2
4
5
6
7

Shifted bit

8
"

#
1
MA
"

MCRA 1

"
0 MCRD

MSP = MCR stack pointer


MA = Bit controlling MCR dependency
Figure 16-7

Master Control Relay Stack

The instructions MCR< and MCR> must always be used in pairs within your
program.
The MCR< instruction adopts the signal state of the RLO and copies it to the
MCR bit.
The MCR> instruction sets the MCR bit to 1 unconditionally. Because of this
characteristic, every other instruction between the instructions MCRA and
MCRD operates independent of the MCR bit (for information about MCRA
and MCRD, see above).

Nesting the
Instructions MCR<
and MCR>

You can nest the instructions MCR< and MCR>. The maximum nesting
depth is eight, in other words, you can write a maximum of eight MCR<
instructions in succession before inserting an MCR> instruction. You must
program an equal number of MCR< and MCR> instructions.
If the MCR< instructions are nested, the MCR bit of the lower nesting level
is formed. The MCR< instruction then combines the current RLO with the
current MCR bit according to the AND truth table.
When an MCR> instruction completes a nesting level, it fetches the MCR bit
from the next highest level.

16-14

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Program Control Instructions

MCRA
I0.0

MCR<

I0.1

MCR<
Q4.0
S

I0.3

MCR>
Q4.1
=

I0.4

MCR>
MCRD

When the MCRA instruction activates the MCR function, you can create up to eight nested MCR
zones. In the example, there are two MCR zones. The first MCR> instruction works together with the
second MCR< instruction. All instructions between the second set of MCR brackets (MCR<MCR>)
belong to the second MCR zone. The operations are executed as follows:
S If I0.0 = 1: the signal state of input I0.4 is assigned to output Q4.1.
S If I0.0 = 0: the signal state of output Q4.1 is 0 regardless of the signal state of input I0.4. Output
Q4.0 remains unchanged regardless of the signal state of input I0.3.
S If I0.0 and I0.1 = 1: output Q4.0 is set to 1 if I0.3 = 1 and Q4.1 = I0.4.
S If I0.1 = 0: output Q4.0 remains unchanged regardless of the signal state of input I0.3 and input
I0.0.

Status Word Bits

writes
Figure 16-8

BR

CC1

CC0

OV

OS

OR
0

STA
1

RLO

FC
0

Master Control Relay Off

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

16-15

Program Control Instructions

16-16

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Appendix

Alphabetical Lists of Instructions

Programming Examples

References

P-18

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Alphabetical Lists of Instructions


Chapter
Overview

Section

Description

A
Page

A.1

List of Instructions with International Names

A-2

A.2

List of Instructions with International (English) Names and


German Equivalents

A-6

A.3

List of Instructions with German SIMATIC Names

A-10

A.4

List of Instructions with German Names and International


(English) Equivalents

A-14

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

A-1

Alphabetical List of Instructions

A.1

List of Instructions with International Names


Table A-1 contains an alphabetical list of FBD instructions with international
(English) full names, the corresponding short name or mnemonic, and the
reference to the page on which the instruction is described.

Table A-1

FBD Instructions Arranged Alphabetically by International (English) Full Names with Short
Names
Short Name

Full Name

Page

Add Double Integer

ADD_DI

7-3

Add Integer

ADD_I

7-2

Add Real

ADD_R

8-3

Address Negative Edge Detection

NEG

4-31

Address Positive Edge Detection

POS

4-30

AND

&

4-3

Assign

4-9

Assign a Value

MOVE

10-2

BCD to Double Integer

BCD_DI

10-6

BCD to Integer

BCD_I

10-3

Call FB from Box

CALL_FB

16-4

Call FC from Box

CALL_FC

16-4

Call FC SFC (without parameters)

CALL

16-2

Call System FB from Box

CALL_SFB

16-4

Call System FC from Box

CALL_SFC

16-4

Ceiling

CEIL

10-16

Compare Double Integer (>, <, ==, <>, <=, >=)

CMP >=D

9-3

Compare Integer (>, <, ==, <>, <=, >=)

CMP >=I

9-2

Compare Real (>, <, ==, <>, <=, >=)

CMP >=R

9-4

Divide Double Integer

DIV_DI

7-9

Divide Integer

DIV_I

7-8

Divide Real

DIV_R

8-6

Double Integer to BCD

DI_BCD

10-7

Double Integer to Real

DI_R

10-8

Down Counter (counter instruction)

S_CD

6-7

Down Counter (bit logic instruction)

CD

4-17

Exception Bit Binary Result

BR

15-3

Exception Bit Overflow

OV

15-7

Exception Bit Overflow Stored

OS

15-8

Exception Bit Unordered

UO

15-6

Exclusive OR

XOR

4-6

Extended Pulse S5 Timer (timer instruction)

S_PEXT

5-7

A-2

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Alphabetical List of Instructions

Table A-1

FBD Instructions Arranged Alphabetically by International (English) Full Names with Short
Names, cont.
Full Name

Short Name

Page

Extended Pulse Timer (bit logic instruction)

SE

4-20

Floor

FLOOR

10-17

Form the Absolute Value of a Floating-Point Number

ABS

8-8

Form the Arc Cosine of a Floating-Point Number

ACOS

8-13

Form the Arc Sine of a Floating-Point Number

ASIN

8-13

Form the Arc Tangent of a Floating-Point Number

ATAN

8-13

Form the Cosine of a Floating-Point Number

COS

8-13

Form the Exponential Value of a Floating-Point Number

EXP

8-12

Form the Natural Logarithm of a Floating-Point Number

LN

8-11

Form the Sine of a Floating-Point Number

SIN

8-13

Form the Square of a Floating-Point Number

SQR

8-9

Form the Square Root of a Floating-Point Number

SQRT

8-10

Form the Tangent of a Floating-Point Number

TAN

8-13

Insert Binary Input

4-7

Integer to BCD

I_BCD

10-4

Integer to Double Integer

I_DI

10-5

Jump

JMP

14-3

Jump-If-Not

JMPN

14-5

Master Control Relay Activate

MCRA

16-10

Master Control Relay Deactivate

MCRD

16-10

Master Control Relay Off

MCR>

16-13

Master Control Relay On

MCR<

16-13

Midline Output

4-10

Multiply Double Integer

MUL_DI

7-7

Multiply Integer

MUL_I

7-6

Multiply Real

MUL_R

8-5

Negate Binary Input

o|

4-8

Negate Real Number

NEG_R

10-13

Negative RLO Edge Detection

4-29

Off-Delay S5 Timer (timer instruction)

S_OFFDT

5-13

Off-Delay Timer (bit logic instruction)

SF

4-26

On-Delay S5 Timer (timer instruction)

S_ODT

5-9

On-Delay Timer (bit logic instruction)

SD

4-22

Ones Complement Double Integer

INV_DI

10-10

Ones Complement Integer

INV_I

10-9

Open Data Block: DB or DI

OPN

13-2

OR

>=1

4-4

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

A-3

Alphabetical List of Instructions

Table A-1

FBD Instructions Arranged Alphabetically by International (English) Full Names with Short
Names, cont.
Full Name

Short Name

Page

Positive RLO Edge Detection

4-28

Pulse S5 Timer (timer instruction)

S_PULSE

5-5

Pulse Timer (bit logic instruction)

SP

4-18

Reset Output

4-13

Reset_Set Flip Flop

RS

4-33

Result Bit Equal 0

==0

1-6

Result Bit Greater Equal 0

>=0

15-4

Result Bit Greater Than 0

>0

15-4

Result Bit Less Equal 0

<=0

15-4

Result Bit Less Than 0

<0

15-4

Result Bit Not Equal 0

<>0

15-4

Retentive On-Delay S5 Timer (timer instruction)

S_ODTS

5-11

Retentive On-Delay Timer (bit logic instruction)

SS

4-24

Return

RET

16-7

Return Fraction Double Integer

MOD

7-10

Rotate Left Double Word

ROL_DW

12-11

Rotate Right Double Word

ROR_DW

12-12

Round to Double Integer

ROUND

10-14

Save RLO to BR Memory

SAVE

4-11

Set Output

4-12

Set Counter Value

SC

4-14

Set_Reset Flip Flop

SR

4-32

Shift Left Double Word

SHL_DW

12-4

Shift Left Word

SHL_W

12-3

Shift Right Double Integer

SHR_DI

12-9

Shift Right Double Word

SHR_DW

12-6

Shift Right Integer

SHR_I

12-8

Shift Right Word

SHR_W

12-5

Subtract Double Integer

SUB_DI

7-5

Subtract Integer

SUB_I

7-4

Subtract Real

SUB_R

8-4

Truncate Double Integer Part

TRUNC

10-15

Twos Complement Double Integer

NEG_DI

10-12

Twos Complement Integer

NEG_I

10-11

Up Counter (counter instruction)

S_CU

6-5

Up Counter (bit logic instruction)

CU

4-16

Up-Down Counter

S_CUD

6-3

A-4

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Alphabetical List of Instructions

Table A-1

FBD Instructions Arranged Alphabetically by International (English) Full Names with Short
Names, cont.
Full Name

Short Name

Page

(Word) AND Double Word

WAND_DW

11-4

(Word) AND Word

WAND_W

11-3

(Word) Exclusive OR Double Word

WXOR_DW

11-8

(Word) Exclusive OR Word

WXOR_W

11-7

(Word) OR Double Word

WOR_DW

11-6

(Word) OR Word

WOR_W

11-5

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

A-5

Alphabetical List of Instructions

A.2

List of Instructions with International (English) Names and German


Equivalents
Table A-4 contains an alphabetical list of FBD instructions with international
(English) full names, the German SIMATIC equivalents, and the reference to
the page on which the instruction is described.

Table A-2

FBD Instructions Arranged Alphabetically by International (English) Full Names with German
Equivalents
Full Name

German SIMATIC Equivalent

Page

Add Double Integer

Ganze Zahlen addieren (32 Bit)

7-3

Add Integer

Ganze Zahlen addieren (16 Bit)

7-2

Add Real

Gleitpunktzahlen addieren

8-3

Address Negative Edge Detection

Signalflanke 1 0 abfragen

4-31

Address Positive Edge Detection

Signalflanke 0 1 abfragen

4-30

AND

UND-Verknpfung

4-3

Assign

Zuweisung

4-9

Assign a Value

Wert bertragen

10-2

BCD to Double Integer

BCD-Zahl in Ganzzahl (32 Bit) wandeln

10-6

BCD to Integer

BCD-Zahl in Ganzzahl (16 Bit) wandeln

10-3

Call FB from Box

FB aufrufen

16-4

Call FC from Box

FC aufrufen

16-4

Call FC SFC (without parameters)

FC/SFC aufrufen ohne Parameter

16-2

Call System FB from Box

System FB aufrufen

16-4

Call System FC from Box

System FC Box aufrufen

16-4

Ceiling

Aus Gleitpunktzahl nchsthhere Ganzzahl


erzeugen

10-16

Compare Double Integer (>, <, ==, <>, <=, >=)

Ganze Zahlen vergleichen (32 Bit)

9-3

Compare Integer (>, <, ==, <>, <=, >=)

Ganze Zahlen vergleichen (16 Bit)

9-2

Compare Real (>, <, ==, <>, <=, >=)

Gleitpunktzahlen vergleichen

9-4

Divide Double Integer

Ganze Zahlen dividieren (32 Bit)

7-9

Divide Integer

Ganze Zahlen dividieren (16 Bit)

7-8

Divide Real

Gleitpunktzahlen dividieren

8-6

Double Integer to BCD

Ganzzahl (32 Bit) in BCD-Zahl wandeln

10-7

Double Integer to Real

Ganzzahl (32 Bit) in Gleitpunktzahl wandeln

10-8

Down Counter (counter instruction)

Rckwrtszhlen

6-7

Down Counter (bit logic instruction)

Rckwrtszhlen

4-17

Exception Bit Binary Result

Strungsbit BIE-Register

15-3

Exception Bit Overflow

Strungsbit berlauf

15-7

Exception Bit Overflow Stored

Strungsbit berlauf gespeichert

15-8

Exception Bit Unordered

Strungsbit Ungltige Operation

15-6

A-6

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Alphabetical List of Instructions

Table A-2

FBD Instructions Arranged Alphabetically by International (English) Full Names with German
Equivalents, cont.
Full Name

German SIMATIC Equivalent

Page

Exclusive OR

EXKLUSIV-ODER-Verknpfung

4-6

Extended Pulse S5 Timer (timer instruction)

Zeit als verlngerten Impuls starten (SV)

5-7

Extended Pulse Timer (bit logic instruction)

Zeit als verlngerten Impuls starten (SV)

4-20

Floor

Aus Gleitpunktzahl nchstniedere Ganzzahl


erzeugen

10-17

Form the Absolute Value of a Floating-Point


Number

Absolutwert einer Gleitpunktzahl bilden

8-8

Form the Arc Cosine of a Floating-Point


Number

Arcuscosinus einer Gleitpunktzahl bilden

8-13

Form the Arc Sine of a Floating-Point Number

Arcussinus einer Gleitpunktzahl bilden

8-13

Form the Arc Tangent of a Floating-Point


Number

Arcustangens einer Gleitpunktzahl bilden

8-13

Form the Cosine of a Floating-Point Number

Cosinus einer Gleitpunktzahl bilden

8-13

Form the Exponential Value of a Floating-Point


Number

Exponentialwert einer Gleitpunktzahl bilden

8-12

Form the Natural Algorithm of a Floating-Point Natrlichen Logarithmus einer Gleitpunktzahl


Number
bilden

8-11

Form the Sine of a Floating-Point Number

Sinus einer Gleitpunktzahl bilden

8-13

Form the Square of a Floating-Point Number

Quadrat einer Gleitpunktzahl bilden

8-9

Form the Square Root of a Floating-Point


Number

Quadratwurzel einer Gleitpunktzahl bilden

8-10

Form the Tangent of a Floating-Point Number

Tangens einer Gleitpunktzahl bilden

8-13

Insert Binary Input

Binren Eingang einfgen

4-7

Integer to BCD

Ganzzahl (16 Bit) in BCD-Zahl wandeln

10-4

Integer to Double Integer

Ganzzahl (16 Bit) in Ganzzahl (32 Bit) wandeln

10-5

Jump

Springe wenn 1

14-3

Jump-If-Not

Springe wenn 0

14-5

Master Control Relay Activate

Master Control Relay Anfang

16-10

Master Control Relay Deactivate

Master Control Relay Ende

16-10

Master Control Relay Off

Master Control Relay ausschalten

16-13

Master Control Relay On

Master Control Relay einschalten

16-13

Midline Output

Konnektor

4-10

Multiply Double Integer

Ganze Zahlen multiplizieren (32 Bit)

7-7

Multiply Integer

Ganze Zahlen multiplizieren (16 Bit)

7-6

Multiply Real

Gleitpunktzahlen multiplizieren

8-5

Negate Binary Input

Binren Eingang negieren

4-8

Negate Real Number

Vorzeichen einer Gleitpunktzahl wechseln

10-13

Negative RLO Edge Detection

Flanke 1 0 abfragen

4-29

OR

ODER-Verknpfung

4-4

Off-Delay S5 Timer (timer instruction)

Zeit als Ausschaltverzgerung starten (SA)

5-13

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

A-7

Alphabetical List of Instructions

Table A-2

FBD Instructions Arranged Alphabetically by International (English) Full Names with German
Equivalents, cont.
Full Name

German SIMATIC Equivalent

Page

Off-Delay Timer (bit logic instruction)

Zeit als Ausschaltverzgerung starten (SA)

4-26

On-Delay S5 Timer (timer instruction)

Zeit als Einschaltverzgerung starten (SE)

5-9

On-Delay Timer (bit logic instruction)

Zeit als Einschaltverzgerung starten (SE)

4-22

Ones Complement Double Integer

1er Komplement zu Ganzzahl (32 Bit) erzeugen

10-10

Ones Complement Integer

1er Komplement zu Ganzzahl (16 Bit) erzeugen

10-9

Open Data Block: DB or DI

Datenbaustein ffnen

13-2

Positive RLO Edge Detection

Flanke 0 1 abfragen

4-28

Pulse S5 Timer (timer instruction)

Zeit als Impuls starten (SI)

5-5

Pulse Timer (bit logic instruction)

Zeit als Impuls starten (SI)

4-18

Reset Output

Ausgang rcksetzen

4-13

Reset_Set Flip Flop

Flipflop rcksetzen setzen

4-33

Result Bit Equal 0

Ergebnisbit bei gleich 0

15-4

Result Bit Greater Equal 0

Ergebnisbit bei grer gleich 0

15-4

Result Bit Greater Than 0

Ergebnisbit bei grer als 0

15-4

Result Bit Less Equal 0

Ergebnisbit bei kleiner gleich 0

15-4

Result Bit Less Than 0

Ergebnisbit bei kleiner 0

15-4

Result Bit Not Equal 0

Ergebnisbit bei ungleich 0

15-4

Retentive On-Delay S5 Timer (timer instruction) Zeit als speich. Einschaltverzgerung starten (SS)

5-11

Retentive On-Delay Timer


(Bitverknpfungsperation)

Zeit als speich. Einschaltverzgerung starten (SS)

4-24

Return

Springe zurck

16-7

Return Fraction Double Integer

Divisionsrest gewinnen (32 Bit)

7-10

Rotate Left Double Word

32 Bit links rotieren

12-11

Rotate Right Double Word

32 Bit rechts rotieren

12-12

Round to Double Integer

Zahl runden

10-14

Save RLO to BR Memory

Verknpfungsergebnis ins BIE-Register laden

4-11

Set Output

Ausgang setzen

4-12

Set Counter Value

Zhleranfangswert setzen

4-14

Set_Reset Flip Flop

Flipflop setzen rcksetzen

4-32

Shift Left Double Word

32 Bit links schieben

12-4

Shift Left Word

16 Bit links schieben

12-3

Shift Right Double Integer

Ganzzahl (32 Bit) rechts schieben

12-9

Shift Right Double Word

32 Bit rechts schieben

12-6

Shift Right Integer

Ganzzahl (16 Bit) rechts schieben

12-8

Shift Right Word

16 Bit rechts schieben

12-5

Subtract Double Integer

Ganze Zahlen subtrahieren (32 Bit)

7-5

Subtract Integer

Ganze Zahlen subtrahieren (16 Bit)

7-4

Subtract Real

Gleitpunktzahlen subtrahieren

8-4

A-8

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Alphabetical List of Instructions

Table A-2

FBD Instructions Arranged Alphabetically by International (English) Full Names with German
Equivalents, cont.
Full Name

German SIMATIC Equivalent

Page

Truncate Double Integer Part

Ganze Zahl erzeugen

10-15

Twos Complement Double Integer

2er Komplement zu Ganzzahl (32 Bit) erzeugen

10-12

Twos Complement Integer

2er Komplement zu Ganzzahl (16 Bit) erzeugen

10-11

Up Counter (counter instruction)

Vorwrtszhlen

6-5

Up Counter (bit logic instruction)

Vorwrtszhlen

4-16

Up-Down Counter

Vorwrts-/Rckwrtszhlen

6-3

(Word) AND Double Word

32 Bit UND verknpfen

11-4

(Word) AND Word

16 Bit UND verknpfen

11-3

(Word) Exclusive OR Double Word

32 Bit EXKLUSIV ODER verknpfen

11-8

(Word) Exclusive OR Word

16 Bit EXKLUSIV ODER verknpfen

11-7

(Word) OR Double Word

32 Bit ODER verknpfen

11-6

(Word) OR Word

16 Bit ODER verknpfen

11-5

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

A-9

Alphabetical List of Instructions

A.3

List of Instructions with German SIMATIC Names


Table A-3 contains an alphabetical list of FBD instructions with the German
full names, the corresponding short name or mnemonic, and the reference to
the page on which the instruction is described.

Table A-3

FBD Instructions Arranged Alphabetically by German Full Names, with Short Names
SIMATIC Short Name

Page

1er Komplement zu Ganzzahl (16 Bit) erzeugen

INV_I

10-9

1er Komplement zu Ganzzahl (32 Bit) erzeugen

INV_DI

10-10

2er Komplement zu Ganzzahl (16 Bit) erzeugen

NEG_I

10-11

2er Komplement zu Ganzzahl (32 Bit) erzeugen

NEG_DI

10-12

16 Bit EXKLUSIV ODER verknpfen

WXOR_W

11-7

16 Bit links schieben

SHL_W

12-2

16 Bit ODER verknpfen

WOR_W

11-5

16 Bit rechts schieben

SHR_W

12-5

16 Bit UND verknpfen

WAND_W

11-3

32 Bit EXKLUSIV ODER verknpfen

WXOR_DW

11-8

32 Bit links rotieren

ROL_DW

12-11

32 Bit links schieben

SHL_DW

12-4

32 Bit ODER verknpfen

WOR_DW

11-6

32 Bit rechts rotieren

ROR_DW

12-12

32 Bit rechts schieben

SHR_DW

12-6

32 Bit UND verknpfen

WAND_DW

11-4

Absolutwert einer Gleitpunktzahl bilden

ABS

8-8

Arcuscosinus einer Gleitpunktzahl bilden

ACOS

8-13

Arcussinus einer Gleitpunktzahl bilden

ASIN

8-13

Arcustangens einer Gleitpunktzahl bilden

ATAN

8-13

Ausgang rcksetzen

4-13

Ausgang setzen

4-12

Aus Gleitpunktzahl nchsthhere Ganzzahl erzeugen

CEIL

10-16

Aus Gleitpunktzahl nchstniedere Ganzzahl erzeugen

FLOOR

10-17

BCD-Zahl in Ganzzahl (16 Bit) wandeln

BCD_I

10-3

BCD-Zahl in Ganzzahl (32 Bit) wandeln

BCD_DI

10-6

Binren Eingang einfgen

4-7

Binren Eingang negieren

o|

4-8

Cosinus einer Gleitpunktzahl bilden

COS

8-13

Datenbaustein ffnen

AUF

13-2

Divisionsrest gewinnen (32 Bit)

MOD

7-10

Ergebnisbit bei gleich 0

==0

15-4

Ergebnisbit bei grer als 0

>0

15-4

Full Name

A-10

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Alphabetical List of Instructions

Table A-3

FBD Instructions Arranged Alphabetically by German Full Names, with Short Names, cont.
Full Name

SIMATIC Short Name

Page

Ergebnisbit bei grer gleich 0

>=0

15-4

Ergebnisbit bei kleiner 0

<0

15-4

Ergebnisbit bei kleiner gleich 0

<=0

15-4

Ergebnisbit bei ungleich 0

<>0

15-4

EXKLUSIV-ODER-Verknpfung

XOR

4-6

Exponentialwert einer Gleitpunktzahl bilden

EXP

8-12

FB aufrufen

CALL_FB

16-4

FC aufrufen

CALL_FC

16-4

FC/SFC aufrufen ohne Parameter

CALL

16-2

Flanke 0 1 abfragen

4-28

Flanke 1 0 abfragen

4-29

Flipflop rcksetzen setzen

RS

4-33

Flipflop setzen rcksetzen

SR

4-32

Ganze Zahlen addieren (16 Bit)

ADD_I

7-2

Ganze Zahlen addieren (32 Bit)

ADD_DI

7-3

Ganze Zahlen dividieren (16 Bit)

DIV_I

7-8

Ganze Zahlen dividieren (32 Bit)

DIV_DI

7-9

Ganze Zahlen multiplizieren (16 Bit)

MUL_I

7-6

Ganze Zahlen multiplizieren (32 Bit)

MUL_DI

7-7

Ganze Zahlen subtrahieren (16 Bit)

SUB_I

7-4

Ganze Zahlen subtrahieren (32 Bit)

SUB_DI

7-5

Ganze Zahlen vergleichen (16 Bit)

CMP >=I

9-2

Ganze Zahlen vergleichen (32 Bit)

CMP >=D

9-3

Ganze Zahl erzeugen

TRUNC

10-15

Ganzzahl (16 Bit) in Ganzzahl (32 Bit) wandeln

I_DI

10-5

Ganzzahl (16 Bit) in BCD-Zahl wandeln

I_BCD

10-4

Ganzzahl (16 Bit) rechts schieben

SHR_I

12-8

Ganzzahl (32 Bit) in BCD-Zahl wandeln

DI_BCD

10-7

Ganzzahl (32 Bit) in Gleitpunktzahl wandeln

DI_R

10-8

Ganzzahl (32 Bit) rechts schieben

SHR_DI

12-9

Gleitpunktzahlen addieren

ADD_R

8-3

Gleitpunktzahlen dividieren

DIV_R

8-6

Gleitpunktzahlen multiplizieren

MUL_R

8-5

Gleitpunktzahlen subtrahieren

SUB_R

8-4

Gleitpunktzahlen vergleichen

CMP >=R

9-4

Konnektor

4-10

Master Control Relay Anfang

MCRA

16-10

Master Control Relay ausschalten

MCR>

16-13

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

A-11

Alphabetical List of Instructions

Table A-3

FBD Instructions Arranged Alphabetically by German Full Names, with Short Names, cont.
Full Name

SIMATIC Short Name

Page

Master Control Relay einschalten

MCR<

16-13

Master Control Relay Ende

MCRD

16-10

Natrlichen Logarithmus einer Gleitpunktzahl bilden

LN

8-11

ODER-Verknpfung

>=1

4-4

Quadrat einer Gleitpunktzahl bilden

SQR

8-9

Quadratwurzel einer Gleitpunktzahl bilden

SQRT

8-10

Rckwrtszhlen (Zhloperation)

Z_RUECK

6-7

Rckwrtszhlen (Bitverknpfungsoperation)

ZR

4-17

Signalflanke 0 1 abfragen

POS

4-30

Signalflanke 1 0 abfragen

NEG

4-31

Sinus einer Gleitpunktzahl bilden

SIN

8-13

Springe wenn 0

JMPN

14-5

Springe wenn 1

JMP

14-3

Springe zurck

RET

16-7

Strungsbit BIE-Register

BIE

15-3

Strungsbit berlauf

OV

15-7

Strungsbit berlauf gespeichert

OS

15-8

Strungsbit Ungltige Operation

UO

15-6

System FB aufrufen

CALL_SFB

16-4

System FC aufrufen

CALL_SFC

16-4

Tangens einer Gleitpunktzahl bilden

TAN

8-13

UND-Verknpfung

&

4-3

Verknpfungsergebnis ins BIE-Register laden

SAVE

4-11

Vorwrts-/Rckwrtszhlen

ZAEHLER

6-3

Vorwrtszhlen (Zhloperation)

Z_VORW

6-5

Vorwrtszhlen (Bitverknpfungsoperation)

ZV

4-16

Vorzeichen einer Gleitpunktzahl wechseln

NEG_R

10-13

Wert bertragen

MOVE

10-2

Zahl runden

ROUND

10-14

Zhleranfangswert setzen

SZ

4-14

Zeit als Ausschaltverzgerung starten (SA) (Zeitoperation)

S_AVERZ

5-13

Zeit als Ausschaltverzgerung starten (SA) (Bitverknpfungsoperation)

SA

4-26

Zeit als Einschaltverzgerung starten (SE) (Zeitoperation)

S_EVERZ

5-9

Zeit als Einschaltverzgerung starten (SE) (Bitverknpfungsoperation)

SE

4-22

Zeit als Impuls starten (SI) (Zeitoperation)

S_IMPULS

Zeit als Impuls starten (SI) (Bitverknpfungsoperation)

SI

4-18

Zeit als speich. Einschaltverzgerung starten (SS) (Zeitoperation)

S_SEVERZ

5-11

A-12

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Alphabetical List of Instructions

Table A-3

FBD Instructions Arranged Alphabetically by German Full Names, with Short Names, cont.
Full Name

SIMATIC Short Name

Page

Zeit als speich. Einschaltverzgerung starten (SS)


(Bitverknpfungsoperation)

SS

4-24

Zeit als verlngerten Impuls starten (SV) (Zeitoperation)

S_VIMP

5-7

Zeit als verlngerten Impuls starten (SV) (Bitverknpfungsoperation)

SV

4-20

Zuweisung

4-9

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

A-13

Alphabetical List of Instructions

A.4

List of Instructions with German Names and International (English)


Equivalents
Table A-4 contains an alphabetical list of FBD instructions with German
SIMATIC full names, the international (English) equivalents, and the
reference to the page on which the instruction is described.

Table A-4

FBD Instructions Arranged Alphabetically by German Full Names with International (English)
Equivalents
International (English) Equivalent

SIMATIC Full Name

Page

1er Komplement zu Ganzzahl (16 Bit) erzeugen

Ones Complement Integer

10-9

1er Komplement zu Ganzzahl (32 Bit) erzeugen

Ones Complement Double Integer

10-10

2er Komplement zu Ganzzahl (16 Bit) erzeugen

Twos Complement Integer

10-11

2er Komplement zu Ganzzahl (32 Bit) erzeugen

Twos Complement Double Integer

10-12

16 Bit EXKLUSIV ODER verknpfen

(Word) Exclusive OR Word

11-7

16 Bit links schieben

Shift Left Word

12-2

16 Bit ODER verknpfen

(Word) OR Word

11-5

16 Bit rechts schieben

Shift Right Word

12-5

16 Bit UND verknpfen

(Word) AND Word

11-3

32 Bit EXKLUSIV ODER verknpfen

(Word) Exclusive OR Double Word

11-8

32 Bit links rotieren

Rotate Left Double Word

12-11

32 Bit links schieben

Shift Left Double Word

12-4

32 Bit ODER verknpfen

(Word) OR Double Word

11-6

32 Bit rechts rotieren

Rotate Right Double Word

12-12

32 Bit rechts schieben

Shift Right Double Word

12-6

32 Bit UND verknpfen

(Word) AND Double Word

11-4

Absolutwert einer Gleitpunktzahl bilden

Form the Absolute Value of a Floating-Point


Number

8-8

Arcuscosinus einer Gleitpunktzahl bilden

Form the Arc Cosine of a Floating-Point Number

8-13

Arcussinus einer Gleitpunktzahl bilden

Form the Arc Sine of a Floating-Point Number

8-13

Arcustangens einer Gleitpunktzahl bilden

Form the Arc Tangent of a Floating-Point


Number

8-13

Ausgang rcksetzen

Reset Output

4-13

Ausgang setzen

Set Output

4-12

Aus Gleitpunktzahl nchsthhere Ganzzahl erzeugen

Ceiling

10-16

Aus Gleitpunktzahl nchstniedere Ganzzahl erzeugen

Floor

10-17

BCD-Zahl in Ganzzahl (16 Bit) wandeln

BCD to Integer

10-3

BCD-Zahl in Ganzzahl (32 Bit) wandeln

BCD to Double Integer

10-6

Binren Eingang einfgen

Insert Binary Input

4-7

Binren Eingang negieren

Negate Binary Input

4-8

Cosinus einer Gleitpunktzahl bilden

Form the Cosine of a Floating-Point Number

8-13

Datenbaustein ffnen

Open Data Block: DB or DI

13-2

A-14

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Alphabetical List of Instructions

Table A-4

FBD Instructions Arranged Alphabetically by German Full Names with International (English)
Equivalents, cont.
SIMATIC Full Name

International (English) Equivalent

Page

Divisionsrest gewinnen (32 Bit)

Return Fraction Double Integer

7-10

Ergebnisbit bei gleich 0

Result Bit Equal 0

15-4

Ergebnisbit bei grer als 0

Result Bit Greater Than 0

15-4

Ergebnisbit bei grer gleich 0

Result Bit Greater Equal 0

15-4

Ergebnisbit bei kleiner 0

Result Bit Less Than 0

15-4

Ergebnisbit bei kleiner gleich 0

Result Bit Less Equal 0

15-4

Ergebnisbit bei ungleich 0

Result Bit Not Equal 0

15-4

EXKLUSIV-ODER-Verknpfung

Exclusive OR

4-6

Exponentialwert einer Gleitpunktzahl bilden

Form the Exponential Value of a Floating-Point


Number

8-12

FB aufrufen

Call FB from Box

16-4

FC aufrufen

Call FC from Box

16-4

FC/SFC aufrufen ohne Parameter

Call FC SFC (without parameters)

16-2

Flanke 0 1 abfragen

Positive RLO Edge Detection

4-28

Flanke 1 0 abfragen

Negative RLO Edge Detection

4-29

Flipflop rcksetzen setzen

Reset_Set Flip Flop

4-33

Flipflop setzen rcksetzen

Set_Reset Flip Flop

4-32

Ganze Zahlen addieren (16 Bit)

Add Integer

7-2

Ganze Zahlen addieren (32 Bit)

Add Double Integer

7-3

Ganze Zahlen dividieren (16 Bit)

Divide Integer

7-8

Ganze Zahlen dividieren (32 Bit)

Divide Double Integer

7-9

Ganze Zahlen multiplizieren (16 Bit)

Multiply Integer

7-6

Ganze Zahlen multiplizieren [32 Bit)

Multiply Double Integer

7-7

Ganze Zahlen subtrahieren (16 Bit)

Subtract Integer

7-4

Ganze Zahlen subtrahieren (32 Bit)

Subtract Double Integer

7-5

Ganze Zahlen vergleichen (16 Bit)

Compare Integer (>, <, ==, <>, <=, >=)

9-2

Ganze Zahlen vergleichen (32 Bit)

Compare Double Integer (>, <, ==, <>, <=, >=)

9-3

Ganze Zahl erzeugen

Truncate Double Integer Part

10-15

Ganzzahl (16 Bit) in Ganzzahl (32 Bit) wandeln

Integer to Double Integer

10-5

Ganzzahl (16 Bit) in BCD-Zahl wandeln

Integer to BCD

10-4

Ganzzahl (16 Bit) rechts schieben

Shift Right Integer

12-8

Ganzzahl (32 Bit) in BCD-Zahl wandeln

Double Integer to BCD

10-7

Ganzzahl (32 Bit) in Gleitpunktzahl wandeln

Double Integer to Real

10-8

Ganzzahl (32 Bit) rechts schieben

Shift Right Double Integer

12-9

Gleitpunktzahlen addieren

Add Real

8-3

Gleitpunktzahlen dividieren

Divide Real

8-6

Gleitpunktzahlen multiplizieren

Multiply Real

8-5

Gleitpunktzahlen subtrahieren

Subtract Real

8-4

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

A-15

Alphabetical List of Instructions

Table A-4

FBD Instructions Arranged Alphabetically by German Full Names with International (English)
Equivalents, cont.
SIMATIC Full Name

International (English) Equivalent

Page

Gleitpunktzahlen vergleichen

Compare Real (>, <, ==, <>, <=, >=)

9-4

Konnektor

Midline Output

4-10

Master Control Relay Anfang

Master Control Relay Activate

16-10

Master Control Relay ausschalten

Master Control Relay Off

16-13

Master Control Relay einschalten

Master Control Relay On

16-13

Master Control Relay Ende

Master Control Relay Deactivate

16-10

Natrlichen Logarithmus einer Gleitpunktzahl bilden

Form the Natural Algorithm of a Floating-Point


Number

8-11

Quadrat einer Gleitpunktzahl bilden

Form the Square of a Floating-Point Number

8-9

Quadratwurzel einer Gleitpunktzahl bilden

Form the Square Root of a Floating-Point


Number

8-10

ODER-Verknpfung

OR

4-4

Rckwrtszhlen (Zhloperation)

Down Counter

6-7

Rckwrtszhlen (Bitverknpfungsoperation)

Down Counter

4-17

Signalflanke 01 abfragen

Address Positive Edge Detection

4-30

Signalflanke 10 abfragen

Address Negative Edge Detection

4-31

Sinus einer Gleitpunktzahl bilden

Form the Sine of a Floating-Point Number

8-13

Springe wenn 0

Jump-If-Not

14-5

Springe wenn 1

Jump

14-3

Springe zurck

Return

16-7

Strungsbit BIE-Register

Exception Bit Binary Result

15-3

Strungsbit berlauf

Exception Bit Overflow

15-7

Strungsbit berlauf gespeichert

Exception Bit Overflow Stored

15-8

Strungsbit Ungltige Operation

Exception Bit Unordered

15-6

System FB aufrufen

Call System FB from Box

16-4

System FC aufrufen

Call System FC from Box

16-4

Tangens einer Gleitpunktzahl bilden

Form the Tangent of a Floating-Point Number

8-13

UND-Verknpfung

AND

4-3

Verknpfungsergebnis ins BIE-Register laden

Save RLO to BR Memory

4-11

Vorwrts-/Rckwrtszhlen

Up-Down Counter

6-3

Vorwrtszhlen (Zhloperation)

Up Counter

6-5

Vorwrtszhlen (Bitverknpfungsoperation)

Up Counter

4-16

Vorzeichen einer Gleitpunktzahl wechseln

Negate Real Number

10-13

Wert bertragen

Assign a Value

10-2

Zahl runden

Round to Double Integer

10-14

Zhleranfangswert setzen

Set Counter Value

4-14

Zeit als Ausschaltverzgerung starten (SA)


(Zeitoperation)

Off-Delay S5 Timer

5-13

A-16

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Alphabetical List of Instructions

Table A-4

FBD Instructions Arranged Alphabetically by German Full Names with International (English)
Equivalents, cont.
SIMATIC Full Name

International (English) Equivalent

Page

Zeit als Ausschaltverzgerung starten (SA)


(Bitverknpfungsoperation)

Off-Delay Timer

4-26

Zeit als Einschaltverzgerung starten (SE)


(Zeitoperation)

On-Delay S5 Timer

5-9

Zeit als Einschaltverzgerung starten (SE)


(Bitverknpfungsoperation)

On-Delay Timer

4-22

Zeit als Impuls starten (SI) (Zeitoperation)

Pulse S5 Timer

5-5

Zeit als Impuls starten (SI) (Bitverknpfungsoperation) Pulse Timer

4-18

Zeit als speich. Einschaltverzgerung starten (SS)


(Zeitoperation)

Retentive On-Delay S5 Timer

5-11

Zeit als speich. Einschaltverzgerung starten (SS)


(Bitverknpfungsoperation)

Retentive On-Delay Timer

4-22

Zeit als verlngerten Impuls starten (SV)


(Zeitoperation)

Extended Pulse S5 Timer

5-7

Zeit als verlngerten Impuls starten (SV)


(Bitverknpfungsoperation)

Extended Pulse Timer

4-20

Zuweisung

Assign

4-9

Table A-5

FBD Instructions Listed in this Manual with their International Full and Short Names and their
SIMATIC Short Names
SIMATIC Full Name

International Short
Name

SIMATIC Short Name

Page

Down Counter (counter instruction)

S_CD

Z_RUECK

6-7

Down Counter (bit logic instruction)

CD

ZR

4-17

Exception Bit Binary Result

BR

BIE

15-3

Extended Pulse S5 Timer (timer instruction)

S_PEXT

S_VIMP

5-7

Extended Pulse Timer (bit logic instruction)

SE

SV

11-5

Off-Delay S5 Timer (timer instruction)

S_OFFDT

S_AVERZ

5-13

Off-Delay Timer (bit logic instruction)

SF

SA

4-26

On-Delay S5 Timer (timer instruction)

S_ODT

S_EVERZ

5-9

On-Delay Timer (bit logic instruction)

SD

SE

4-22

Open Data Block: DB or DI

OPN

AUF

13-2

Pulse S5 Timer (timer instruction)

S_PULSE

S_IMPULS

5-5

Pulse Timer (bit logic instruction)

SP

SI

4-18

Retentive On-Delay S5 Timer (timer


instruction)

S_ODTS

S_SEVERZ

5-11

Retentive On-Delay Timer (bit logic


instruction)

SS

SS

4-24

Set Counter Value

SC

SZ

4-14

Up Counter (counter instruction)

S_CU

Z_VORW

6-5

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

A-17

Alphabetical List of Instructions

Table A-5

FBD Instructions Listed in this Manual with their International Full and Short Names and their
SIMATIC Short Names, continued
SIMATIC Full Name

International Short
Name

SIMATIC Short Name

Page

Up Counter (bit logic instruction)

CU

ZV

4-16

Up-Down Counter

S_CUD

ZAEHLER

6-3

A-18

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Programming Examples
Chapter
Overview

Section

Description

Page

B.1

Overview

B-2

B.2

Bit Logic Instructions

B-3

B.3

Timer Instructions

B.4

Counter and Comparison Instructions

B-11

B.5

Integer Math Instructions

B-13

B.6

Word Logic Instructions

B-14

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

B-7

B-1

Programming Examples

B.1

Overview

Practical
Applications

Each FBD instruction described in this manual executes a specific function.


When you combine these instructions into a program, you can accomplish a
wide variety of automation tasks. This chapter provides the following
examples of practical applications of the FBD instructions:

S Controlling a conveyor belt using bit logic instructions


S Detecting direction of movement on a conveyor belt using bit logic
instructions

S Generating a clock pulse using timer instructions


S Keeping track of storage space using counter and comparison instructions
S Solving a problem using integer math instructions
S Setting the length of time for heating an oven
Instructions Used

The examples in this chapter use the following instructions:

S Add Integer (ADD_I)


S AND
S Assign (=)
S Assign a Value (MOVE)
S Compare Integer (CMP_I>=)
S Compare Integer (CMP_I<=)
S Divide Integer (DIV_I)
S Down Counter (S_CD)
S Extended Pulse Timer (SE)
S Jump-If-Not (JMPN)
S Multiply Integer (MUL_I)
S OR
S Positive RLO Edge Detection (P)
S Reset Output (R)
S Return (RET)
S Set Output (S)
S Up Counter (S_CU)
S (Word) AND Word (WAND_W)
S (Word) OR Word (WOR_W)

B-2

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Programming Examples

B.2

Bit Logic Instructions

Controlling a
Conveyor Belt

Figure B-1 shows a conveyor belt that can be activated electrically. There are
two push button switches at the beginning of the belt: S1 for START and S2
for STOP. There are also two push button switches at the end of the belt: S3
for START and S4 for STOP. It it possible to start or stop the belt from either
end. Sensor S5 stops the belt when an item on the belt reaches the end.

Symbolic
Programming

You can write a program to control the conveyor belt shown in Figure B-1
using symbols that represent the various components of the conveyor system.
If you choose this method, you need to make a symbol table to correlate the
symbols you choose with absolute values (see Table B-1). You define the
symbols in the symbol table (see the STEP 7 Online Help).
Table B-1

Elements of Symbolic Programming for Conveyor Belt System


Absolute
Address

Symbol

Start button

I1.1

S1

I1.1

S1

Stop button

I1.2

S2

I1.2

S2

Start button

I1.3

S3

I1.3

S3

Stop button

I1.4

S4

I1.4

S4

Sensor

I1.5

S5

I1.5

S5

Motor

Q4.0

MOTOR_ON

Q4.0

MOTOR_ON

System Component

Symbol Table

Sensor S5

MOTOR_ON
Figure B-1

S1
S2

` Start
` Stop

S3
S4

` Start
` Stop

Conveyor Belt System

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

B-3

Programming Examples

Absolute
Programming

You can write a program to control the conveyor belt shown in Figure B-1
using absolute values that represent the different components of the conveyor
system (see Table B-2). Figure B-2 shows an FBD program to control the
conveyor belt.
Table B-2

Elements of Absolute Programming for Conveyor Belt System


Absolute Address

System Component
Start button

I1.1

Stop button

I1.2

Start button

I1.3

Stop button

I1.4

Sensor

I1.5

Motor

Q4.0

Network 1: Pressing either start button turns the motor on.

I1.1

>=1
Q4.0
S

I1.3

Network 2: Pressing either stop button or the sensor at the end of the belt responding turns the
motor off.

I1.2
I1.4
E1.5

Figure B-2

B-4

>=1
Q4.0
R

Function Block Diagram to Control a Conveyor Belt

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Programming Examples

Detecting the
Direction of a
Conveyor Belt

Figure B-3 shows a conveyor belt that is equipped with two photoelectric
barriers (PEB1 and PEB2) that are designed to detect the direction in which a
package is moving on the belt.

Symbolic
Programming

You can write a program to activate a direction display for the conveyor belt
system shown in Figure B-3 using symbols that represent the various
components of the conveyor system, including the photoelectric barriers that
detect direction. If you choose this method, you need to make a symbol table
to correlate the symbols you choose with absolute values (see Table B-3).
You define the symbols in the symbol table (see the STEP 7 Online Help).
Table B-3

Elements of Symbolic Programming for Detecting Direction


Absolute
Address

System Component
Photoelectric barrier 1

Absolute
Programming

Q4.0

Figure B-3

Symbol

Symbol Table

I0.0

PEB1

I0.0

PEB1

Photoelectric barrier 2

I0.1

PEB2

I0.1

PEB2

Display for movement to right

Q4.0

RIGHT

Q4.0

RIGHT

Display for movement to left

Q4.1

LEFT

Q4.1

LEFT

Clock memory bit 1

M0.0

PM1

M0.0

PM1

Clock memory bit 2

M0.1

PM2

M0.1

PM2

You can write a program to activate the direction display for the conveyor
belt shown in Figure B-3 using absolute values that represent the
photoelectric barriers that detect direction (see Table B-4). Figure B-4 shows
an FBD program to control the direction display for the conveyor belt.

PEB2

PEB1

Q4.1

Conveyor Belt System with Photoelectric Light Barriers for Detecting


Direction

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

B-5

Programming Examples

Table B-4

Elements of Absolute Programming for Detecting Direction


Absolute Address

System Component
Photoelectric barrier 1

I0.0

Photoelectric barrier 2

I0.1

Display for movement to right

Q4.0

Display for movement to left

Q4.1

Clock memory bit 1

M0.0

Clock memory bit 2

M0.1

Network 1: If there is a transition in signal state from 0 to 1 (rising edge) at input I0.0 and, at the same
time, the signal state at input I0.1 is 0, then the package on the belt is moving to the left.

M 0.0
I0.0

&
Q4.1
S

I0.1

Network 2: If there is a transition in signal state from 0 to 1 (rising edge) at input I0.1 and, at the same
time, the signal state at input I0.0 is 0, then the package on the belt is moving to the right.
M 0.1
I0.1

P
I0.0

&
Q4.0
S

If one of the photoelectric light barriers is interrupted, this means that there is a package between the
barriers.
&
I0.0
I0.1

Q4.0
R
Q4.1
R

Figure B-4

B-6

Function Block Diagram for Detecting the Direction of a Conveyor Belt

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Programming Examples

B.3

Timer Instructions

Clock Pulse
Generator

You can use a clock pulse generator or flasher relay when you want to
produce a signal that is repeated periodically. Clock pulse generators are
commonly found in signaling systems that control flashing indicator lamps.
When you use the S7-300, you can implement the clock pulse generator
function by using time-driven program execution in special organization
blocks. The example shown in the following FBD program illustrates the use
of timer functions to generate a clock pulse.
The following example shows how to implement a freewheeling clock pulse
generator by using a timer (pulse duty factor 1:1). The frequency is divided
into the values listed in Table B-5.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

B-7

Programming Examples

Network 1: If the signal state of timer T1 is 0, load the time value 250 ms into T1 and start T1 as an
extended-pulse timer.
T1
SE

&

M0.2

TV

S5T#250MS

Network 2: The state of the timer is saved temporarily in an auxiliary memory bit.
M0.2
=

&

T1

Network 3: If the signal state of timer T1 is 1, jump to jump label N001.


N001
JMP

&

M0.2

Network 4: When the timer T1 expires, the memory word 100 is incremented by 1.

??.?

ADD_I
EN

MW100

IN1

OUT

IN2

ENO

MW100

Network 5: The MOVE instruction allows you to output the different clock frequencies at
outputs Q12.0 through Q13.7.

N001

??.?
MW100

Figure B-5

B-8

MOVE
EN
OUT
IN

QW12

ENO

Function Block Diagram to Generate a Clock Pulse

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Programming Examples

A signal check of timer T1 produces the result of logic operation (RLO, see
Section 2.3) shown in Figure B-6.

1
0
250 ms

Figure B-6

RLO for the Negated Input Parameter AN T1 in the Clock Pulse Timer
Example

As soon as the time runs out, the timer is restarted. Because of this, the signal
check made by AN M0.2 produces signal state 1 only briefly.
Figure B-7 shows the negated (inverted) RLO bit.

1
0
250 ms

Figure B-7

Negated RLO Bit of Timer T1 in the Clock Pulse Timer Example

Every 250 ms the RLO bit is 0. The jump is ignored and the content of
memory word MW100 is incremented by 1.

Achieving a
Specific
Frequency

Table B-5 lists the frequencies that you can achieve from the individual bits
of memory bytes MB101 and MB100. Network 5 in the FBD diagram shown
in Figure B-5 illustrates how the MOVE instruction allows you to see the
different clock frequencies at outputs Q12.0 through Q13.7.
Table B-5

Frequencies for Clock Pulse Timer Example

Bits in
MB101/MB100

Frequency in Hz

Duration

M101.0
M101.1

2.0
1.0

0.5 s (250 ms on/250 ms off)


1 s (0.5 s on/0.5 s off)

M101.2
M101.3

0.5
0.25

2 s (1 s on/1 s off)
4 s (2 s on/2 s off)

M101.4
M101.5

0.125
0.0625

8 s (4 s on/4 s off)
16 s (8 s on/8 s off)

M101.6

0.03125

32 s (16 s on/16 s off)

M101.7

0.015625

64 s (32 s on/32 s off)

M100.0

0.0078125

128 s (64 s on/64 s off)

M100.1

0.0039062

256 s (128 s on/128 s off)

M100.2

0.0019531

512 s (256 s on/256 s off)

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

B-9

Programming Examples

Table B-5

Frequencies for Clock Pulse Timer Example

Bits in
MB101/MB100

Frequency in Hz

Duration

M100.3

0.0009765

1024 s (512 s on/512 s off)

M100.4

0.0004882

2048 s (1024 s on/1024 s off)

M100.5

0.0002441

4096 s (2048 s on/2048 s off)

M100.6

0.000122

8192 s (4096 s on/4096 s off)

M100.7

0.000061

16384 s (8192 s on/8192 s off)

Table B-6 lists the signal states of the bits of memory byte MB101.
Figure B-8 shows the signal state of memory bit M101.1.
Table B-6

Signal States of the Bits of Memory Byte MB101

Scan
Cycle

Time
Value
in ms

250

250

250

250

250

250

250

250

250

250

10

250

11

250

12

250

Signal State of Bits of Memory Byte MB101

T
M101.1

1
0
Time
0

250 ms 0.5 s 0.75 s 1 s

1.25 s 1.5 s

Frequency + 1 + 1 + 1Hz
1 s
T
Figure B-8

B-10

Signal State of Bit 1 of MB101 (M101.1)

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Programming Examples

B.4

Counter and Comparison Instructions

Storage Area with


Counter and
Comparator

Figure B-9 shows a system with two conveyor belts and a temporary storage
area in between them. Conveyor belt 1 delivers packages to the storage area.
A photoelectric barrier at the end of conveyor belt 1 near the storage area
detects how many packages are delivered to the storage area. Conveyor belt 2
transports packages from the temporary storage area to a loading dock where
trucks take the packages away for delivery to customers. A photoelectric
barrier at the end of conveyor belt 2 near the storage area detects how many
packages leave the storage area to go to the loading dock.
A display panel with five lamps indicates the fill level of the temporary
storage area. Figure B-10 shows the FBD program that activates the indicator
lamps on the display panel.

Display panel

Storage area
empty
(Q12.0)

Storage area
not empty
(Q12.1)

I0.0
Packages in

Storage area
50% full
(Q15.2)

Temporary
storage for 100
packages

Conveyor belt 1

(Q15.3)

Storage area
filled to capacity
(Q15.4)

I0.1
Packages out

Conveyor belt 2
Photoelectric barrier 1

Figure B-9

Storage area
90% full

Photoelectric barrier 2

Storage Area with Counter and Comparator

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

B-11

Programming Examples

Network 1: Counter C1 counts up at each signal change from 0 to 1 at input CU and counts down at
each signal change from 0 to 1 at input CD. With a signal change from 0 to 1 at input S, the counter
value is set to the value PV. A signal change from 0 to 1 at input R resets the counter value to 0.
MW200 contains the current counter value of C1. Q12.1 indicates storage area not empty.

C1
S_CUD
I12.0

CU

I12.1

CD

I12.2

CV

MW210

C#10

PV CV_BCD

MW200

I12.3

Q12.1
=

Network 2: Q12.0 indicates storage area not empty.


Q12.0
Q12.1

&

Network 3: If 50 is less than or equal to the counter value (in other words if the current counter value
is greater than or equal to 50), the indicator lamp for storage area 50% full is lit.
CMP
<= I
50

IN1

MW200

IN2

Q15.2
=

Network 4: If the counter value is greater than or equal to 90, the indicator lamp for storage area 90%
full is lit.

MW200

CMP
>= I
IN1
IN2

90

Q15.3
=

Network 5: If the counter value is greater than or equal to 100, the indicator lamp for storage area full
is lit. Use output Q4.4 to interlock conveyor belt 1.
CMP
>= I
MW200

IN1

100

IN2

Figure B-10

B-12

Q15.4
=

Function Block Diagram for Activating Indicator Lamps on a Display Panel

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Programming Examples

B.5

Integer Math Instructions

Solving a Math
Problem

The following sample program shows you how to use three integer math
instructions and the L and T instructions to produce the same result as the
following equation:
MW4 +

(IW0 ) DBW3)
MW0

15

Network 1: Open Data Block DB1


DB1
OPN

Network 2: Input word IW0 is added to shared data word DBW3 (data block must be defined and
opened) and the sum is loaded into memory word MW100. MW100 is then multiplied by 15 and the
answer stored in memory word MW102. MW102 is divided by MW0 with the result stored in MW4. As
long as all results are in the permitted range of each instruction, the ENO passes a signal state of 1 to
the next box.

??.?

ADD_I
EN

IW0

IN1

DBW3

IN2

OUT

MW100
MUL_I
EN

ENO
MW100

IN1

OUT

IN2

ENO

MW102
DIV_I

15

Figure B-11

EN
MW102

IN1

OUT

MW0

IN2

ENO

MW4

Function Block Diagram for Integer Math Instructions

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

B-13

Programming Examples

B.6

Word Logic Instructions

Heating an Oven

The operator of the oven shown in Figure B-12 starts the oven heating by
pushing the start push button. The operator can set the length of time for
heating by using the thumbwheel switches shown in the figure. The value
that the operator sets indicates seconds in binary coded decimal (BCD)
format. Table B-7 lists the components of the heating system and their
corresponding absolute addresses used in the sample program shown in
Figure B-12.
Table B-7

Heating System Components and Corresponding Absolute Addresses


Absolute Address in FBD Program

System Component
Start button

I0.7

Thumbwheel for ones

I1.0 to I1.3

Thumbwheel for tens

I1.4 to I1.7

Thumbwheel for hundreds

I0.0 to I0.3

Start heating

Q4.0

Thumbwheels for setting BCD digits

Oven

Heat
Q4.0

7....

...0

XXXX

7...

0001

1001

IB0

IB1

4
...0

Bits

0001

IW0
Bytes

Start button I0.7

Figure B-12

B-14

Using the Inputs and Outputs for a Time-Limited Heating Process

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Programming Examples

Network 1: If the timer is running, then turn on the heater. If the timer is running, the Return instruction
ends the processing here.

&

T1

Q4.0
=

Network 2: If the timer is running, the Return instruction ends the processing here.
T1

&

RET

Network 3: Mask input bits I0.4 through I0.7 (that is, reset them to 0). These bits of the thumbwheel
inputs are not used. The 16 bits of the thumbwheel inputs are combined with W#16#0FFF according
to the (Word) And Word instruction. The result is loaded into memory word MW1. In order to set the
time base of seconds, the preset value is combined with W#16#2000 according to the (Word) Or
Word instruction, setting bit 13 to 1 and resetting bit 12 to 0.

??.?

WAND_W
EN

IW0

IN1

OUT

IN2

ENO

W#16#FFF

MW1
WOR_W
EN
MW1

IN1

OUT

W#16#2000

IN2

ENO

MW2

Network 4: Start timer T1 as an extended pulse timer if the start push button is pressed, loading as a
preset value memory word MW2 (derived from the logic above).
T1
I0.7

SE

&
MW2

Figure B-13

TV

Function Block Diagram for Heating an Oven

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

B-15

Programming Examples

B-16

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

References
/30/

Getting Started: Working with STEP 7 V5.0

/70/

Manual: S7-300 Programmable Controller,


Hardware and Installation

/71/

Reference Manual: S7-300, M7-300 Programmable Controllers


Module Specifications

/72/

Instruction List: S7-300 Programmable Controller

/100/ Manual: S7-400/M7-400 Programmable Controllers,


Hardware and Installation
/101/ Reference Manual: S7-400/M7-400 Programmable Controllers
Module Specifications
/102/ Instruction List: S7-400 Programmable Controller
/231/ Manual:
Configuring Hardware and Communication Connections, STEP 7 V5.0
/232/ Reference Manual: Statement List (STL) for S7-300 and S7-400
Programming
/233/ Reference Manual: Ladder Logic (LAD)for S7-300and S7-400,
Programming
/234/ Manual: Programming with STEP 7 V5.0
/235/ Reference Manual: System Software for S7-300 and S7-400
System and Standard Functions
/250/ Manual: Structured Control Language (SCL) for S7-300/S7-400,
Programming
/251/ Manual: S7-GRAPH for S7-300 and S7-400,
Programming Sequential Control Systems
/252/ Manual: S7-HiGraph for S7-300 and S7-400,
Programming State Graphs
/253/ Manual: C Programming for S7-300 and S7-400,
Writing C Programs
/254/ Manual: Continuous Function Charts (CFC) for S7 and M7,
Programming Continuous Function Charts
/270/ Manual: S7-PDIAG for S7-300 and S7-400
Configuring Process Diagnostics for LAD, STL, and FBD
/271/ Manual: NETPRO,
Configuring Networks
Function Block Diagram (FBD) for S7-300 and S7-400
C79000-G7076-C566-01

C-1

References

/800/ DOCPRO
Creating Wiring Diagrams (CD only)
/801/ TeleService for S7, C7 and M7
Remote Maintenance for Automation Systems (CD only)
/802/ PLC Simulation for S7-300 and S7-400 (CD only)
/803/ Reference Manual: Standard Software for S7-300 and S7-400,
STEP 7 Standard Functions, Part 2

C-2

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Glossary

A
Absolute
Addressing

In absolute addressing, the memory location of the address to be processed is


given.

Accumulator

Accumulators are registers in the CPU which act as intermediate buffers for
load, transfer, comparison, math, and conversion operations.

Actual Parameter

Actual parameters replace the formal parameters when function blocks (FBs)
and functions (FCs) are called.
Example: The formal parameter Start is replaced by the actual parameter
I3.6.

Address

An address is part of a STEP 7 statement and specifies what the processor


should execute the instruction on. Addresses can be absolute or symbolic.

Address Identifier

An address identifier is the part of the address which contains various data.
The data can include elements such as a value itself (data object) or the size
of a value with which the instruction can, for example, perform a logic
operation. In the instruction statement L IB10 IB is the address identifier
(I indicates the memory input area and B indicates a byte in that area).

Array

An array is a complex data type which consists of data elements of the same
type. These data elements can be elementary or complex.

B
Bit Result (BR)

The bit result is the link between bit and word-oriented processing. This is an
efficient method to allow the binary interpretation of the result of a word
instruction and to include it in a series of logic operations.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Glossary-1

Glossary

C
Call Hierarchy

All blocks must be called first before they can be processed. The sequence
and nesting of these calls within an organized block is called the call
hierarchy.

Condition Codes
CC 1 and CC 0

The CC 1 and CC 0 bits (condition codes) provide information on the


following results or bits:

S Result of a math operation


S Result of a comparison
S Result of a digital operation
S Bits that have been shifted out by a shift or rotate command
Current Path

Characteristic of the Ladder Logic programming language. Current paths


contain contacts and coils. Complex elements (for example, math functions)
can also be inserted into current paths in the form of boxes. Current paths
are connected to power rails.

D
Data Block (DB)

Data blocks (DBs) are areas in a user program which store user data. There
are shared data blocks which can be accessed by all logic blocks and there
are instance data blocks which are associated with a certain function block
(FB) call. In contrast to all other blocks, data blocks do not contain
instructions.

Data, Static

Static data are local data of a function block which are stored in the instance
data block and, therefore, remain intact until the function block is processed
again.

Data Type

A data type defines how the value of a variable or a constant should be used
in the user program.
In SIMATIC STEP 7 two data types are available to the user (IEC 11313):

S Elementary data types


S Complex data types
Data Type,
Complex

Glossary-2

Complex data types are created by the user with the data type declaration.
They do not have their own name and cannot, therefore, be used again. They
can either be arrays or structures. The data types STRING and DATE AND
TIME are classed as complex data types.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Glossary

Data Type,
Elementary

Elementary data types are preset data types according to IEC 11313.
Examples:

S Data type BOOL defines a binary variable (Bit)


S Data type INT defines a 16-bit fixed-point variable.

Declaration

The declaration section is used for the declaration of the local data of a logic
block when programming in the Text Editor.

Direct Addressing

In direct addressing, the address contains the memory location of a value


which is to be used by the instruction.
Example:
The location Q4.0 defines bit 0 in byte 4 of the process-image output table.

F
First Check Bit

First check of the result of logic operation.

Folder

Directory of the user interface of the SIMATIC Manager which can be


opened and can hold other directories or objects.

Formal Parameter

A formal parameter is a placeholder for the actual parameter in logic blocks.


In function blocks (FBs) and functions (FCs) the formal parameters are
declared by the user, in system function blocks (SFBs) and system functions
(SFCs) they are already available. When a block is called, formal parameters
are assigned actual parameters, so the called block works with the current
values.
The formal parameters are classed as local data. They can be input, output, or
in/out parameters.

Function (FC)

According to the International Electrotechnical Commissions IEC 11313


standard, functions are logic blocks without a memory (meaning they do
not have static data). A function allows you to transfer parameters in the user
program, which means they are suitable for programming frequently
recurring, complex functions, such as calculations. Important: As a function
has no memory, you must continue processing the calculated values directly
after the function has been called.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Glossary-3

Glossary

Function Block
(FB)

According to the International Electrotechnical Commissions IEC 11313


standard, function blocks are logic blocks with a memory (meaning they
have static data). A function block allows you to transfer parameters in the
user program, which means they are suitable for programming frequently
recurring, complex functions, such as closed-loop control and operating
mode selection. As a function block has a memory (instance data block), you
can access its parameters (for example, outputs) at any time and at any point
in the user program.

Function Block
Diagram (FBD)

Function Block Diagram (FBD) is one of the programming languages in


STEP 5 and STEP 7. FBD represents logic in the boxes familiar from
Boolean algebra. In addition, complex functions (for example, math
functions) can be represented in direct connection with the logic box.
Programs created with FBD can also be translated into other programming
languages (for example, Ladder Logic).

I
Immediate
Addressing

In immediate addressing, the address contains the value with which the
instruction works.
Example: L.27 means load constant 27 into accumulator.

Input, Incremental

When a block is input incrementally, each line or element is checked


immediately for errors (for example, syntax errors). If an error is detected, it
is marked and must be corrected before programming is completed.
Incremental input is possible in STL (Statement List), LAD (Ladder Logic),
and FBD (Function Block Diagram).

Instance

An instance is the call of a function block. An instance data block is


assigned to each call.

Instance Data
Block (DB)

An instance data block stores the formal parameters and the static data of
function blocks. An instance data block can be assigned to one function
block call or a call hierarchy of function blocks.

Instruction

An instruction is part of a STEP 7 statement; it specifies what the processor


should do.

Glossary-4

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Glossary

K
Keyword

Keywords are used when programming with source files to identify the start
and end of a block and to select sections in the declaration section of blocks,
the start of block comments and the start of titles.

L
Ladder Logic
(LAD)

Ladder Logic is a graphic programming language in STEP 5 and STEP 7. Its


representation is standardized in compliance with DIN 19239 (international
standard IEC 1131-1). Ladder Logic representation corresponds to the
representation of relay ladder logic diagrams. In contrast to Statement List
(STL), LAD has a restricted set of instructions.

Logic Block

Logic blocks are blocks within SIMATIC S7 that contain a part of the
STEP 7 user program. In contrast, data blocks (DBs) only contain data. There
are the following types of logic blocks: organization blocks (OBs), function
blocks (FBs), functions (FCs), system function blocks (SFBs), and system
functions (SFCs). Blocks are stored in the Blocks folder under the S7
Program folder.

Logic String

A logic string is that portion of a user program which begins with an FC bit
that has a signal state of 0 and which ends when an instruction or event resets
the FC bit to 0. When the CPU executes the first instruction in a logic string,
the FC bit is set to 1. Certain instructions such as output instructions (for
example, Set, Reset, or Assign) reset the FC bit to 0. See First Check Bit
above.

M
Master Control
Relay

The Master Control Relay (MCR) is an American relay ladder logic master
switch for energizing and de-energizing power flow (current path). A
de-energized current path corresponds to an instruction sequence that writes a
zero value instead of the calculated value, or, to an instruction sequence that
leaves the existing memory value unchanged.

Memory Area

In SIMATIC S7 a CPU has three memory areas:

S Load memory
S Work memory
S System memory

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Glossary-5

Glossary

Mnemonic
Representation

Mnemonic representation is an abbreviated form for displaying the names of


addresses and programming instructions in the program (for example, I
stands for input). STEP 7 supports the international representation (based
on the English language), and the SIMATIC representation (based on the
German abbreviations of the instruction set and the SIMATIC addressing
conventions).

N
Network

Networks subdivide LAD and FBD blocks into complete current paths and
Statement List (STL) blocks into clear units.

O
Overflow Bit

The status bit OV stands for overflow. An overflow can occur, for example,
after a math operation.

P
Pointer

You can use a pointer to identify the address of a variable. A pointer contains
an identifier instead of a value. If you allocate an actual parameter type, you
provide the memory address. With STEP 7 you can either enter the pointer in
pointer format or simply as an identifier (for example, M 50.0). In the
following example, the pointer format is shown with which data from M 50.0
is accessed:
P#M50.0

Project

A project is a folder for all objects in an automation task, irrespective of the


number of stations, modules, and how they are connected in networks.

R
Reference Data

Glossary-6

Reference data are used to check your S7 program and include the
cross-reference list, the assignment lists, the program structure, the list of
unused addresses, and the list of addresses without symbols.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Glossary

Result of Logic
Operation (RLO)

The result of logic operation (RLO) is the result of the logic string which is
used to process other binary signals. The execution of certain instructions
depends entirely on their preceding RLO.

S
S7 Program

A folder for blocks, source files, and charts for S7 programmable controllers.
The S7 program also includes the symbol table.

Shared Data Block


(DB)

A shared data block is a DB whose address is loaded in the DB address


register when it is opened. It provides storage and data for all logic blocks
(FCs, FBs, or OBs) that are being executed.
In contrast, an instance DB is designed to be used as specific storage and data
for the FB with which it has been associated.

Source File

A source file (text file) is part of a program created either with a graphic or a
text-oriented editor and is compiled into an executable S7 user program or
the machine code for M7.
An S7 source file is stored in the Sources folder under the S7 program
folder.

Statement List
(STL)

Statement List (STL) is a textual representation of the STEP 7 programming


language, similar to machine code. STL is the assembler language of STEP 5
and STEP 7. If you program in STL, the individual statements represent the
actual steps in which the CPU executes the program.

Station

A station is a device which can be connected to one or more subnets; for


example, the programmable controller, programming device, and operator
station.

Status Bit

The status bit stores the value of a bit that is referenced. The status of a bit
instruction that has read access to the memory (A, AN, O, ON, X, XN) is
always the same as the value of the bit that this instruction checks (the bit on
which it performs its logic operation). The status of a bit instruction that has
write access to the memory (S, R, =) is the same as the value of the bit to
which the instruction writes or, if no writing takes place, the same as the
value of the bit that the instruction references. The status bit has no
significance for bit instructions that do not access the memory. Such
instructions set the status bit to 1 (STA=1). The status bit is not checked by
an instruction. It is interpreted during program test (program status) only.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Glossary-7

Glossary

Status Word

The status word is part of the register of the CPU. It contains status
information and error information which is displayed when specific STEP 7
commands are executed. The status bits can be read and written on by the
user, the error bits can only be read.

Stored Overflow
Bit

The status bit OS stands for stored overflow bit of the status word. An
overflow can take place, for example, after a math operation.

Symbol

A symbol is a name which can be defined by the user subject to syntax


guidelines. After it has been declared (for example, as a variable, data type,
jump label, block etc) the symbol can be used for programming and for
operator interface functions. Example: Address: I 5.0, data type: BOOL,
Symbol: momentary contact switch / emergency stop.

Symbol Table

A table in which the symbols of addresses for shared data and blocks are
allocated. Examples: Emergency Stop (symbol) -I 1.7 (address) or
closed-loop control (symbol) - SFB24 (block).

Symbolic
Addressing

In symbolic addressing, the address being processed is designated with a


symbol (as opposed to an absolute address).

System Function
(SFC)

A system function is a function (without a memory) that is integrated in the


S7 operating system and can, if necessary, be called from the STEP 7 user
program like a function (FC).

System Function
Block (SFB)

A system function block (SFB) is a function (with a memory) that is


integrated in the S7 operating system and can, if necessary, be called from
the STEP 7 user program like a function block (FB).

U
User Data Types
(UDTs)

User data types are special data structures which you can create yourself and
use in the entire user program after they have been defined. They can be used
like elementary or complex data types in the variable declaration of logic
blocks (FCs, FBs, OBs) or as a template for creating data blocks with the
same data structure.

User Program

The user program contains all the statements and declarations and all the data
for signal processing which can be used to control a device or a process. It is
part of a programmable module (CPU, FM) and can be structured with
smaller units (blocks).

Glossary-8

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Glossary

User Program
Structure

The user program structure describes the call hierarchy of the blocks within
an S7 program and provides an overview of the blocks used and their
dependency.

V
Variable
Declaration Table

The variable declaration table is used for declaring the local data of a logic
block, when programming takes place in the Incremental Editor.

Variable Table
(VAT)

The variable table is used to collect together the variables that you want to
monitor and modify and set their relevant formats.

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Glossary-9

Glossary

Glossary-10

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Index
Symbols
(Word) AND Double Word (WAND_DW)
instruction, 11-411-5
(Word) AND Word (WAND_W) instruction,
11-311-4
(Word) Exclusive OR Double Word
(WXOR_DW) instruction, 11-811-9
(Word) Exclusive OR Word (WXOR_W)
instruction, 11-711-8
(Word) OR Double Word (WOR_DW)
instruction, 11-611-7
(Word) OR Word (WOR_W) instruction,
11-511-6
#. See Connector
=. See Assign

A
Absolute addressing, practical application, B-4
Accumulators
count value, 6-2
description, 2-9
function, 2-9
ACOS. See Arc Cosine
Add Double Integer (ADD_DI), 7-3
Add Integer (ADD_I), 7-2
Add Real (ADD_R), 8-3
ADD_DI. See Add Double Integer
ADD_I. See Add Integer
ADD_R. See Add Real
Address
box with address, 2-2
box with address and value, 2-2
description, 3-4
element, 3-2
label of a jump instruction, 14-2
types, 3-4
Address identifier, 3-4
Address Negative Edge Detection (NEG), 4-31
Address Positive Edge Detection (POS), 4-30

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Address types, 3-4


Addressing
absolute, B-4
definition, 3-2
direct, 3-2
immediate, 3-2
symbolic, B-3
AND, 4-3
truth table, 2-6
AND-before-OR, 4-5
Arc Cosine (ACOS), 8-138-15
Arc Sine (ASIN), 8-138-14
Arc Tangent (ATAN), 8-13
ASIN. See Arc Sine
Assign Value (MOVE), 10-2
Assignment, 4-9
ATAN. See Arc Tangent
AUF. See Open Data Block, SIMATIC
mnemonic

B
BCD Conversion Error (BCDF), 10-3, 10-6
BCD to Double Integer (BCD_DI), 10-6
BCD to Integer (BCD_I), 10-3
BCD_DI. See BCD to Double Integer
BCD_I. See BCD to Integer
BCDF. See BCD Conversion Error
Beginning of a logic string, 2-10
BIE. See Exception Bit Binary Result,
SIMATIC mnemonic
Binary input
inserting, 4-7
negating, 4-8
Binary Result bit (BR), status bit, 2-13
Binary result bit (BR)
Exception Bit Binary Result (BR), 15-3
Exception Bit Unordered (UO), 15-6
save RLO to BR memory, 4-11
Bit logic, practical applications, B-3B-6

Index-1

Index

Bit logic instruction


Address Negative Edge Detection (NEG),
4-31
Address Positive Edge Detection (POS),
4-30
assignment (=), 4-9
connector, 4-10
down counter (CD), 4-17
Extended Pulse Timer (SE), 4-20
insert binary input, 4-7
negate binary input, 4-8
Negative RLO Edge Detection (N), 4-29
Off-Delay Timer (SF), 4-26
On-Delay Timer (SD), 4-22
Positive RLO Edge Detection, 4-28
Pulse Timer (SP), 4-18
Reset output (R), 4-13
Reset_Set Flip Flop, 4-33
Retentive On-Delay Timer (SS), 4-24
save RLO to BR memory, 4-11
set counter value (SC), 4-14
set output (S), 4-12
Set_Reset Flip Flop, 4-32
up counter (CU), 4-16
Bit logic instructions, 4-2
See also Status bit instructions
practical application, B-3B-6
Bit logic operation
AND, 4-3
AND-before-OR, 4-5
EXCLUSIVE OR logic operation, 4-6
OR, 4-4
OR-before-AND, 4-5
Bits of the status word, changing, 2-9
Blocks
calling, 16-216-3
exiting, 16-7
Boolean (BOOL), range, 3-3
Boolean logic, 2-62-8
Box, instruction as box, 2-2
BR. See Exception Bit Binary Result,
international mnemonic
Byte, range, 3-3

C
CALL. See Call FC/SFC without Parameters

Index-2

Call FC/SFC without Parameters (CALL),


16-216-3
Calling function blocks
as a box, 16-416-6
effects of a call on the status bits, 16-4
supplying parameters, 16-6
Calling functions
as a box, 16-416-6
effects of a call on the status bits, 16-4
supplying parameters, 16-6
with the Call FC/SFC without Parameters
instruction, 16-2
Calling system function blocks
as a box, 16-416-6
effects of the call on the status bits, 16-4
supplying parameters, 16-6
Calling system functions
effects of the call on the status bits, 16-4
supplying parameters, 16-6
with the Call FC/SFC without Parameters
instruction, 16-2
CC1 and CC0. See Condition code bits (CC1
and CC0)
CD. See Down Counter, international mnemonic
CEIL. See Ceiling
Ceiling (CEIL), 10-16
Character (CHAR), range, 3-3
Checking the condition code bits (CC1 and
CC0), 2-11
CMP_D. See Compare Double Integer
CMP_I. See Compare Integer
CMP_R. See Compare Real
Compare Double Integer (CMP_D), 9-3
Compare Integer (CMP_I), 9-2
Compare Real (CMP_R), 9-4
Comparing the result of math instruction with
zero, 15-4
Comparison instructions
Compare Double Integer, 9-3
Compare Integer, 9-2
Compare Real, 9-4
practical applications, B-11B-12
Condition code bits (CC1 and CC0), 2-11
and Exception Bit Unordered, 15-6
effects of math instructions, 7-11, 8-7
relative to the result bit, 15-415-5
status bits, 2-11

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Index

Conditional Jump (JMP), 14-4


Connector, 4-10
Conversion instructions
BCD to Integer (BCD_I), 10-3
BCD to Integer (BDC_I), 10-3
Ceiling (CEIL), 10-16
Double Integer to BCD (DI_BCD), 10-7
Double Integer to Real (DI_R), 10-8
Floor (FLOOR), 10-17
Integer to BCD (I_BCD), 10-4
Integer to Double Integer (I_DI), 10-5
Negate Real Number (NEG_R), 10-13
Ones Complement Double Integer
(INV_DI), 10-10
Ones Complement Integer (INV_I), 10-9
Round to Double Integer (ROUND), 10-14
Truncate Double Integer Part (TRUNC),
10-15
Twos Complement Double Integer
(NEG_DI), 10-12
Twos Complement Integer (NEG_I), 10-11
Count, up/down, 6-3
Count value
format, 6-2
range, 6-2
Counter, instructions with counters
down counter (CD), 4-17
set counter value (SC), 4-14
up counter (CU), 4-16
Counters
address range, 2-4, 2-5
count instructions, Up Counter/Down
Counter (S_CUD), 6-3
count value
format, 6-2
range, 6-2
instructions used with counters, practical
applications, B-11B-12
memory area, 6-2
supported counters, 6-2
Counting
down, 4-17, 6-76-8
up, 4-16, 6-56-6
CPU register, 2-9
count value in a counter, 6-2
status word, 2-9
time value in timer cell, 5-3
CPU registers, function, 2-9
CU. See Up Counter, international mnemonic

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

D
Data block (DB)
instance, 16-6
memory areas, 2-5
Data block instructions, Open Data Block
(OPN), 13-2
Data types, 3-3
Boolean (BOOL), 3-3
BYTE, 3-3
character (CHAR), 3-3
date (D), 3-3
double integer (DINT), 3-3
double word (DWORD), 3-3
integer (INT), 3-3
REAL, 3-3
S5 TIME, 3-3
time (T), 3-3
time of day (TOD), 3-3
WORD, 3-3
DI_BCD. See Double Integer to BCD
DI_R. See Double Integer to Real
DIV_DI. See Divide Double Integer
DIV_I. See Divide Integer
DIV_R. See Divide Real
Divide Double Integer (DIV_DI), 7-9
Divide Integer (DIV_I), 7-8
Divide Real (DIV_R), 8-6
Double integer (DINT), range, 3-3
Double Integer to BCD (DI_BCD), 10-7
Double Integer to Real (DI_R), 10-8
Double word, as data object, 3-5
Double word (DWORD), range, 3-3
Down counter (CD), 4-17
Down Counter (S_CD), 6-76-8

E
Edge detection, 4-28
Element, instruction as, 2-2
Element assignment (=), 4-9
EN. See Enable input (EN)
EN / ENO, meaning, 2-14
Enable input (EN), parameters, 2-3
Enable output (ENO)
See also BR bit
parameters, 2-3
ENO. See Enable output (ENO)

Index-3

Index

Examples, practical application of instructions,


B-2
Exception Bit Binary Result (BR), 15-3
Exception Bit Overflow (OV), 15-7
Exception Bit Overflow Stored (OS),
15-815-10
Exception Bit Unordered (UO), 15-6
and floating-point math, 15-6
Exclusive OR, truth table, 2-8
Extended Pulse S5 Timer (S_PEXT), 5-75-8
Extended Pulse Timer (SE), 4-20

F
FBD, explanation, 1-1
First Check (FC), 2-102-14
result, 2-10
status bit, 2-10
Flip flop, 4-32
Reset_Set, 4-33
Set_Reset, 4-32
Floating-point math
and exception bit unordered (UO), 15-6
Subtract Double Integer (SUB_DI), 7-5
Floating-point math instructions
Add Real (ADD_R), 8-3
Divide Real (DIV_R), 8-6
Multiply Real (MUL_R), 8-5
Subtract Real (SUB_R), 8-4
Floating-point numbers
Compare Real, 9-4
data type for. See Real number, data type

Index-4

Floating-point math, 8-2


Arc Cosine (ACOS), 8-138-15
Arc Sine (ASIN), 8-138-14
Arc Tangent (ATAN), 8-13
effects on the bits of the status word, 8-7
result within the valid range, 8-7
Floor (FLOOR), 10-17
Format
count value, 6-2
time value, 5-2
Function Block Diagram, 1-1
Function blocks (FBs)
calling FBs as a box, 16-416-6
supplying parameters, 16-6
Functions (FCs)
calling FCs as a box, 16-416-6
calling FCs with the Call FC/SFC without
Parameters instruction, 16-2
supplying parameters, 16-6

G
German SIMATIC names and SIMATIC
mnemonics, alphabetical list, A-10

I
I/O external inputs and outputs, address range,
2-4, 2-5
I_BCD. See Integer to BCD
I_DI. See Integer to Double Integer

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Index

Input
inserting, 4-7
negating, 4-8
Input parameter, as part of a box, 2-3
Instance data block (DI), 16-6
Instruction
as box with address, 2-2
as box with address and value, 2-2
as box with parameters, 2-3
as element, 2-2

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Instructions
alphabetical list, A-10A-24
German SIMATIC names and SIMATIC
mnemonics, A-10
international names and international
mnemonics, A-2
international names and SIMATIC
equivalents, A-6
SIMATIC names and international
equivalents, A-14
SIMATIC names with SIMATIC
mnemonics and international
mnemonics, A-17
bit logic instructions, 4-2
practical application, B-3
comparison, practical applications,
B-11B-12
counter, practical applications, B-11B-12
dependent on Master Control Relay (MCR),
16-8
evaluating the condition code bits (CC1 and
CC0), 7-11, 8-7
evaluating the OS bit, 7-11, 8-7
evaluating the OV bit, 7-11, 8-7
floating-point math, 8-7
effects on the bits of the status word, 8-7
result within the valid range, 8-7
integer math instructions, 7-11
effects on the bits of the status word,
7-11
valid range for results, 7-11
jump instructions, 14-2
math instructions with integers, practical
applications, B-13
practical application, B-2
result bits, 15-415-5
rotate instructions, 12-1012-12
shift instructions, 12-212-10
status bit instructions, 15-215-10
timer, practical applications, B-7B-10
word logic, practical applications,
B-14B-15
word logic instructions, practical
applications, B-14B-16
Integer (INT), range, 3-3

Index-5

Index

Integer math instructions


Add Double Integer (ADD_DI), 7-3
Add Integer (ADD_I), 7-2
Divide Double Integer (DIV_DI), 7-9
Divide Integer (DIV_I), 7-8
effects on the bits of the status word, 7-11
Multiply Double Integer (MUL_DI), 7-7
Multiply Integer (MUL_I), 7-6
Return Fraction Double Integer (MOD_DI),
7-10
Subtract Integer (SUB_I), 7-4
valid range for results, 7-11
Integer to BCD (I_BCD), 10-4
Integer to Double Integer (I_DI), 10-5
Integers, comparing, 9-2, 9-3
International names and German SIMATIC
equivalents, alphabetical list, A-6
International names with international
mnemonics, alphabetical list, A-2
International names with SIMATIC mnemonics
and international mnemonics, alphabetical
list, A-17
INV_DI. See Ones Complement Double Integer
INV_I. See Ones Complement Integer

J
JMP. See Conditional Jump; Unconditional
Jump
Jump instruction, jump label as address, 14-2
Jump instructions, 14-2
conditional Jump (JMP), 14-4
unconditional jump, 14-3
Jump label, as address of the jump instruction,
14-2

L
Languages, switching between LAD, FBD, and
STL, 1-1
Loading a count value
format, 6-2
range, 3-3
Loading a time value
format, 5-2
range, 3-3
Local data, memory area, address range, 2-4,
2-5

Index-6

M
Master Control Relay (MCR)
effects on the instructions Set Output (S) and
Reset Output (R), 16-8
important notes, 16-9
Master Control Relay (MCR) instructions,
16-816-9
Master Control Relay Activate (MCRA),
16-10
Master Control Relay Deactivate (MCRD),
16-10
Master Control Relay Off (MCR>), 16-13
Master Control Relay On (MCR<),
16-1316-16
nesting, 16-14
Master Control Relay Activate (MCRA),
16-1016-16
Master Control Relay Deactivate (MCRD),
16-1016-16
Master Control Relay Off (MCR), 16-1316-16
Master Control Relay On (MCR<), 16-1316-16
Math instructions, practical applications with
integers, B-13
MCR Functions, important notes, 16-9
MCR<. See Master Control Relay On
MCR>. See Master Control Relay Off
MCRA. See Master Control Relay Activate
MCRD. See Master Control Relay Deactivate
Memory area, process input image, 2-4
Memory areas, 2-3
bit memory, 2-4
counters, 2-4
data block, 2-4
I/Os (external inputs and outputs), 2-4
inputs and outputs, 2-4
local data, 2-4
process input image, 2-4
process output image, 2-4
timers, 2-4
MOD_DI. See Return Fraction Double Integer
MOVE. See Assign Value
Move instructions, Assign Value, 10-2
MUL_DI. See Multiply Double Integer
MUL_I. See Multiply Integer
MUL_R. See Multiply Real
Multiple instances, calling, 16-6
Multiply Double Integer (MUL_DI), 7-7
Multiply Integer (MUL_I), 7-6

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Index

Multiply Real (MUL_R), 8-5

N
N. See Negative RLO Edge Detection
NEG. See Address Negative Edge Detection
NEG_DI. See Twos Complement Double
Integer
NEG_I. See Twos Complement Integer
NEG_R. See Negate Real Number
Negate Real Number (NEG_R), 10-13
Negative RLO Edge Detection (N), 4-29
Nesting, Master Control Relay (MCR), 16-14

O
Off-Delay S5 Timer (S_OFFDT), 5-135-14
On-Delay S5 Timer (S_ODT), 5-95-10
Ones Complement Double Integer (INV_DI),
10-10
Ones Complement Integer (INV_I), 10-9
Open Data Block (OPN), instruction, 13-2
OPN. See Open Data Block, international
mnemonic
OR, 4-4
truth table, 2-7
OR status bit, 2-11
OR-before-AND, 4-5
OS. See Exception Bit Overflow Stored
OS bit (stored overflow)
Exception Bit Overflow Stored (OS),
15-815-10
status bit, 2-11
Output parameter, as part of the structure of a
box, 2-3
OV. See Exception Bit Overflow
OV bit (overflow)
Exception Bit Overflow (OV), 15-7
status bit, 2-11
Overflow (OV), effects of math instructions,
7-11, 8-7

P
P. See Positive RLO Edge Detection
Parameter
Enable input (EN), 2-3
Enable output (ENO), 2-3
inputs and outputs as part of a box, 2-3

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Pointer, 3-5
POS. See Address Positive Edge Detection
Positive RLO edge detection (P), 4-28
Process input image, memory area, 2-4
address range, 2-5
Process output image, memory area, 2-4
address range, 2-5
Program control instructions
Call FC/SFC without Parameters (CALL),
16-216-3
Master Control Relay Activate (MCRA),
16-1016-12
Master Control Relay Deactivate (MCRD),
16-10
Master Control Relay Off (MCR>),
16-1316-16
Master Control Relay On (MCR<),
16-1316-16
Return (RET), 16-7
Programming, practical applications, B-2
Pulse S5 Timer (S_PULSE), 5-55-6
Pulse Timer (SP), 4-18

R
R. See Reset output
Real number
data type, 3-3
range, 3-3
Register, CPU, 2-92-14
Reset output (R), 4-13
Resolution. See Time base for S5 TIME
Result bits
checking the condition code bits (CC1 and
CC0), 2-11
instructions, 15-415-5
Result of logic operation, description, 2-6
Result of logic operation (RLO)
status bit, 2-6
status word bit, 2-102-11
RET. See Return instruction
Retentive On-Delay Timer (S_ODTS),
5-115-12
Retentive on-delay timer (SS), 4-24
Return Fraction Double Integer (MOD_DI),
7-10
Return instruction (RET), 16-7
RLO. See Result of Logic Operation
ROL_DW. See Rotate Left Double Word
ROR_DW. See Rotate Right Double Word

Index-7

Index

Rotate instructions, 12-1012-12


Rotate Left Double Word (ROL_DW),
12-1012-12
Rotate Right Double Word (ROR_DW),
12-1112-12
Rotate Left Double Word (ROL_DW),
12-1012-12
Rotate Right Double Word (ROR_DW),
12-1112-12
ROUND. See Round to Double Integer
Round to Double Integer (ROUND), 10-14
RS. See Reset_Set Flip Flop

S
S. See Set output
S_AVERZ. See Off-Delay S5 Timer, SIMATIC
mnemonic
S_CD. See Down Counter, international
mnemonic
S_CU. See Up Counter, international mnemonic
S_CUD. See Up Counter/Down Counter,
international mnemonic
S_EVERZ. See On-Delay S5 Timer, SIMATIC
mnemonic
S_IMPULS, 5-5
S_ODT. See On-Delay S5 Timer, international
mnemonic
S_ODTS. See Retentive On-Delay S5 Timer,
international mnemonic
S_OFFDT. See Off-Delay S5 Timer,
international mnemonic
S_PEXT. See Extended Pulse S5 Timer,
international mnemonic
S_PULSE. See Pulse S5 Timer instruction
S_SEVERZ. See Retentive On-Delay S5 Timer,
SIMATIC mnemonic
S_VIMP. See Extended Pulse S5 Timer,
SIMATIC mnemonic
S5 TIME
range, 3-3
time base, 5-2
time value, 5-2
SA. See Off-Delay Timer, SIMATIC mnemonic
SAVE. See Save RLO to BR Memory
Save RLO to BR memory (SAVE), 4-11

Index-8

SC. See Set counter value, international


mnemonic
SD. See On-Delay Timer, international
mnemonic
SE. See Extended Pulse Timer, international
mnemonic; On-Delay Timer, SIMATIC
mnemonic
Set counter value, 4-14
Set counter value (SC), 4-14
Set output (S), 4-12
SF, 4-26
Shift instructions, 12-212-9
Shift Left Double Word (SHL_DW),
12-412-9
Shift Left Word (SHL_W), 12-212-9
Shift Right Double Integer (SHR_DI), 12-9
Shift Right Double Word (SHR_DW),
12-612-9
Shift Right Integer (SHR_I), 12-712-9
Shift Right Word (SHR_W), 12-512-9
Shift Left Double Word (SHL_DW), 12-412-9
Shift Left Word (SHL_W), 12-212-9
Shift Right Double Integer (SHR_DI), 12-9
Shift Right Double Word (SHR_DW),
12-612-9
Shift Right Integer (SHR_I), 12-712-9
Shift Right Word (SHR_W), 12-512-9
SHL_DW. See Shift Left Double Word
SHL_W. See Shift Left Word
SHR_DI. See Shift Right Double Integer
SHR_DW. See Shift Right Double Word
SHR_I. See Shift Right Integer
SHR_W. See Shift Right Word
SI. See Pulse Timer, SIMATIC mnemonic
SIMATIC names and international equivalents,
alphabetical list, A-14
SP. See Pulse Timer, international mnemonic
SR. See Set_Reset Flip Flop
SS. See Retentive On-Delay Timer
STA. See Status bit
Status bit (STA), 2-11

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Index

Status bit instructions, 15-2


Exception Bit Binary Result (BR), 15-3
Exception Bit Overflow (OV), 15-7
Exception Bit Overflow Stored (OS), 15-8
Exception Bit Unordered (UO), 15-6
result bits, 15-415-5
Status word
binary result bit (BR bit), 15-3
Binary Result bit (BR), 2-13
bits affected by math instructions, 7-11, 8-7
changing the bits, 2-9
condition code bits (CC1 and CC0), 2-11
and Exception Bit Unordered (UO), 15-6
relative to the result bit instructions,
15-415-5
description, 2-9
effects of calling an FB, FC, SFB or SFC on
the status bits, 16-4
EN = 0, 2-14
EN = 1, 2-14
Exception Bit Overflow, 15-7
Exception Bit Overflow Stored, 15-815-10
First Check (FC), 2-10
OR bit, 2-11
OS bit (stored overflow), 2-11
OV bit (overflow), 2-11
result of logic operation (RLO) bit,
2-102-11
specifying the invalid range for integer math
instructions, 7-11
specifying the valid range for integer math
instructions, 7-11
Status bit (STA), 2-11
status bit instructions, 15-215-10
structure, 2-9, 15-2
Stored overflow (OS), effects of math
instructions, 7-11, 8-7
String of logic operations
definition, 2-10
end, 2-10
SUB_DI. See Subtract Double Integer
SUB_I. See Subtract Integer
SUB_R. See Subtract Real
Subtract Double Integer (SUB_DI), 7-5
Subtract Integer (SUB_I), 7-4
Subtract Real (SUB_R), 8-4
SV. See Extended Pulse Timer, SIMATIC
mnemonic
Symbolic addressing, practical example, B-3
System function blocks (SFBs)
calling SFBs as a box, 16-416-6
supplying parameters, 16-6

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

System functions (SFCs)


calling SFCs as a box, 16-416-6
supplying parameters, 16-6
SZ. See Set counter value, SIMATIC mnemonic

T
Time base, resolution, 5-3
Time base for S5 TIME, 5-25-14
Time of day (TOD), range, 3-3
Time resolution. See Time base for S5 TIME
Time value, 5-3
format in timer cell, 5-3
range, 5-35-14
reading, 5-3
syntax, 5-2
Timer, instructions with timers
Extended Pulse Timer (SE), 4-20
Off-Delay Timer (SF), 4-26
On-Delay Timer (SD), 4-22
Pulse Timer (SP), 4-18
Retentive On-Delay Timer (SS), 4-24
Timers
address range, 2-5
components, 5-25-3
Extended Pulse S5 Timer (S_PEXT),
5-75-8
instructions used with timers, practical
applications, B-7B-10
memory area, 5-2
numbers supported, 5-2
overview, 5-4
Pulse S5 Timer (S_PULSE), 5-55-6
reading the time and the time base, 5-3
time value, 5-2
range, 5-25-14
syntax, 5-2
timer instructions
Off-Delay S5 Timer (S_OFFDT), 5-13
On-Delay S5 Timer (S_ODT), 5-9
Retentive On-Delay S5 Timer
(S_ODTS), 5-11
TRUNC. See Truncate Double Integer Part
Truncate Double Integer Part (TRUNC), 10-15
Truth table
AND, 2-6
exclusive OR, 2-8
OR, 2-7
Twos Complement Double Integer (NEG_DI),
10-12
Twos Complement Integer (NEG_I), 10-11

Index-9

Index

U
Unconditional Jump (JMP), 14-3
UO. See Exception Bit Unordered
Up Counter, (S_CU), 6-56-6
Up counter, CU, 4-16
Up Counter/Down Counter (S_CUD), 6-3

WXOR_DW. See (Word) Exclusive OR Double


Word instruction
WXOR_W. See (Word) Exclusive OR Word
instruction

X
XOR, 4-6

W
WAND_DW. See (Word) AND Double Word
instruction
WAND_W. See (Word) AND Word instruction
WOR_DW. See (Word) OR Double Word
instruction
WOR_W. See (Word) OR Word instruction
WORD, range, 3-3
Word, as data object, 3-5
Word logic instructions
(Word) AND Double Word (WAND_DW),
11-411-5
(Word) AND Word (WAND_W), 11-311-4
(Word) Exclusive OR Double Word
(WXOR_DW), 11-811-9
(Word) Exclusive OR Word (WXOR_W),
11-711-8
(Word) OR Double Word (WOR_DW),
11-611-7
(Word) OR Word (WOR_W), 11-511-6
practical applications, B-14B-16

Index-10

Z
Z_RUECK. See Down Counter, SIMATIC
mnemonic
Z_VORW. See Up Counter, SIMATIC
mnemonic
ZAEHLER. See Up Counter/Down Counter,
SIMATIC mnemonic
ZR. See Down Counter, SIMATIC mnemonic
ZV. See Up Counter, SIMATIC mnemonic

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Siemens AG
A&D AS E81
Oestliche Rheinbrueckenstr. 50
D-76181 Karlsruhe
Federal Republic of Germany

From:
Your Name: _ _ _ _
Your Title: _ _ _ _
Company Name:
_
Street:
_
City, Zip Code_
Country:
_
Phone:
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

Please check any industry that applies to you:


r

Automotive

Pharmaceutical

Chemical

Plastic

Electrical Machinery

Pulp and Paper

Food

Textiles

Instrument and Control

Transportation

Nonelectrical Machinery

Other _ _ _ _ _ _ _ _ _ _ _

Petrochemical

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

Remarks Form
Your comments and recommendations will help us to improve the quality and usefulness
of our publications. Please take the first available opportunity to fill out this questionnaire
and return it to Siemens.

Please give each of the following questions your own personal mark within the range
from 1 (very good) to 5 (poor).
1.

Do the contents meet your requirements?

2.

Is the information you need easy to find?

3.

Is the text easy to understand?

4.

Does the level of technical detail meet your requirements?

5.

Please rate the quality of the graphics/tables:

Additional comments:
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

Function Block Diagram (FBD) for S7-300 and S7-400


C79000-G7076-C566-01

You might also like