EQUIPMENT SCHEDULE

A. AIR COMPRESSOR
1. Capacity = 411 SCFM
2. Discharge Pressure = 132 psig
3. Motor Horsepower = 100 hp
4. Cooling water = 19 gpm
5. Volts/Phase/Hertz = 440 / 3 / 60
6. Reference: ATLAS COPCO

B. AIR RECEIVER
1. Capacity = 1500 cfm
2. Design Pressure = 160 psig
3. Type = Vertical
4. Diameter = 1000 mm
5. Height = 2384 mm (with support excluding safety valve)
6. Reference: ATLAS COPCO

C. AIR DRYER
1. Type = Refrigerated
2. Capacity = 377 cfm
3. Dewpoint = 38 F
4. Inlet Air Pressure = 100 psig
5. Inlet Air Temperature = 120 F
6. Ambient Temperature = 110 F
7. Power = 3.6 kw
8. Volts/Phase/Hertz = 220 / 3 / 60
9. Reference: DELTECH

D. LIQUID SEPARATOR
1. Liquid removal: 99+% of water
2. Max. liquid loading: 30,000 ppm w/w
3. Solid particle removal: 10 microns
4. Oil carry over: N/A
5. Pressure drop: Wet: 0.8 psi
6. Modular type housing
7. Connection size: 2 NPTF
8. Max. working pressure = 250 psig
9. Max. inlet temperature = 150 F
10. Reference: KAESER



E. FILTERED SEPARATOR
1. Liquid removal: 99+% of water
2. Max. liquid loading: 25,000 ppm w/w
3. Solid particle removal: 3 microns
4. Oil carry over: 5 ppm w/w
5. Pressure drop: Dry 1psi; Wet 1.5 psi
6. Modular type housing
7. Connection size: 2 NPTF
8. Max. working pressure = 250 psig
9. Max. inlet temperature = 150 F
10. Reference: KAESER

F. PARTICULATE FILTER
1. Liquid removal: 100% of water
2. Max. liquid loading: 2,000 ppm w/w
3. Solid particle removal: 1 micron
4. Oil carry over: 1 ppm w/w
5. Pressure drop: Dry 1psi; Wet 2 psi
6. Modular type housing
7. Connection size: 2 NPTF
8. Max. working pressure = 250 psig
9. Max. inlet temperature = 150 F
10. Reference: KAESER