B. E. (ELECTRONICS)
PROGRAMMABLE
LOGIC
CONTROLLER
Prepared by:
Guided by:
B V M ENGINEERING COLLEGE
SARDAR PATEL UNIVERSITY
VALLABH VIDYANAGAR 388120
CERTIFICATE
Date:
Signature of Professor:
Head of Department
AKNOWLEGEMENTS
Chapter 1
INTRODUCTION
Simplification of engineering and precise control of manufacturing
process can result in significant cost savings. The most cost-effective way, which
can pay big dividends in the long run, is flexible automation; a planned approach
towards integrated control systems. It requires a conscious effort on the part of
plant managers to identify areas where automation can result in better
deployment/utilization of human resources and savings in man-hours, down time.
Automation need not be high ended and too sophisticated; it is the phased, stepby-step effort to automate, employing control systems tailored to ones specific
requirements that achieves the most attractive results. That is where Industrial
electronics has been a breakthrough in the field of automation and control
techniques.
ROLE OF ELECTRONICS IN AUTOMATION
A constant demand for better and more efficient manufacturing and
process machinery has led to the requirement for higher quality and reliability in
control techniques. With the availability of intelligent, compact solid state
electronic devices, it has been possible to provide control systems that can reduce
maintenance, down time and improve productivity to a great extend. By installing
efficient and user friendly industrial electronics systems for manufacturing
machinery or processors, one can obtain a precise, reliable and prolific means for
generating quality products.
Considering the varied demand and increasing competition, one has to
provide for flexible manufacturing process. One of the latest techniques in solid
state controls that offers flexible and efficient operation to the user is
PROGRAMMABLE CONTROLLERS.
The basic idea behind these
programmable controllers was to provide means to eliminate high cost associated
with inflexible, conventional relay controlled systems. Programmable controllers
offer a system with computer flexibility:
1. Suited to withstand the industrial environment
2. Has simplicity of operation
3. Maintenance by plant technicians and
4. Reduce machine down time and provide expandability for future.
DEFINATION OF PLC
7.
Chapter 2
PLC ARCHITECTURE
PLCs contain three basic sections:
1. Central processing unit (CPU).
2. Memory: EPROM, RAM, and so on.
3. Input/output section for communication with peripherals (ADC, DAC).
A PLC is basically a black box with a number of inputs from, and a number of
outputs to, the outside world. It can make decisions, store data, do timing cycles, do
simple arithmetic, convert codes, and so on. The basic difference between this black
box and a hardware logic system using IC chips or a relay controlled system, is that
specific coded messages are stored in areas called program memory, which are
PROM or ROM and RAM chips. It is, however, much easier to change a program
when a different process is required than to rewire the control system. For example, it
may take electricians a couple of weeks to require a pipe mill, whereas a programmer
will spend only a fraction of this time to reprogram a PLC since no wires will have to
be changed. In addition, various recipes can be stored in memory and accessed when
required, making the program extremely flexible.
The system operates through interaction with the processor and program memory.
When the power to the system is turned on, the processor reads the first instruction
stored in memory and acts on this instruction. When completed, it goes back to the
memory for the next instruction, and so on until task is complete. This operation is
called the fetch-execute cycle. The processor communicates with the outside world
via input and output modules.
THE PARTS OF A PROGRAMMABLE CONTROLLER
Programmable logic controllers (PLC) can be considered to have three parts:
1. Input/output Section
The I/O section contains input modules and output modules. Functionally, the input
modules are equivalent to the signal converters (i.e. Analog to Digital or high power to
low power). All modern PLC input modules use optical devices to accomplish electrically
isolated coupling between the input circuit and the processor electronics.
Each input device is wired to a particular input terminal on the I/O section. Thus if the
switch is closed, 5v dc appears on input terminal, converts this dc voltage to a digital 1
and sends it to the processor via programmable peripheral interface (PPI). Conversely, if
the switch is open, no dc voltage appears on input terminal. Input section will respond to
this condition by sending a digital 0 to the processor. The other input terminals behave
identically.
2. The Processor
The processor of a PLC holds and executes the user program. In order to carry out
this job, the processor must store the most up-to-date input and output conditions.
(a) Input image table:
The input conditions are stored in the input image table, which is a portion of the
processors memory. That is, every single input module in the I/O section has assigned to
it a particular location within the input image table. That particular location is dedicated
solely to the task of keeping track of the latest condition of its input terminal. As
mentioned in earlier section, if the input terminal has 5v dc power fed to it by its input
device, the location within the input image table contains a binary 1(HI); if the input
terminal has no 5v dc power fed to it, the location contains a binary 0(LO).
The processor needs to know the latest input conditions because the user program
instructions are contingent upon those conditions. In other words, an individual
instruction may have one outcome if a particular input is HI and a different outcome if
that input is LO.
(b) Output image table:
The output conditions are stored in the output image table, which is another portion of
the processors memory. The output image table bears the same relation to the output
interface of the I/O section that while terminals are analog inputs. You can directly
connect any analog input to the processor via these terminals. Analog signal from these
terminals is first converted to digital value via programmable peripheral interface (PPI).
The I/O sections output modules are functionally the same as the output amplifiers.
They receive a low power digital signal from the processor and convert it into a high
power signal capable of driving an industrial load. A modern PLC output module is
optically isolated, and uses a triac, power transistor or relay as the series connected load
controlling device. Terminal 1 to 8 are these type of O/P terminals whereas terminal D/A
is Analog output terminal from processor. Each output device is wired to a particular
output terminal on the I/O interface. Thus, for example, if output module 1 receives a
digital 1 by applying 5v dc to output terminal 1, thereby illuminating LED is
extinguished.
Besides 5v dc (TTL devices), I/O module are also for interfacing to other industrial
levels, including 12v dc.
The input image table bears to the input modules. That is, every single output module
has assigned to it a particular memory location is dedicated solely to the task of keeping
track of the latest condition of its output module.
Of course, the output situation differs from the input situation with regard to the direction
of information flow is from the output image table to the output modules, while in the
input situation the information flow is from the input modules to the input image table.
The locations within the input and output image tables are identified by addresses, which
refers to unique address of each terminal.
(c)
The subsection of the processor that actually performs the program execution will
be called the central processing unit (CPU) with reference to input and output image table
CPU executes the user program and continuously updates the output image table.
The output image table has a dual nature; its first function is to receive immediate
information from the CPU and pass if on to the output modules of the I/O section; but
secondly, it also must be capable of passing output information backward to the CPU,
when the user program instruction that the CPU is working on calls for an item of output
information. The input image table does not have its dual nature. Its single mission is to
acquire information from the input modules and pass that information forward to the
CPU when the instruction that the CPU is working on calls for an item of input
information.
(d) User program memory:
A particular portion of the processors memory is used for storing the user program
instructions. We will use the name user program memory to refer to this processor
subsection.
Before a PLC can begin controlling an industrial system, a human user must enter the
coded instructions that make up the user program. This procedure called programming
the PLC.
As the user enters instructions, they are automatically stored at sequential locations
within the user program memory. This sequential placement of program instructions is
self-regulated by the PLC, with no discretion needed by the human user.
The total number of instructions in the user program can range from a half dozen or
so, for controlling a simple machine, to several thousand, for controlling a complex
machine or process.
After the programming procedure is complete, the human user manually switches the
PLC out to PROGRAM mode into RUN mode, which causes the CPU to start executing
the program from beginning to end repeatedly.
(e) The complete scan cycle:
As long as the PLC is left in the RUN mode, the processor executes the user program
over and over again. Figure depicts the entire repetitive series of events. Beginning at
the top of the circle representing the scan cycle, the first operation is the input scan.
During the input scan, the current status of every input module is stored in the input
image table, bringing it up to date.
Following the input scan, the processor enters its user program execution. Sometimes
called program scan. The program executes with reference to input and output image
tables and updates output image table.
Throughout the user program execution, the processor continuously keeps its output
image table up to date, as stated earlier. However, the output modules themselves are not
kept continuously up to date. Instead, the entire output image table is transferred to the
output module during the output scan following the program execution.
(f) Data Memory:
A PLC is a computer, after all. Therefore, it can perform arithmetic, numeric
comparisons, counting, etc. Naturally the numbers and data can change from one scan
cycle to the next. Therefore the PLC must have a section of its memory set aside for
keeping track of variable data, or numbers, that are involved with the user program. This
section of memory we will call data memory.
When the CPU is executing an instruction for which a certain data value must be
known, that data value is brought in from data memory. When the CPU executes an
instruction that provides a numerical result, that result is put out into data memory. Thus,
CPU can read from or write to the data memory. Understand that this relationship is
different from the relationship between the CPU and the user program memory. When
the user program is executing, the CPU can only reads from the user program memory,
never write to it.
(g) Operating System of PLC:
The function of the operating system is to present the user with the equivalent of an
extended machine or virtual machine that is easier to program than the underlying
hardware.
Due to this operating system, PLC is very easy to program. It can be programmed
using electrical schemes with familiar relay symbols so that a plant electrician can easily
access the PLC. Even though he does not know the assembly language or even if he may
not have any familiarity with computers and electronics, he will be able to program the
PLC.
The function of PLC Operating system is:
1. Loads the user program from programming device to program memory.
2. To read status of input devices.
3. To execute user program.
4. To form and update input image table.
5. As per the status of output image table controls the output devices.
Chapter 3
SYSTEM OVERVIEW:
This low cost PLC system was designed to satisfy hunger of Automation of Indian
Industry and also helps beginners as well as development engineers to get into
Automation field.
System consist of following main sections:
(1) The CPU:
The CPU uses the 89c51 microcontroller, which operates at 11.0592Mhz. It has
8k RAM, which can be used as data memory, 8k RAM that can be used as program
memory as well as data memory, 8k EEPROM that can be used as program memory.
(2) Input/output Section:
This part of system is on separate board connected to processor via cable. It allows
the processor to communicate with the outside world. It is also called Data Acquisition
System (DAS).
This part of system provides 4 digital inputs consisting of 2 dc and 2 ac, 4 digital
outputs consisting of 2 dc and 2 ac each. It also provides 8 analog inputs with following
ranges:
1. 5v to +5v (one channel).
2. 0v to 10v (one channel).
3. 4mA to 20mA (one channel).
4. 0v to 5v (five channel).
(3) Timer/Counter:
The system has 2 timers or 2 counters or 1 timer and 1 counter. The timer provides
maximum of 255sec delay and the counter provides maximum of 255 counts.
Chapter 4
HARDWARE CONFIGURATION
1. Microcontroller:
Here we are using 89c51 microcontroller, which has one full duplex serial data
receiver/transmitter, which is used for serial communication having interface with
ICL232 chip.
It has also two 16 bits timer/counter namely T0 and T1 which are used for timer and
counter applications. Timer T1 is used to set baud rate for serial communication in
program mode.
2. Memory:
The system consist of four types of memory:
a. 4k of EEPROM which is internal to 89c51 microcontroller. This memory is
used to store the operating system. It has address from 0000h to 0fffh. It can
only be accessed when the external access pin of controller is connected to
+5v. In our system this pin is permanently connected with +5v so external
program memory is accessed only when the address is beyond 0fffh.
b. 8k of RAM which is used as data memory. The CPU can read data from and
write data into this memory. This memory has address from 0000h to 1fffh.
c. 8k of RAM which is used as data memory as well as program memory. The
CPU can write program codes in and read program codes from this memory.
This memory has address from 2000h to 3fffh.
d. 8k of EEPROM, which is used as, program memory. The subroutines, which
are helpful in executing the main program, are stored here. This memory has
location from 4000h to 5fffh.
3. Programmable Peripheral Interface(PPI):
Here two 8255 are used as PPI. One is used to control the ADC and DAC, while
other is used for Input/output interface. The addresses for the 8255 used to control ADC
and DAC are:
Port A: 6000h
Port B: 6001h
Port C: 6002h
Control Word: 6003h
The addresses for the 8255 used for Input/output interfaces are:
Port A: 8000h
Port B: 8001h
Port C: 8002h
Control Word: 8003h
4. Analog to Digital Converter(ADC):
Here ADC0809 is used as an 8 bit ADC. 8255 whose addresses are 6xxxh is used to
give control signals to this ADC. The port pins of 8255 are connected with the control
pins of ADC as shown below:
8255 Pins
ADC Pins
PB0
ADD0 (A)
PB1
ADD1 (B)
PB2
ADD2 (C)
PB3
PB4
OE (Output Enable)
PC7
Note: Here PB4 is connected to OE pin of ADC through NOT Gate. So we have to give
negative pulse by pin PB4 to pin OE to give Output Enable.
This ADC is used to convert the real world analog data into digital form.
8. Digital Input:
DC Input:
We have two digital DC inputs with following specifications:
1. 0v to 5v LOW
2. 20v to 25v- HIGH
3. Optocoupler Isolation.
AC Input:
We have two digital AC inputs with following specifications:
1. 0v to 10v-LOW
2. 20v to 25v-HIGH
3. 47hz to 63hz frequency.
4. Optocoupler Isolation.
9. Digital Outputs:
DC outputs:
We here have two DC outputs with following specification:
1. 0v t0 3v-0v
2. 3.5v to 5v-24v
3. 0.5amp output current.
4. Optocoupler Isolation.
AC outputs:
We have two relays as AC outputs with following specification:
1. 0v to 3v- relay OFF
2. 3.5v to 5v- relay ON
3. Optocoupler Isolation.
4. Relay with12v, 4ohm.
Chapter 5
ADDRESSES
AC Output:
Output
Address
00
01
20
21
Output
Address
02
03
22
23
Input
Address
In 1(Normally Open)
04
In 2(Normally Open)
05
In 1(Normally Close)
24
In 2(Normally Close)
25
DC Output:
AC Input:
DC Input:
Input
Address
In 1(Normally Open)
06
In 2(Normally Open)
07
In 1(Normally Close)
26
In 2(Normally close)
27
Input
Address
In 1(Normally Open)
08
In 2(Normally Open)
09
In 3(Normally Open)
0a
In 4(Normally Open)
0b
In 5(Normally Open)
0c
In 6(Normally Open)
0d
In 7(Normally Open)
0e
In 8(Normally Open)
0f
In 1(Normally Close)
28
In 2(Normally Close)
29
In 3(Normally Close)
2a
In 4(Normally Close)
2b
In 5(Normally Close)
2c
In 6(Normally Close)
2d
In 7(Normally Close)
2e
In 8(Normally Close)
2f
Analog Input:
Counter/Timer:
Counter/Timer
Address
Counter 0/Timer 0
(Normally OFF)
00
Counter 1/Timer 1
(Normally OFF)
01
Counter 0/Timer 0
(Normally ON)
02
Counter 1/Timer 1
(Normally ON)
03
Note: The timer and counter has same address because at a time we can use only one of
them i.e. either counter 0 with address 00 or timer o with address 00. Here normally OFF
means when timer/counter is running this remains low and when count of timer/counter
reaches it becomes high. Reverse is the case for normally ON.
Chapter 6
SOFTWARE DESCRIPTION
This chapter explains how to program the PLC. It describes how to write a
program, how the program is structured and representation of the programming language.
Writing a Program:
A control program specifies a series of operations that tell the programmable controller
how it has to control a system. For example, a control program might be the series of
operations that tell the PLC how to use open loop control or close loop control for a
specific system. We must write the program in a specific programming language and
according to some specific rules so that the programmable controller can understand it.
Method of Representation:
The following methods of representation are possible to program PLC.
1. Statement List (STL):
STL represents the program as a sequence of operation mnemonics. A statement has the
following format:
A I 04
Where A represents AND operation,
I represent INPUT and
04 represent ADDRESS of INPUT.
2. Control System Flowchart(CSF):
CSF represents logic operations with graphics symbols.
3. Ladder Diagram(LAD):
LAD graphically represents control functions with circuit diagram symbols.
4. Graph 5:
Graph 5 describes the structure of sequence control systems.
In our system we are using Statement List (STL) Language.
OPERAND AREAS:
Inputs
Outputs
Timer
Counter
AND Operation
OR Operation
Equals
End of Program
AND Operation:
The AND operation scans to see if various conditions are satisfied simultaneously.
Circuit Diagram
Output U 01 is 1 when all two inputs are 1. The
Output is 0 if atleast one input is 0.
I 04
I 05
U 01
I 04 I 05
U 01
Representation in STL
A I 04
A I 05
= U 01
OR Operation:
The OR operation scans to see if one of two conditions has been satisfied.
Circuit Diagram:
Output U 01 is 1 when at-least one of the
I 04
I 05
Input is 1. Output U 01 is 0 when all
inputs are 0 simultaneously.
U 01
Representation in STL:
O I 04
O I 05
= U 01
Representation in Ladder Diagram
I 04
U 01
I 05
Representation in STL:
O
O
A
O
O
=
I 04
I 05
I 06
I 07
U 01
A I 06
A I 07
= U 01
Circuit Diagram:
Ladder Diagram:
I 04
I 05
I 04
I 06
I 05
U 01
I 07
U 01
I 06
I 07
Timer Operation:
Representation in STL:
A
A
=
O
O
=
I 04
I 05
T 00 10
I 05
T 00
U 01
If both inputs I 04 and I 05 are 1 then only timer T 00 is activated. The count
10 after T 00 in third instruction specifies that the timer should continue till 10 seconds.
O T 00 specifies that the output U 01 is 1 only if I 05 is 1 or the count of timer has
Counter Operation:
Representation in STL:
A
A
=
O
O
=
I 04
I 05
C 00 10
I 06
C 00
U 01
Chapter 7
right;
Ai 04
wrong;
A I 04 right;
AI 04 wrong;
A I 04
wrong;
A I04 wrong;
AI
04
wrong;
AI04 wrong;
3. Clear out all the previously written instruction from the file before writing
instruction for another application.
4. Always specify hex number in lower case.
= T 00 0a
right;
= T 00 0A
wrong;
right;
= T 00 255
wrong;
Chapter 9
SOFTWARE ANALYSIS
The higher-level language program on PC side converts the control program
written in STL language into specific hex codes and transmits these codes to the PLC.
The codes are stored in RAM location in PLC.
The lower-level language program, which is stored in EEPROM internal to the
controller, reads hex codes from memory location one by one. It compares the code read
from the memory location with the predefined hex code and executes the instruction with
accordance to it.
As soon as we put the PLC in RUN mod, it reads the status of all the I/P. It stores
the status in bit addressable memory location as 1 or 0 depends upon the status. Now it
runs the program and performs operation on the status bit directed as user program. It
stores the result in another bit addressable memory location which are corresponds to the
O/P. After this it updates all the O/P.
The Flow chart of the ASSEMBLY LANGUAGE program is given below:
Chapter 9
Chapter 10
APPLICATIONS OF PLC
In the present industrial world, a flexible system that can be controlled by user at
site is preferred. Systems, whose logic can be modified but still, used without disturbing
its connection to external world, is achieved by PLC. Utilizing the industrial sensors
such as limit switches, ON-OFF switches, timer contact, counter contact etc., PLC
controls the total system. The drive to the solenoid valves, motors, indicators,
enunciators, etc are controlled by the PLCs.
The above said controlling elements (normally called as inputs of PLCs) and
controlled elements (called as outputs of PLCs) exist abundantly in any industry. These
inputs, outputs, timers, counters, auxiliary contacts are integral parts of all industries. As
such, it is difficult to define where a PLC cannot be used.
Proper application of a PLC begins with conversion of information into convenient
parameters to save money, time and effort and hence easy operation in plants and
laboratories.
The areas where PLC is used maximum are as follows:
1. The batch processes in chemical, cement, food and paper industries which are
sequential in nature, requiring time of event based decisions is controlled by
PLCs.
2. In large process plants PLCs are being increasingly used for automatic start up
and shut down of critical equipment. A PLC ensures that equipment cannot be
started unless all the permissive conditions for safe start have seen established.
It also monitors the conditions necessary for safe running of the equipment
and trips the equipment whenever any abnormality in the system is detected.
3. The PLC can be programmed to function as an energy management system for
boiler control for maximum efficiency and safety.
4. In automation of blender reclaimers
5. In automation of bulk material handling system at ports.
6. In automation for a ship unloader.
7. Automation for wagon loaders.
Thus PLC is ideal for application where plant machine interlock requirements are
finalized at a later stage and need changes during engineering trial runs, commissioning
or normal use. It can be used extensively to replace conventional relay controls in power
stations, refineries, cement, steel, fertilizer, petrochemical, chemical industries etc.
Applications can thus be extended from monitoring to supervision, control and
management.
FUTURE OF PLCs
The PLC offers a compromise between advance control techniques and present day
technology. It is extremely difficult to forecast the rate and form of progress of PLCs, but
there is strong evidence that development is both rapid and cumulative. Though a PLC is
not designed to replace a computer, it is useful and cost effective for medium sized
control systems. With the capability of functioning as local controllers in distributed
control systems. PLCs will retain their application in large process plants.
A further development of PLCs leads to the development of programmable function
controller (PFC) is compatible to PCs and directly controls the desired functions.
In India every process industry is replacing relay control systems by PLCs and will go
for PFCs in near future. In the near future every flats and offices may possess PFCs to
control room temperature, as elevator controller, maintain water tank levels, as small
telephone exchange etc.
BIBLIOGRAPHY
(1) PROGRAMMABLE LOGIC CONTROLLERS, OPERATION, INTERFACING
AND PROGRAMMING.
JOB DEN OTTER.
(2) IBM PC AND CLONES
GOVINDRAJALU.
(3) MICROPROCESSORS
HARDWARE.
AND
INTERFACING
PROGRAMMING
AND
DOUGLAS HALL.
(4) THE 8051 MICROCONTROLLER ARCHITECTURE, PROGRAMMING AND
APPLICATIONS.
KENNETH AYALA.
(5) MICROPROCESSOR
APPLICATIONS.
ARCHITECTURE,
PROGRAMMING
AND
RAMESH GAONKAR.
(6) MICROPROCESSORS AND MICROCOMPUTERS.
B. RAM.
(7) PROGRAMMING IN ANSI C.
E. BALAGURUSAMY.
(8) SIEMENS SIMATIC S5 PROGRAMMABLE CONTROLLER.
SYSTEM MANUAL.
(9) DIGITAL ELECTRONICS.
WIILIAM GOTHMAN.
(10) INTEGRATED CIRCUITS.
K R BOTKAR.
(11) DATA SHEETS FROM
NATIONAL SEMICONDUCTOR CORPORATION, INTEL, PHILLIPS,
FAIRCHILD
SEMICONDUCTOR
CORPORATION,
MOTOROLA
CORPORATION.
(12) MAGAZINES ELECTRONICS FOR YOU (EFY).
(13) OLD PROJECT REPORTS AND SEMINARS ON PLCS.
Valve A
Agitator
Float switch 1
Valve B
Float switch 2
Problem:
In figure when START button is pressed, solenoid valve A is energized and a
batch of liquid is entered in tank. Float switch 1 detects the upper limit of liquid of liquid
level and Float switch 2 detects the lower limit of liquid. As, tank begins to fill, Switch 2
closes. When the tank is full, switch 1 shuts off the solenoid valve A and start agitator to
mix the liquid. The Agitator mixes the liquid for 30 seconds and shuts off. When the
Agitator turn off, solenoid valve B is energized to drain the liquid. After the tank has been
emptied, float switch 2 opens and solenoid B shuts off.
The Addresses of I/P and O/P are given below.
DEVICE
ADDRESS
NO
NC
Stop Switch
I 04
I 24
Start Switch
I 05
I 25
Float Switch 1
I 06
I 26
Float Switch 2
I 07
I 27
Valve A
U 00
U 20
Valve B
U 01
U 21
Agitator Motor
U 02
U 22
Control Relay
U 03
U 23
I 05
O 03
O 03
I 06
O 03
I 07
O 00
O 00
EN
T 00
I 06
O 03
30
sec
O 01
DN
DN
I 07
DN
O 01
I 06
O 02
O 01
INDEX
Chapter No.
Topics
Page No.
1.
Introduction
1.1 Role of Electronics in Automation.
1.2 Definition of PLC.
1.3 Benefits of Programmable Controllers.
2.
PLC Architecture
2.1 The Parts of Programmable Controllers.
3.
System Overview.
12
4.
Hardware Configuration
14
5.
Addresses
19
6.
Software Description.
6.1 Writing a Program.
6.2 Method of Representation.
6.3 Operand Areas
6.4 Statement List(STL) Programming
Language.
22
7.
29
8.
30
9.
34
10.
Applications of PLC.
35
BIBLIOGRAPHY
38
APPENDIX A
39
APPENDIX B
44