You are on page 1of 28

1

BC80 system catalog.


Building Technologies
A wide range of applications.
BC80 comprises an extensive product portfolio and
can be installed in various building types. For instance,
it is a perfect solution for:
Hotels Commercial buildings Residential complexes
Government buildings Retail stores
2
3
High quality based on decades
of experience, in-depth research,
and state-of-the-art production
technology from Siemens
A flexible solution
expandable and compatible
with future developments
Cost-effective moderate
investment and easy adaptation
to changing requirements
BC80
advantages at a glance:
Siemens quality high reliability
With the BC80 system, you can offer
your customers Siemens quality,
based on in-depth research and de-
velopment, state-of-the-art produc-
tion technology and over 150 years
of experience in fire protection. The
products meet all technical safety
requirements, from short-circuit pro-
tection to immunity against electro-
magnetic interference.
BC80 offers the flexibility your cus-
tomers need, whether they want to
expand or modernize their system.
Thanks to its open topology, the sys-
tem is forward-looking for easy
adaptation to growth and changing
requirements.
Siemens technology
high cost-effectiveness
BC80 combines high-quality tech-
nology with cost-effectiveness, in
procurement as well as operation.
Moderate hardware costs keep the
investment manageable, while the
flexible, expandable installation pro-
tects the long-term view genuine
brand quality at an economical price,
for years to come.
High-quality Siemens
products reliable and
economical.
Your customers are responsible for the protec-
tion of their employees, buildings, and assets.
They also experience cost competition. As a
result, they need fire protection components
that deliver reliable fire detection and alarm
signaling, but which are also cost-efficient. Fire
safety products from Siemens position you per-
fectly to satisfy your customers requirements.
The BC80 system products range from fire detec-
tors to control panels. They are moderately
priced and of reliable quality.
4
Easy installation
fast protection
Because the BC80 system units have
been designed for easy installation,
buildings can be protected quickly.
BC80 provides polarity-free wiring;
poles can no longer be accidentally
reversed. Therefore, the networking
of BC80 fire detectors, peripheral
equipment, and BC80 control panels
is rapid and accurate. The use of spur
lines and T-Branches (F-Bus) further
simplifies installation.
Easy configuration
fast commissioning
Commissioning of the BC80 system
is supported by an integrated auto-
configuration function; with it, the
system automatically detects all inte-
grated devices (auto-mapping). This
reduces manual configuration to a
minimum eliminating a potential
source of error. You benefit from a
shorter time to a fully-operational
system.
More complex manual programming
can be conducted via the control
panels or by using Windows-based
software.
Easy concepts make
your work easier.
BC80 fire protection products are easy to imple-
ment and service. They can be quickly installed
and rapidly commissioned. This reduces your
costs and speeds up order processing. Simplicity
of design reduces the period needed to gain
familiarity with the system, so you can offer
your customers user-friendly fire protection in
the shortest possible time.
Easy maintenance
no interruption of operation
All devices displayed on the con-
trollers are shown with both their
address number and position details.
These help your customers assess
error messages as aids to decision-
making, and you to keep a clear
overview during installation and
maintenance. Devices with conven-
tional technology, such as collective
fire detectors, can also be wired to
the BC80 system via spur lines.
Tracing faulty fire detectors or periph-
eral devices during system operation
is swift, targeted, and cost-efficient.
5
Easy installation and fast building
protection thanks to installation
aids and polarity-free non-shielded
cabling
Fast commissioning thanks to
auto-mapping and Windows-based
software
Minimal maintenance with
address and position of all detectors
and peripheral devices needing
service directly indicated
Smooth expansion via card inserts
for control panels and T-Branches
for cabling
Easy modernization through use
of present cabling, compatibility
with existing peripheral equipment,
and simple software uploads
BC80
advantages at a glance:
Easy expandability
high flexibility
BC80 grows with your customers
requirements. When buildings or
rooms are extended, the BC80 in-
stallation can also be expanded, for
example with new T-Branches in the
cabling and expansion cards in the
control panels.
With an expansion card it is possible
to hook up an additional 127 periph-
eral devices via the F-Bus, as many as
32 additional control panels via the
A-Bus, and up to three B-Bus devices,
such as extinguishing control panels
or interlocking panels. This increases
options for larger projects.
Easy conversion
fast modernization
Existing systems can be replaced and
modernized with BC80 without large
cabling expenditures. Currently in-
stalled cables can be used to network
BC80 devices, since neither the fire
detector lines nor the notification
appliance circuits require a shielded
wire. The system can also be linked
with existing peripheral devices,
which saves time and money. Soft-
ware updates can be uploaded via
the USB port of the control panels.
6
BC80 design and
installation guidelines.
In this section, we illustrate best practice for
installation of fire detection equipment. While
not all possible cases may be covered, these are
intended to provide guidelines. Local regulations
may be more detailed and must always be ob-
served. Please contact your local Siemens sales
organization for more detailed information and
documentation.
BC80 detectors
detectors should be
positioned*
at least 0.5 m from the wall
max. 12 m from the previous
detector
BC80 manual call points
manual call points should
be positioned*
in a clearly visible location
1.5 m from floor level
BC80 fire control panels
mounting the fire control
panel*
Keep a minimum distance to
objects which could obscure
the panel or the view to it
7
* or observe local regulations
Detector positioning
near elevators*
Detector positioning near
fresh air supply*
Use a support to install a
detector at ceiling height*
8
BC80 design and
installation guidelines.
* or observe local regulations
Place the detector at the
highest point in the room*
Ensure the correct distance
to ceiling obstacles*
Position the detector within
the top 10% of a space*
Ensure a minimum distance
to objects which could ob-
struct the view to a manual
call point*
Manual call points should
not be obscured by an open
door*
9
Planning aid for fieldbus.
BDS031
BDS051
BDS121
BDS132
BDS221
BDS152
BDS161
BDS331
Load Max. current (mA)
Quiescent
current (mA)
Name Address points
0.71
0.71
0.43
0.6
0.61
0.07
4
10
0.89
0.89
2.86
3.8
2.19
0.5
16
90
1
1
1
1
2
0
10
1
Heat detector
Photoelectric smoke detector
Manual call point
Input module
Output module
Isolate module
Collective input module
Fire alarm display panel
BC8001
BC8001E
BC8001P
BC8001PE
BC8002-1
BC8002-2
BC8002-3
Source Max. current (mA)
Quiescent
current (mA)
Name Address points
48.5
63.3
51.2
66.0
130.0
170.0
210.0
75.7
113.7
97.0
135.6
224.8
352.6
481.4
127
254
127
254
500
1,000
1,500
Compact controller with 1 line
Compact controller with 2 lines
Compact controller
with 1 line, printer
Compact controller
with 2 lines, printer
Wall-mounted (500 dev.)
Wall-mounted (1,000 dev.)
Wall-mounted (1,500 dev.)
Detectors and peripherals
Panels and systems
A-Bus
Compact
Heat detector
BDS031
Photoelectric
smoke detector
BDS051
Manual
call point
BDS121/e
Output module
BDS221
Manual
call point
BDS121/e
Input module
BDS132
Collective
input module
BDS161
Compact controller
BC8001
F-Bus
Interlocking panel
BT8012
Interlocking panel
BT8011
Compact controller
BC8001
Collective
heat detector
HI520
10
BC80 at a glance.
B-Bus
Extinguishing panel
BC8013
Standard control panel
BC8002
Standard
F-Bus
Collective
photoelectric smoke
detector OP520
Standard control panel
BC8002
11
Legend
A-Bus Network for connecting control panels
(max. 32 control panels, bus length 1 km
can be extended with CAN-Bus bridge)
F-Bus Bus system for connecting line devices
(max. 127 devices per line, bus length 1 km)
B-Bus Network for connecting up to 3 B-Bus devices
(bus length 100 m)
Building Technologies
BC80 Innovative fire safety products
from Siemens.
Are you seeking reliable and easy to use fire safety products everywhere? With the
addressable BC80, Siemens offers an extensive and economical portfolio from fire
detectors to control panels. Thanks to its open topology, BC80 is highly flexible and
adapts easily to changing requirements. The perfect solution for a wide range of
applications from small to large buildings, it can be quickly installed, networked, and
put into service. Backed by 150 years of experience in fire protection, BC80 offers
the effective protection you want for people, buildings and assets.
For more information, please visit www.siemens.com/buildingtechnologies.
Genuine quality for
your protection.
Table of Contents
1 Siemens Building Technologies Group
Panels & Systems ................................................................................................................. 1-1
Addressable Control Panels .............................................................................................. 1-1
Detectors & Peripherals........................................................................................................ 2-5
Conventional Detectors and Bases (Collective).................................................................. 2-5
Addressable Detectors and Bases...................................................................................... 2-6
Manual Call Points ........................................................................................................... 2-7
Addressable Modules ....................................................................................................... 2-8
Spare Parts & Upgrades...................................................................................................... 3-10
Panels & Systems
Addressable Control Panels
1-1 Siemens Building Technologies Group
1
Type Order No.
BC8001.. BC8001 Compact Control Unit
BC8001 is a control unit suitable for small sized projects and construc-
tions. It has the following features:
l
Compatible to BDS series of field devices.
l
Features a polarity free F-BUS with a twisted pair of wires
( 1.5mm2). Transmission distance is up to 1000m. All devices
should be evenly distributed.
l
Specialized BDS Algorithm enhance immunity against environment
disturbances.
l
Menu driven man-machine interface to allow very easy operation.
l
With optional extension card the device can be networked with up to
32 other BC80 control units (BC8001/BC8002).
l
With optional extension card it is possible to connect up to 3 B-Bus
devices i.e. interlocking and extinguishing panels.
l
An optional printer can be mounted into the control unit.
l
The system can be easily configured directly on the panel or via PC.
l
Configuration data can be uploaded to a PC at any time.
Number of detector lines 1
Number of field devices 127
System Network -
Built-in printer -
LCD Display 240 x 128 Backlit
Auto Mapping Yes
Event memory 1000
Digital inputs/outputs 1 Dry contact (24 VDC / 3 A)
1 OC output
2 Monitored inputs
Operating voltage (Main Power) 187... 242 VAC
50... 60 Hz
Battery capacity 24 VDC 7 Ah
Download/Upload USB
Dimensions (W x H x D) 370 x 265 x 120 mm
Weight (without battery) 3.0 kg
Data sheet A5Q00016399A
BC8001..
BC8001 BC8001 Compact Control Unit with 1 F-Bus line for up to
127 Devices
Technical details as BC8001..
A6C50000016
BC8001P BC8001P Compact Control Unit with 1F-Bus line and printer
As BC8001.. for technical details but with the following differences:
One printer TP8000 (thermal sensitive printer) is built-in.
A6C50000018
Panels & Systems
Addressable Control Panels
1-2 Siemens Building Technologies Group
Type Order No.
BC8001E BC8001E Compact Control Unit with 2 F-Bus lines for up to 254
Devices
As BC8001.. for technical details but with the following differences:
An extension card is built-in additionally in the BC8001. This allows
l
Interconnection of up to 32 BC8001 or BC8002 control units (A-Bus).
l
Interconnection of up to 3 B-BUS equipments (BT8011/12 interlock-
ing panel BC8013 extinguishing panel). Another external power
supply (3 A @ 28 VDC) must be used.
A6C50000017
BC8001PE BC8001PE Compact Control Unit with 2 F-Bus lines and printer
As BC8001.. for technical details but with the following differences:
Printer and extension card are built-in additionally.
A6C50000019
BC8002.. BC8002-1/e wall-mounted Advanced Control Unit
BC8002 is an advanced control unit based on latest technology to sup-
port easy operation and commissioning.
l
Text and graphic Display with 10 LCD,640x320 dots backlit.
l
Easy operation with a menu structure similar to Windows Explorer.
l
Advanced micro-processor system (32-bit ARM based micro-proces-
sor).
l
LCD display shows real time values of fire parameters for every detec-
tion point.
l
Auto mapping of the controller configuration simplifies commission-
ing.
l
Multi-tasking real time operating system monitors the system regu-
larly. This ensures high system reliability.
l
Up to 1000 events are stored in the event memory.
l
Modular structure allows flexible system customization.
l
System configurations can be done via panel keypads or via PC tool
(parameters and logic expressions).
l
Powerful interlocking features can be added for demanding control
functions.
l
Up to 32 control units can be interconnected via A-Bus network.
Transmission distance is up to 1000m with a twisted pair of wires
( 1.5mm2).
l
BC8002 can be connected to a management station.
Mains voltage 220 VAC 50 Hz
Operating voltage 23... 30 VDC
Battery capacity 24 VDC 17 Ah
Quiescent current 40... 100 W
Fuse 2.0 A
Operating temperature -10... +50 C
Relative humidity 95% (40 2 C)
Dimensions (W x H x D) 700 x 520 x 120 mm
Weight 22 kg
Data sheet A5Q00016408A
BC8002..
BC8002-1 BC8002-1/e wall-mounted Advanced Control Unit for up to 500
devices 4 loops
As BC8002.. for technical details but with the following differences:
The fire alarm control unit with the original 1 line card can connect up
to 500 devices.
A6C50000029
Panels & Systems
Addressable Control Panels
1-3 Siemens Building Technologies Group
1
Type Order No.
BC8002-2 BC8002-2 wall-mounted Advanced Control Unit for up to 1000
devices
As BC8002.. for technical details but with the following differences:
The fire alarm control unit with an additional line card can connect up
to 1000 devices using 8 loops
A6C50000030
BC8002-3 BC8002-3 wall-mounted Advanced Control Unit forv1500 devices
As BC8002.. for technical details but with the following differences:
The fire alarm control unit with 3 line cards can connect up to 1500
devices using 12 loops
A6C50000030
BT80.. BT8011 / BT8012 Interlocking Panel
BT8011 / BT8012 are interlocking panels. It allows manual and auto-
matic control of external equipment. It is usually installed in the fire
control center together with fire alarm panels in order to control
pumps fans etc.
Operating voltage 24... 29 VDC
Quiescent current 50 mA
Operating temperature 0... +50 C
Storage temperature -20... +60 C
Relative humidity 95 % Rh
Load for each output 300 4 K
Installation height 3 U
Data sheet A5Q00016409A
BT80..
BT8011 BT8011 Interlocking Panel
As BT80.. for technical details but with the following differences:
l
equipped with 16 inputs and 8 outputs.
l
Inputs: 8 inputs are for general purpose and 8 inputs are for confir-
mations.
l
Outputs: OC output capacity is 28 VDC / 80 mA.
l
Output can be configured as steady on or pulsed.
l
Device is connected with the control unit via B-Bus.
l
Indication of activation confirmation and fault for each output .
l
Silence and lamp test keypad available.
l
Panel can be set to manual mode or automatic mode.
l
Panel address output mode connection mode are set with DIP-
switch.
l
TP8000 printer is built-in.
A6C50000032
BT8012 BT8012 Interlocking Panel (without printer)
As BT80.. for technical details but with the following differences:
l
Equipped with 16 outputs and 24 inputs.
l
Inputs: 8 inputs are for general purpose 16 inputs are for confirma-
tion
l
Outputs: each OC output capacity is 28 VDC / 80 mA.
l
Output can be configured as steady on or pulsed.
l
Device is connected with the control unit via B-Bus.
l
Indication of activation confirmation and fault for each output.
l
Silence and lamp test keypad available.
l
Panel can be set to manual mode or automatic mode.
l
Panel address output mode connection mode are set with DIP-
switch.
A6C50000033
Panels & Systems
Addressable Control Panels
1-4 Siemens Building Technologies Group
Type Order No.
BC8013.. BC8013 Extinguishing Panel
The extinguishing panel is used for the control of the extinguishing
sections of a fire installation.
l
One panel monitors 2 extinguishing sections.
l
Each section is equipped with 3 outputs to activate extinguishing
alert extinguishing section separation and gas release. 3 inputs serve
as confirmation of above control outputs.
l
The device is connected via B-Bus. The address is set with a DIP-
switch.
l
Important information of the extinguishing section are displayed on
the control unit.
l
Parameters can be configured on the panel directly or via PC-Tool.
l
External control wires are monitored for short or open circuit.
l
Panel can be set to automatic mode and manual mode.
l
Panel supports auto mapping feature .
Operating voltage 24... 28 VDC
Quiescent current 40 mA
Operating current 200 m A
Output current 80 m A
Maximum current per output 200 m A
Operating temperature -20... +40 C
Data sheet A5Q00016401A
BC8013..
BC8013 BC8013 Extinguishing Panel
Same technical details as BC8013..
A6C50000038
BC8013H BC8013H wall-mounted Extinguishing Panel
As BC8013.. for technical details but with the following differences:
Wall-mounted Extinguishing Panel
A6C50000022
Detectors & Peripherals
Conventional Detectors and Bases (Collective)
2-5 Siemens Building Technologies Group
2
Type Order No.
HI520 HI520 Collective Heat Detector (Rate of Rise and Fix Temperature)
l
Newly developed circuit and sensor ensure high performance of
fixed and rate of rise temperature detection.
l
High stability against dust electromagnetic interference tempera-
ture fluctuation humidity and corrosion.
l
Produced with SMT advanced technology.
Operating voltage 16... 32 VDC
Output voltage 5... 13 VDC
Operating temperature -10... +50 C
Storage temperature -30... +75 C
Relative humidity 95 % (40 2 C)
Quiescent current 100 A
Alarm current 1.5 mA
EMC 10 V/m
Data sheet A5Q00016379A
A6C50000009
OP520 OP520 Collective Optical Smoke Detector
The OP520 is an non addressable detector which can be connected in
to S11 and BC80 system via corresponding collective input modules.
l
Patented optical structure and labyrinth.
l
Homogeneous sensitivity for different kind of smoke.
l
High stability against dust electromagnetic interference tempera-
ture fluctuation humidity and corrosion.
l
Produced with advanced SMT technology.
l
Connection is independent of line polarity.
Operating voltage 21... 29 VDC
Output voltage 5... 13 VDC
Operating temperature -10... +50 C
Storage temperature -30... +75 C
Relative humidity 95 % (40 2 C)
Quiescent current 100 A
Alarm current 1.5 mA
EMC 10 V/m
Data sheet A5Q00016380A
A6C50000010
SO520 SO520 Collective Detector Base
The detector base for field devices HI520 and OP520.
Data sheet A5Q00016382A
A6C50000011
Detectors & Peripherals
Addressable Detectors and Bases
2-6 Siemens Building Technologies Group
Type Order No.
BDS031 BDS031 Addressable Heat Detector (Rate of Rise and Fix Tempera-
ture)
BDS031 is a heat detectors which can be connected to the F-Bus
l
Newly developed circuit and sensor ensure high performance of
fixed and rate of rise temperature detection.
l
High stability against dust electromagnetic interference tempera-
ture fluctuation humidity and corrosion.
l
Produced with SMT advanced technology.
Operating voltage 16... 32 VDC
Operating temperature -10... +50 C
Storage temperature -30... +75 C
Relative humidity 95 % (40 2 C)
Quiescent current 1.0 mA
Alarm current 3.0 mA
EMC 10 V/m
Data sheet A5Q00016383A
A6C50000001
BDS051 BDS051 Addressable Optical Smoke Detector
BDS051 is smoke detector which can be connected to the F-Bus.
l
Patented labyrinth optical structure.
l
New built-in ASIC ensures high reliability of data processing.
l
Homogeneous response to different kind of smoke.
l
High stability against dust electromagnetic interference tempera-
ture fluctuation humidity and corrosion.
l
Produced with SMT advanced technology.
Operating voltage 16... 32 VDC
Operating temperature -10... +50 C
Storage temperature -30... +75 C
Relative humidity 95 % (40 2 C)
Quiescent current 1.0 mA
Alarm current 3.0 mA
EMC 10 V/m
Data sheet A5Q00016384A
A6C50000002
BDS000 BDS000 Addressable Detector Base
Detector base is for field devices BDS051 and BDS031.
The detector covers the whole base the wiring capacity is 1.0 to 1.5
mm.
Data sheet A5Q00016385A
A6C50000000
Detectors & Peripherals
Manual Call Points
2-7 Siemens Building Technologies Group
2
Type Order No.
BDS121 BDS121 Manual Call Point
Manual call point can immediate trigger a fire alarm by breaking the
glass.
l
Connected to F-Bus
l
Installed in the public area such as staircase elevator lobby etc
l
Device address can be set via a DIP-switch.
l
A built-in dry contact can be used to activate another equipment.
l
Mounted on the wall 1.5 meters above the ground.
l
Electronic part and housing are delivered separately.
Operating voltage 24 VDC
Operating temperature -20... +55 C
Relative humidity 95 % (40 2 C)
Quiescent current 1 mA
Alarm current 3.0 mA
Capacity of dry contact 24 VDC / 0.1 A
EMC 10 V/m
Data sheet A5Q00016386A
A6C50000003
Detectors & Peripherals
Addressable Modules
2-8 Siemens Building Technologies Group
Type Order No.
BDS132 BDS132 Input Module
The input module serves as an interface to transmit alarms or technical
signals from other equipments to the fire alarm control unit.
l
Connected to the F-Bus device address can be set with a DIP-switch.
l
Serves as interface for potential free signals from flow switches pres-
sure switches etc to the fire alarm system.
l
The signal will be transmitted to the controller and trigger corre-
sponding actions.
l
Connection faults will be automatically detected and displayed on
the controller.
Operating voltage 24 VDC
Operating temperature -20... +55 C
Relative humidity 95 % (40 2 C)
Activation current 3 m A
Quiescent current 1 mA
Wiring Capacity 1.0 1.5 mm
Data sheet A5Q00016394A
A6C50000004
BDS152 BDS152 Isolation Module
The isolation module is used to isolate a short circuit on the detection
bus. The device will automatically recover to its normal status when the
cause of the short circuit disapears.
l
The isolation module separates a short circuit on the F-Bus.
l
Parallel connection on the first place of each branch or stub is possi-
ble.
l
No device address is required.
l
When a single loop is used to connect devices mounted on several
floors it is recommended to install one isolation module on each
floor.
l
Up to 25 field devices can be mounted to an isolation module.
l
The connection is polarity free.
l
Faults will be automatically detected and displayed on the controller.
Operating temperature -20... +50 C
Relative humidity 95 % (40 2 C)
Activation current 0.5 mA
Pass through voltage 1 VDC
Wiring Capacity 1.0... 1.5 mm
Data sheet A5Q00016395A
A6C50000005
Detectors & Peripherals
Addressable Modules
2-9 Siemens Building Technologies Group
2
Type Order No.
BDS161 BDS161 Collective Input Module
Collective input module can connect collective detectors to the F-Bus
l
Directly connected to the F-Bus addresses are set with a DIP-switch
l
Up to 15 collective detectors can be connected to the module
l
An end of line element P6KE18CA has to be used.
l
Module transmits alarm fault and danger level signal to the control
unit
l
The same indications are displayed on the module.
l
Connection is polarity free.
l
Faults will be automatically detected and displayed on the control
unit.
Alarm voltage 3.7... 16.4 VDC
Fault voltage 0... 3.7 VDC (short)
22.1 VDC (open)
Normal voltage 16.4... 22.1 VDC
Alarm current <16 mA
Operating temperature -10... +50 C
Quiescent current <4 mA
Relative humidity 95 % (40 2 C)
Wiring Capacity 1.0... 1.5 mm
Data sheet A5Q00016397A
A6C50000006
BDS221 BDS221 Output Module
The output module is used to activate external equipment according to
the function of the fire alarm unit.
l
Connected to F-Bus addresses are set with a DIP-switch.
l
Output can be configured as pulse or steady on with DIP-switch.
l
Connection is polarity free.
l
The input signal for feedback is a potential free contact.
l
It is not recommended to use this module for extinguishing control
directly.
l
Faults will be automatically detected and displayed on the controller.
Operating voltage 24 VDC
Operating temperature -10... +50 C
Relative humidity 95 % (40 2 C)
Activation current 3 mA
Quiescent current 1 mA
Relay output 125 VAC / 0.6 A
24 VDC / 2 A
Status LEDs Steady output - Steady ON
Pulse Output - Flashing
Wiring Capacity 1.0... 1.5 mm
Data sheet A5Q00016398A
A6C50000007
Spare Parts & Upgrades
3-10 Siemens Building Technologies Group
Type Order No.
TP8000 TP8000 Printer
A thermal sensitive printer is used to print events.
Data sheet A5Q00016403A
A6C50000028
BCE8001 BCE8001 Extension Card
Extension card for BC8001 compact controller.
This card contains the following interfaces:
l
A-Bus interface to add the network feature to the compact controller
(networkable up to 32 controllers).
l
B-Bus interface to allow BC8001 to connect up to 3 B-Bus devices.
l
F-Bus interface for additional up to 127 devices.
Data sheet A5Q00016402A
A6C50000024
BCC8001 BCC 8001 Main Board of BC80 Compact
Data sheet A5Q00016405A
A6C50000035
BT8002 BT8002 Operation Panel
The BT8002 is the operation panel of BC8002 Advanced Control Unit.
l
The operation panel consists of the main board BCC8002 the CPU
board BCC8011 LCD and the keypads and LED's as indicators.
l
Connected with other control units via A-Bus.
l
Connected with interlocking panels line cards extinguishing panels
via B-Bus.
l
Download/Upload port on the CPU board.
l
BT8002 Operation panel features also numerical keys and loud
speaker.
l
A communication port for connection to a management station is
built-in.
Data sheet A5Q00016413A
A6C50000034
Spare Parts & Upgrades
3-11 Siemens Building Technologies Group
3
Type Order No.
BCB8001 BCB8001 Wall-mounted Power Supply (8A)
Input voltage 220 VAC / 50HZ
187... 242 VAC (Effective)
Output voltage 20... 28 VDC / 8 A (Main power ork-
ing)
24 VDC (Only battery working)
Operating temperature -10... 50 C
Relative humidity 95 % Rh
Protection Output 8.0 * 110 % (Over current
protection)
Output 1.0 (Output short pro-
tection)
Voltage <20.0 V (Battery low pro-
tection)
Battery CB12170 (12 V / 17 AH)
CB12250 (12 V / 25 AH)
CB12380 (12 V / 38 AH)
DJW (12 V / 24 AH)
DJW (12 V / 38 AH)
NP (12 V / 24 AH)
NP (12 V / 38 AH)
Data sheet A5Q00016411A
A6C50000039
BCC8002 BCC8002 Main Board of BC8002 Advanced Control Unit
The main board includes
l
A-Bus port
l
B-Bus port
l
I/O port
l
FMS connection port
l
power signal port etc.
The board handles data gathered from F-Bus and other channels. It
serves as the data processing center of the control unit.
Data sheet A5Q00016407A
A6C50000036
Spare Parts & Upgrades
3-12 Siemens Building Technologies Group
Type Order No.
BCM8001 BCM8001 Line Card for BC8002 Advanced Control Unit
The BCM8001 is the line card connecting BDS field devices
l
Each BCM8001 can connect 4 loops; each loop can connect up to
127 devices.
l
Overload protection: recovers to normal status when the cause of
overload disappears.
l
B-Bus address is set with a DIP-switch on the board.
Number of loops 4
Number of addresses 127 (on one loop)
Max. load factor 150 (for each loop)
Wiring Capacity RVS1.0... RVS1.5
Max. distance per line 1000 m
Resistor per line 300
Capacitor per line 300 nF
Protection Short protection
Over voltage protection
Connectable field devices BDS Series
Operating voltage Modulated 16... 32 VDC
Quiescent current Full load: 200 mA
No Load: 110 mA
Data sheet A5Q00016410A
A6C50000037
Type Index
1
Siemens Building Technologies Group
Type Description Order No. Page
BC8001 BC8001 Compact Control Unit with 1 F-Bus line for up to
127 Devices
A6C50000016 1-1
BC8001.. BC8001 Compact Control Unit BC8001.. 1-1
BC8001E BC8001E Compact Control Unit with 2 F-Bus lines for up to 254
Devices
A6C50000017 1-2
BC8001P BC8001P Compact Control Unit with 1F-Bus line and printer A6C50000018 1-1
BC8001PE BC8001PE Compact Control Unit with 2 F-Bus lines and printer A6C50000019 1-2
BC8002-1 BC8002-1/e wall-mounted Advanced Control Unit for up to 500
devices 4 loops
A6C50000029 1-2
BC8002-2 BC8002-2 wall-mounted Advanced Control Unit for up to 1000
devices
A6C50000030 1-3
BC8002-3 BC8002-3 wall-mounted Advanced Control Unit forv1500 devices A6C50000031 1-3
BC8002.. BC8002-1/e wall-mounted Advanced Control Unit BC8002.. 1-2
BC8013 BC8013 Extinguishing Panel A6C50000038 1-4
BC8013.. BC8013 Extinguishing Panel BC8013.. 1-4
BC8013H BC8013H wall-mounted Extinguishing Panel A6C50000022 1-4
BCB8001 BCB8001 Wall-mounted Power Supply (8A) A6C50000039 3-11
BCC8001 BCC 8001 Main Board of BC80 Compact A6C50000035 3-10
BCC8002 BCC8002 Main Board of BC8002 Advanced Control Unit A6C50000036 3-11
BCE8001 BCE8001 Extension Card A6C50000024 3-10
BCM8001 BCM8001 Line Card for BC8002 Advanced Control Unit A6C50000037 3-12
BDS000 BDS000 Addressable Detector Base A6C50000000 2-6
BDS031 BDS031 Addressable Heat Detector (Rate of Rise and Fix Temper-
ature)
A6C50000001 2-6
BDS051 BDS051 Addressable Optical Smoke Detector A6C50000002 2-6
BDS121 BDS121 Manual Call Point A6C50000003 2-7
BDS132 BDS132 Input Module A6C50000004 2-8
BDS152 BDS152 Isolation Module A6C50000005 2-8
BDS161 BDS161 Collective Input Module A6C50000006 2-9
BDS221 BDS221 Output Module A6C50000007 2-9
BT80.. BT8011 / BT8012 Interlocking Panel BT80.. 1-3
BT8002 BT8002 Operation Panel A6C50000034 3-10
BT8011 BT8011 Interlocking Panel A6C50000032 1-3
BT8012 BT8012 Interlocking Panel (without printer) A6C50000033 1-3
HI520 HI520 Collective Heat Detector (Rate of Rise and Fix Temperature) A6C50000009 2-5
OP520 OP520 Collective Optical Smoke Detector A6C50000010 2-5
SO520 SO520 Collective Detector Base A6C50000011 2-5
TP8000 TP8000 Printer A6C50000028 3-10
12
www.siemens.com/buildingtechnologies
Siemens Switzerland Ltd
Building Technologies Group
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel +41 41 724 24 24
Fax +41 41 724 35 22
The information in this document contains general descriptions of technical options available,
which do not always have to be present in individual cases. The required features should therefore
be specified in each individual case at the time of closing the contract.
Windows is a registered trademark of Microsoft Corporation
Subject to change Order no. 0-92065-en
Siemens Switzerland Ltd Printed in Switzerland 10705 Ah

You might also like