You are on page 1of 2

Calcular as novas impedncias de cada equipamento, bem como de cada uma das

linhas, da rede de distribuio de energia, adotando a potncia de base do


Gerador de 75 MVA e tenso de base de 18 KV?
G = (frmula do Zpu2)
G = 0,158 * (13,8/18)^2 * (75/45)
G = j0,1547 PU
T1 = 0,122 * (13,8/18)^2 * (75/45)
T1 = j0,0894 PU
REGRA DE
13,2 69
X= 94,09

3:
18
X
Kv

T2 = 0,135 * (69/94,09)^2 * (75/10)


T2 = j0,5445 PU
T3 = 0,128 * (69/94,09)^2 * (75/75)
T3 = j0,6883 PU
T4 = 0,094 * (69/94,09)^2 * (75/35)
T4 = j1,083 PU
ZLT1 = 4,16+J2,76(Ohm) = 5[33,56 GRAUS
ZB = (94,09)^2/75 = 118,03
ZLT1(PU) = 5/118,03 = j0,0423 PU
ZLD1 = 2,56+j0,75 - 2,667[16,32 graus
69
- 94,09
13,2 - X
X= 18 Kv
ZB= (188)^2/75 = 4,32 OHM
ZLD1PU = 2,667/4,32 = j0,617 PU
L2PU = 13,7*(13,8/18)^2*(75/0,3) = j2013,13 PU
M1 = 2,89*(13,8/18)^2*(75/3,5) = j36,4 PU
ZLST1 = 3,36+j1,29 OHM = 3,6[21 GRAUS
69
- 94,09
3,45 - X
X = 47,045 Kv
ZB = (47,0458)^2/75 = 29,5
ZLT1(PU) = 3,6/29,5 = j0,122 PU
M2 = 4,12*(32/47,045)^2*(75/4,35) = j33,63 PU

ZLST2 = 4,57+j2,39 OHM = 5,157[27,6 GRAUS


69 - 94,09
44 - X
X = 60 Kv
ZB = (60)^2/75 = 48
ZLT1(PU) = 5,157/48 = j0,107 PU
M2 = 3,75*(42/60)^2*(75/2,7) = j51,04 PU