1. Wiring guidelines for X20 modules with Ethernet connection Certain X20 System modules have an Ethernet connection. The POWERLINK cables available from B&R can be used for wiring. The following wiring guidelines must be observed: Use CAT5 SFTP cable Do not exceed the cable flex radius (observe data sheet for cable) Secure the cable on the bottom of the module. The cable must be secured vertically under the RJ45 socket on the module. Model number Connection type X20CA0E61.xxxxx Connection cable - RJ45 to RJ45 X20CA3E61.xxxx Connection cable - RJ45 to RJ45, can be used in cable drag chains X67CA0E41.xxxx Attachment cable - RJ45 to M12 X67CA3E41.xxxx Attachment cable - RJ45 to M12, can be used in cable drag chains Table 1: POWERLINK cable with RJ45 connection Information: When the POWERLINK cables offered by B&R are used, the EN61131-2 product standard is met. For any further requirements, the customer must take additional measures. 2 Wiring guidelines with Ethernet cable Data sheet V 1.00 1.1 Wiring diagram Figure 1: Wiring diagram for X20 module with Ethernet cable r r min r r min