SLC 500™ Analog Input Module: Installation Instructions
SLC 500™ Analog Input Module: Installation Instructions
Inside
Important User Information ........................................................................... 2
For More Information ...................................................................................... 3
Hazardous Location Considerations ............................................................. 4
Environnements dangereux .......................................................................... 4
Electrostatic Damage.................................................................................... 5
1746-NI8 Power Requirements..................................................................... 5
Module Location in Chassis .......................................................................... 6
Heat and Noise Considerations .................................................................... 7
Module Installation and Removal.................................................................. 7
Terminal Wiring ........................................................................................... 10
Input Devices .............................................................................................. 15
Specifications.............................................................................................. 17
Publication 1746-IN006A-US-P
@JO"VTQQE
".
Publication 1746-IN006A-US-P
@JO"VTQQE
".
Publication
Number
1770-4.1
1746-6.8
1747-6.2
1747-6.21
Publication 1746-IN006A-US-P
@JO"VTQQE
".
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2.
Do not replace components or disconnect equipment unless
power has been switched off.
Do not connect or disconnect components unless power has
been switched off.
All wiring must comply with N.E.C. article 501-4(b).
Environnements dangereux
Cet quipement est conu pour tre utilis dans des environnements de Classe 1,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
sapplique une utilisation dans des environnements dangereux.
MISE EN GARDE
DANGER DEXPLOSION
La substitution de composants peut rendre cet quipement
impropre une utilisation en environnement de Classe 1,
Division 2.
Ne pas remplacer de composants ou dconnecter
l'quipement sans s'tre assur que l'alimentation est
coupe.
Ne pas connecter ou dconnecter des composants sans
s'tre assur que l'alimentation est coupe.
Publication 1746-IN006A-US-P
@JO"VTQQE
".
Electrostatic Damage
Electrostatic discharge can damage semiconductor devices inside this module if you
touch backplane connector pins. Guard against electrostatic damage by observing
the following precautions.
ATTENTION
24V dc Amps
200 mA
100 mA
When you are using a modular system configuration, add the values shown in the
table above to the requirements of all other modules in the SLC chassis to prevent
overloading the chassis power supply.
Publication 1746-IN006A-US-P
@JO"VTQQE
".
Chassis Location
Publication 1746-IN006A-US-P
@JO"VTQQE
".
RACK
MODULE
ATTENTION
Publication 1746-IN006A-US-P
@JO"VTQQE
".
2. Grasp the terminal block at the top and bottom and pull outward and down.
CURRENT
O 12
N
O 12
N
VOLTAGE CH0
O 12
N
O 12
N
CH7
Publication 1746-IN006A-US-P
@JO"VTQQE
".
Card
Guide
Publication 1746-IN006A-US-P
@JO"VTQQE
".
10
Terminal Wiring
The 1746-NI8 module contains an 18-position, removable terminal block. The
terminal pin-out is shown below.
ATTENTION
Terminal Block
(Terminal Block Spare Part Catalog Number 1746-RT25G)
Shield
Channel 0 (+)
Channel 0 (-)
Channel 1 (+)
Channel 1 (-)
Channel 2 (+)
Channel 2 (-)
Channel 3 (+)
Channel 3 (-)
Channel 4 (+)
Channel 4 (-)
Channel 5 (+)
Channel 5 (-)
Channel 6 (+)
Channel 6 (-)
Channel 7 (+)
Channel 7 (-)
Shield
Publication 1746-IN006A-US-P
@JO"VTQQE
".
11
Use shielded communication cable (Belden 8761) and keep length as short as
possible.
Connect only one end of the cable shield to earth ground.
Connect the shield drain wires for channels 0 to 3 to the top shield terminal.
Shield terminals are internally connected to chassis ground which is connected to
earth ground via the SLC backplane.
Single-ended source commons may be jumpered together at the terminal block.
Channels are not isolated from each other.
If a different signal source has an analog common, it cannot and must not be
connected to the module.
Common mode voltage range is 10.5 volts. The voltage between any two
terminals must be less than 15 volts.
The module does not provide power for the analog inputs.
Use a power supply that matches the transmitter (sensor) specifications.
Publication 1746-IN006A-US-P
@JO"VTQQE
".
12
+
-
Shield
single-end
signal source
+
shield
single-end
signal source
shield
single-end
signal source
+
+
+
+
-
differential
signal source
shield
shield
shield
+
differential
signal source
Channel 5
Channel 4
differential
signal source
Channel 3
+
differential
signal source
Channel 2
single-end
signal source
Channel 1
shield
Channel 0
Channel 6
shield
shield
Channel 7
Shield
Publication 1746-IN006A-US-P
@JO"VTQQE
".
13
When wiring single-ended analog input devices to the analog input module, the
number of total wires necessary can be limited by jumpering all IN terminals
together. Note that differential inputs are more immune to noise than single-ended
inputs.
IMPORTANT
The module does not provide loop power for analog inputs. Use
a power supply that matches the transmitter specifications.
+
-
1746-NI8
+ Signal
IN 0+
IN 0-
Transmitter
+ Signal
IN 1+
IN 1-
Transmitter
+ Signal
IN 2+
IN 2-
Transmitter
Supply
Signal
Ground
IN 3+
IN 3-
Publication 1746-IN006A-US-P
@JO"VTQQE
".
14
+
-
Module
IN +
IN -
Transmitter
3-Wire Transmitter
Supply
Module
IN +
IN -
GND
Power +
Supply-
4-Wire Transmitter
Transmitter
Supply
Signal
Power +
Supply
+
-
IMPORTANT
+
-
Module
IN +
IN -
The module does not provide loop power for analog inputs. Use
a power supply that matches the transmitter specifications.
Publication 1746-IN006A-US-P
@JO"VTQQE
".
15
Wiring Guidelines
ATTENTION
Input Devices
Transducer Source Impedance
If the source impedance of the input device and associated cabling is too high, it
affects the accuracy of the channel data word. Source impedance of 500 ohms
produces up to 0.05% of module error over and above the specified accuracy of the
module.
You can compensate for device impedance error by implementing the following
equation in your ladder program:
VS
V measured
(R s
R in)
R in
Publication 1746-IN006A-US-P
@JO"VTQQE
".
16
Cable
(Cut foil shield
and drain wire.)
Signal Wire
Signal Wire
Signal Wire
Drain Wire
Foil Shield
Signal Wire
Publication 1746-IN006A-US-P
@JO"VTQQE
".
17
Specifications
Electrical Specifications
Description
Specification
200 mA at 5V dc
100 mA at 24V dc
Number of Channels
8 (backplane isolated)
Input Filtering
1 Hz
2 Hz
5 Hz
10 Hz
20 Hz
50 Hz
75 Hz
Calibration
Isolation
Publication 1746-IN006A-US-P
@JO"VTQQE
".
18
Physical Specifications
Description
Specification
LED Indicators
Module ID Code
Recommended Cable
Maximum Cable
Impedance
Terminal Block
Environmental Specifications
Description
Specification
Operating Temperature
Storage Temperature
Relative Humidity
Agency Certification
UL listed
CSA approved
CE compliant for all applicable directives
Hazardous Environment
Classification
Publication 1746-IN006A-US-P
@JO"VTQQE
".
19
Input Specifications
Description
Specification
10V dc
1 to 5V dc
0 to 5V dc
0 to 10V dc
0 to 20 mA
4 to 20 mA
20 mA
0 to 1 mA
Engineering Units
Scaled-for-PID
Proportional Counts (-32,768 to +32,767 range)
Proportional Counts (User Defined Range, Class 3 only)
1746-NI4 Data Format
Input Impedance
1 M
30 mA
1 module scan
(1)
Input Resolution
1 mV or 1 A
Display Resolution
1 mV or 1 A
( 1 Depends
)
on filter selected. Refer to the 1746-NI8 User Manual, publication 1746-6.8.
Publication 1746-IN006A-US-P
@JO"VTQQE
".
PN 40071-081-01 (A)
@JO"VTQQE
".