Professional Documents
Culture Documents
HTC Swbd-1 Relay Setting
HTC Swbd-1 Relay Setting
2013
CONVERTOR DUTY TRANSFORMER(6.6/0.690KV)
FULL LOAD PRIMARY CURRENT
FULL LOAD of EACH SECONDARY CURRENT
Sl No.
Feeder Name
Actual load
2.5 MVA
218.69 A
2091.85A
CT Ratio
I>
in
AMP
I>>>
TI>
I >>
T I >>
IE>
T IE>
I E>>
T IE>>
I EP>
T IEP> IP > in T IP>
in Sec. in AMP in Sec. in AMP in Sec. in AMP in Sec. in AMP in Sec.
AMP
in Sec. in AMP
T>>>
IE>>>
in Sec. in AMP
I/C - 1
1200-800/1+1, 1000/1
0.65
60
1.4
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
250/1+1
0.87
60
1.35
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
250/1+1
0.87
60
1.35
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
OG1( CDT) TO WC
800/1+1+1
0.7
60
1.35
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
OG1(CDT) TO SPARE
250/1+1
0.87
60
1.35
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
BUS COUPLER
800/1+1
0.65
60
1.4
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
250/1+1
0.87
60
1.35
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
10
250/1+1
0.87
60
1.35
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
11
OG2(CDT) TO WC
800/1+1+1
0.7
60
1.35
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
12
OG1(CDT) TO SPARE
250/1+1
0.87
60
1.35
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
0.65
60
1.4
0.1
0.5
0.15
0.3
0.1
0.1
0.7
0.5
2.8
0.25
13
*
1200-800/1+1, 1000/1
ACTUAL LOAD IS TO BE FILLED AT THE TIME OF COMMISSIONING
I/C - 2
2.5 MVA
218.69A
3478.01 A
TE>>>
in Sec.
0
0
0
0
0
0
0
0
0
0
0