DECS-200
File Name:
Settings File Print Out
My Folder\Projekti\Basler za GiM\BASLER -
GiM\MHE_Gozna .de2
BESTCOMS Version: 1.05.00
Model Number: DEcs-200
Style Number: ic
Part Nunbei 9360101014
App Version 1.03.02
DSP Version: 1.03.01
Boot Version. 2.10.00
Serial Number:
Comm Settings: 9600
9600
9600, 247, 10,N, 2
4. sijeeanj 2013
15215139
SHEP GOZNA
Comments:
detsteasesetseeaneenstene System Configuration *#tsttereeseeseseeeanenes
System Operating Mode
System Control Mode
System Operating Status:
Limiter Mode:
Underfrequency Node:
Sensing Configuration:
Generator Frequency:
Voltage Matching Switch
Generator PT Primary Voltage:
Generator PT Secondary Voltage
Generator CT Primary Current:
Generator CT Secondary Current:
Bus PT Primary Voltage:
Bus PT Secondary Voltage:
Internal Tracking Enable:
Internal Tracking Time Delay:
Internal Tracking Traverse Rate:
External Tracking Enable:
External Tracking Time Dela:
External Tracking Traverse Rate
Generator Rated Apparent Power:
Generator Rated Power Facto:
Generator Rated Real Power:
Exciter Field Rated Resistance:
Generator Rated Voltage:
Generator Rated Current
Generator Rated Field Voltage:
Generator Rated Field Current:
Pole Ratio ~ Exciter Poles/Generator Pole
stop
AVR
Droop
SCL/OEL/UEL,
UF
‘Three Phase
50 Hz
oft
6.300 Vac.
110 vac
150 Aac
1 aac
6.300 vac
10 vac
Enabled
0,1 Sec(s)
20,0 Secis)
Disabled
0,1 Sec{s}
20,0 Secs}
1604,05 KVA
0,80
1283, 24 KW
10,55 Ohms
6.300 Vac
147,0 aac
15,0 Vdc
10,9 Ade
1,00
Auxiliary Input Type:
Auxiliary Input Summing Type:
(avR/ECR)
AVR Node Auxiliary Input Gain:
FOR Mode Auxiliery Input Gain:
var Node Auxiliary Input Gain
AVR PF Auxiliary Input Gain:
Reactive Droop Compensation:
Cross Current Compensation Gain:
Page 1
Voltage
Inner Loop
1,00
2,00
1,00
1,00
5,0 %
0,00 $DECS-200 Settings File Print Out
setevsseeensensseesensens Setting Adjustments *#4+thertesresttieesenen
AVR
AVR
AVR
AVR
AVR
SetPoint:
Minimum Setpoint:
Maximum Setpoint
Pre-position
Traverse Rate:
Pre-position Mode:
Setpoin’
Minimum Setpoint
Maximum Setpoint:
Pre-position:
Traverse Rate
Pre-position Mode
6304, 68 Vac
95,0 8
105,0 &
6.300,0 vac
20 Sec(s)
Release
0,00 Ade
0,0 8
105,0 &
0,00 ade
20 Sec(s)
Release
var,
var
var
PF
PE
PE
PE
PE
Gen
Gen
SetPoint:
/BF Voltage Band:
Minimum Setpoint
Maximum Setpoint
Pre-position:
‘Traverse Rate:
Pre-position Mode:
SetPoint:
Maximum Setpoint (Leading):
Maximom Setpoint (Lagging) :
Traverse Rati
Pre-position Mode:
0,00 kvar
20,00 ¥
“40 4 of rated vA
60 $ of rated VA
0,00 kvar|
20 Sec(s)
Release
1,000
0,920
0, 800
20 Secis)
Release
erator Voltage Soft Start Bias:
erator Voltage Soft Start Time
Underfrequency Setting (Corner Frequency):
Und
Vou
vol
EL
EL.
lerfrequency Setting (Slope):
tage Matching Band:
‘tage Matching Level (Generator
to Bus):
58
5 Sec(s)
47,0 He
1,00 V/Hz
5,00 & (nom.
100,0 ¢
styl
Option:
Off-Line OEL Setting - High Current Level:
Off-Line OEL Setting - High Current Time:
Off-Line OFL Setting - Low Current Level
ont
oni
on-i
ont
on-
Take
Take
Take
Take
‘Take
Tak
‘Line OEL
‘Line OEL Setting - High Current
Line OEL
Line OEL
Line OEL Setting - Low Current
Setting - Medium Current Leve:
Setting - Medium Current Time
‘Setting - High Current Level:
Time:
Leve:
Summing Pt
Option 1
5,5 Ade
6 Sec(s)
4,0 Ade
18,6 Adc
6 Secis)
11,5 Ade
120 Sec(s)
10,9 Ade
eover Limiter
eover Limiter
eover Limiter Off-line Timedial
eover Limiter
eover Limiter
eover Limiter On-line Timedial:
Off-line High Current Level:
Off-line Low Current Level
On-line High Current Level:
On-line Low Current Level:
Page 2
Amps
Amps:
0
0
el
70 Amps
70 Amps
1DECS-200 Settings File Print Out
UEL Curve Type Selection: Internal.
UEL Curve = lst Point kW Generate: 0 kW
UEL Curve = 1st Point kvar Absorbed: 640 kvar
UEL Curve = 2nd Point kW Generate o KW
UEL Curve = 2nd Point kvar Absorbed: 0 kvar
UEL Curve = 3rd Point kW Generate: 0 kW
UEL Curve = 3rd Point kvar Absorbe: 0 kvar
UEL Curve = 4th Point kW Generate: 0 kW
UEL Curve = 4th Point kvar Absorbe 0 kvar
UEL Curve = Sth Point ki Generate: 0 kW
UEL Curve = 5th Point kvar Absorbed: 0 kvar
Stator Current Limiter Initial Delay: 0,0 sec
Stator Current Limit Hi Value: 220,5 Amps
Stator Current Limit Hi Time : 3,0 sec
Stator Current Limit Low Value: 429,0 Amps
daweatsesesteeneesenernensee® Control Gaing +#tttthitineesesessenenmnnses
Stability Range (Gain Table Index): 21
AVR/ECR ~ Proportional Gain KP: 30,0
AVR/FCR - Integral Gain KI: 150,0
AVR/FCR - Derivative Gain KD! 2,0
AVR/ECR - Derivative Gain TD: 0,08
AVR - Loop Gain Kg: 3,0
FCR - Loop Gain Kg 25,0
PE - Integral Gain KI: 120,0
var - Loop Gain Kg: 1,00
PE - Loop Gain Kg: 1,0
SCL Integral Gain KT: 10,0
SCL Loop Gain Kg: 1,0
OEL - Integral Gain KI: 10,0
EL - Loop Gain Kg: 1,0
UEL Integral Gain KI 10,0
UEL Loop Gain Kg: 2,0
Voltage Matching - Loop Gain Kg: 1,0
sttetttieseeenenneceeense Protection Settings *##tsteteresseesensienes
Generator Overvoltage: Enabled
Generator Undervoltage Enabled
Exciter Field Overvoltage Enabled
Exciter Field Overcurrent: Enabled
Exciter Open Diode: Disabled
Exciter Shorted Diode: Disabled
Loss Of Field: Enabled
Loss Of Sensing Voltage: Enabled
Loss of Sensing Time Delay: 0,1 Sec(s)
Loss of Sensing Balanced Level: 50,0 &
Loss of Sensing Unbalanced Level: 20,0 &
Transfer To FCR Mode: Enabled
Page 3