You are on page 1of 2

li-ion battery solution for

Telecom Base Station


Samsung SDIs safe, proven and the most
reliable solution for telecom industry
Meet Samsung SDIs newest BTS solution which
will give you peace of mind. With Samsung SDIs
BTS solution, you can enjoy the benefits of lower
total cost of ownership, higher performance,
higher environmental friendliness, lower maintenance, and more.

Special features
Fully replaceable with current batteries
(Lead-Acid, Ni-Cd)

Automatic voltage balancing between trays

Batteries can use existing rectifier by only


adjusting some values (Voltage range, Current)

SDI battery system ensures safety under


any abnormal conditions

Flexible Capacity configuration.


(1.77 kWh / 35Ah ~ 28.32 kWh / 560 Ah, 1 to 16 trays)

Optionally provided gateway can support LCD display,


Dry-contact(8ch), RS-485(1ch), CAN 2.0b(1ch) functions

Simple maintenance

Hot-swappable battery
No power-down during maintenance

Capable of clearing all Pain Points of Lead Acid


volume

capacity

-50%

100%

+60%

100%
Capacity

Lead-Acid

installation weight

LIB

Lead-Acid

-20%

80%

160%

20~25

Cooling system
needed

Capacity

LIB

operating temperature

Lead-Acid

LIB

Lead-Acid

0~55

No additional
cooling need

LIB

specification
Operating conditions
-10C ~ +55C / +14F ~ +131F

Operating temperature
Cycle efficiency

95%

Self-discharge

< 2.5% per month at 25c

Storage time

12 months at 25c

Maximum relative Humidity

90%

Maximum altitude

2000m above sea level

Nominal Characteristics at +25C / +77F


Voltage (V)

50.4

Capacity (Ah)

35

Rated Energy (Wh)

1770

Volumetric energy density (Wh / l)

117

Gravimetric energy density (Wh / kg)

120

Mechanical Characteristics
Width (mm)

482 (19 Rack Mount Type)

Height (mm)

96

Depth (mm)

433

Weight (kg)

18.5

Nominal Characteristics at +25C / +77F


Voltage range (V)

42 ~ 56

Nominal discharge current (Amps)

17.5

Nominal recharge current (Amps)

17.5

Maximum discharge current (Amps)

35

Maximum recharge current (Amps)

35

Peak discharge current in 3sec (Amps)

40

Peak recharge current in 3sec (Amps)

40

Recharge time at 17.5Amps / 35Amps (h)

2.2h / 1.3h

Min

recharge time

typical life cycles

200

20,000

180

12A

160

18,000
16,000

140

17.5A

120

100

14,000
12,000

10,000

80

35A

60

8,000

40

4,000

20

2,000

Number of cycles

6,000

0
10

20

30

40

50

60

70

80

90

100

Soc%

10

20

30

40

50

60

70

80

90

100

DoD%

E-MAIL CONTACT energy.storage@samsung.com