Star Coupler 23SC60

Application
The Star Coupler 23SC60 is used to connect
decentralized I/O modules of the RTU211. It
is used to extend the serial peripheral bus
over distances of more than app. 50 cm.
The Star Coupler 23SC60 is available in 8
versions (Rubrik):

23SC60 R009n

Plastic Fiber
max. 500 m

23SC60 R008n

Glass Fiber
max. 2000 m

Where n is the number of modules within


one plastic enclosure (2 n 5).

Characteristics
The Star Coupler 23SC60 is build by 2 up to
5 interface adaptors 23AD63 in one plastic
enclosure. They are connected in parallel
and to the Wired OR-Bus of the RTU211 by
a special connection cable.
Each interface adaptor 23AD63 is equipped
with two green LEDs, showing the activities
on the bus.

Doc.-No.: 1KGT 150 708 V000 1

Fig. 1: Star Coupler with two lines

ABB AG
RTU211

Data Sheet Star Coupler 23SC60


Technical Data
In addition to the RTU560/RTU211 general technical data, the following applies:

Power Consumption
Typical

n * 0.35 W @ 5 V DC

Mechanical Layout
Length
Width
Height

n * 35.0 mm
107.5 mm
20.0 mm

Connection Type
Connector
R009n:
Plastic Fiber
R008n:
Glass-Fiber

RTU211 System Cable


Plastic, 650 nm, max. 50 m
HCS 650 nm, max. 500 m
Connector Type: HP
Multimode 820 nm,
62.5/125, max. 2000 m
Connector Type: ST

Test Voltage
AC Test Voltage
EN 61000-4-16
IEC 60870-2-1
(class VW3)
Impulse Voltage
with stand test
IEC 60255-5
IEC 60870-2-1
(class VW 3)

2,5 kV, 50 Hz
Test duration: 1 min

5 kV (1,2 / 50 s)

Environmental conditions
Temperature
Relative
Humidity

-25 ... +70 C


5 ... 95 %
(non condensing)

ABB AG

Immunity Test
Electrostatic
Discharge
Immunity Test
IEC 61000-4-2
(level 3)
Radiated RadioFrequency
Electromagnetic
Field Immunity
Test
IEC 61000-4-3
(level 3)
Immunity to
Electrical Fast
Transient / Burst
IEC 61000-4-4
(level 3)
Surge Immunity
Test
IEC 61000-4-5
(level 3)
Immunity to
Conducted
Disturbances,
induced by RadioFrequency Fields
IEC 61000-4-6
(level 3)

4 kV Contact
8 kV Air
Performance criteria A
10 V/m
Performance criteria A

2 kV
Performance criteria A

2 kV
Performance criteria A
10 V
Performance criteria A

Ordering Information
23SC60 R009n
Plastic Fiber
23SC60 R008n
Glass Fiber

1KGT 015 800 R009n


1KGT 015 800 R008n

Where n = number of channels per enclosure

Kallstadter Str. 1, D 68309 Mannheim


Phone
+49 (0) 621 381 7592
Fax
+49 (0) 621 381 7622
www.abb.com/pt
Subject to alterations

Doc.-No.: 1KGT 150 708 V000 1

You might also like