1.

UNLESS OTHERWISE STATED, SECURE ALL CONDUITS TO


STRUCTURAL STEEL WORK USING RIGHT ANGLE TYPE
(U-BOLT) CONDUIT. ENSURE THAT SUPPORTS ARE SIZED
TO SUIT CONDUIT.

M88 X

ITEM
SAMSS
UNIT
DESCRIPTION
NO.
NO.
1 12-066-569 SF STEEL PLATE: 1"x1 1/2 "x 3/8 " THICK

PLANT NO.

INDEX

DA-950068 1 OF 3 00
DRAWING NUMBER

SHT. NO.

12

14

16

WELL CONDUCTOR

13

15

17

(TYP.)

FLANGE

18
SEE NOTE 3

15-195-484

MT

CABLE: 70mm2

15-282-502

EA

STUFFING BOX: 1"

15-290-852

EA

BUSHING: 1" CONDUIT

15-314-914

PC

CONDUIT: 1"

15-444-136

EA

CONDUIT NIPPLE: 1" PVC COATED

15-515-810

EA

SUPPORT:

15-537-334

EA

UNION: 1" CONDUIT PVC COATED

15-591-110

EA

CONDUIT HUB: 1" GUAT, PVC COATED

10

15-625-500

EA

UNIVERSAL BREATHER:

11

15-736-153

EA

REDUCER: 1"x 1/2 "

12

20-476-815

BX

CARTRIDGE: CADWELD #65

13

20-476-818

BX

CARTRIDGE: CADWELD #90

14

20-477-040

EA

CLAMP: CADWELD B-323-B

15

20-477-060

EA

CLAMP: CADWELD L-160

16

20-495-397

EA

MOLD: HAA-Y4-5

17
18

20-495-447
17-858-793

EA

MOLD: CADWELD TAC-Y4Y4

MT

CABLE: 70mm2

PVC CABLE

2. ENSURE THAT ALL CONDUIT AND CONDUIT FITTINGS


ARE PVC COATED.
3. ON J-55 OR K-55 TYPE STEEL CASINGS, MARK NEGATIVE
CONNECTION TO FLANGES NOT TO CASING.

PVC COATED

RIGHT ANGLE TYPE, 1" CONDUIT U-BOLT; PVC COATED

1/2 "

4. WELD AND COAT ALL STEEL PER APPLICABLE SAES


STANDARDS.
5. BOAT LANDING SUPPORT SHOWN IS TYPICAL. ACTUAL
CLAMP ARRANGMENT WILL VARY.

HMWPE CABLE

SEE DETAIL-4
(TYP.)

CABLE TO NEGATIVE
JUNCTION BOX

18

SUPPORT MEMBER
TO BOAT LANDING

SEE DETAIL-1

12

9
10

WELL CONDUCTOR

14

16

SEE DETAIL-4
(TYP.)
6

BOAT LANDING SUPPORT


MEMBER CLAMP

11

TYP. FOR 2

(TYP.)

SYMBOLS:

TO VERTICAL JACKET
LEG OR BRACE
CONDUIT UNION

DETAIL-1

PLAN VIEW
WELL CONDUCTOR BONDING

TYPICAL WELL CONDUCTOR BONDING

CONDUIT

BOAT LANDING SUPPORT


REFERENCE DRAWINGS

(TYPICAL) SEE NOTE 5

RISER

AA-036384

OFFSHORE NEGATIVE JUNCTION BOX

AA-036108

OFFSHORE LIDA ANODE PILE MOUNTED

AB-036008

OFFSHORE STRUCTURES ANODE


INSTALLATION DETAILS

AA-036348

OFFSHORE TENSION SPRING IMPRESSED


CURRENT SYSTEM

AA-036780

(TYP.)
SEE DETAIL-4
(TYP.)

(TYP.)

12

RISER BRACKET SUPPORT

OFFSHORE ANODE JUNCTION BOX

2
12

14

16

J-TUBE
OR RISER

14
1

16

TYP. FOR 2

10

25

SEE DETAIL-4
(TYP.)

TYPICAL FOR 2

12

RISER CLAMP

38

70mm
HMWPE CABLE
IN 1" CONDUIT TO
NEGATIVE JUNCTION BOX

MAIN DECK PLATE

14
16
HORIZONTAL JACKET
BRACING MEMBER

1
18

OR

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.

NOTES:

MATERIAL LIST

FORMERLY STD. DWG. AA-036394; SHT. 001; REV. 00


STRUCTURAL MEMBERS

DETAIL-2

DETAIL-3

DETAIL-4

RISER BONDING

RISER BONDING

CADWELD CONNECTION
REV.
NO.

DATE

BY

DESCRIPTION

JO/EWO

CHKD.

CERT.

APPD.

SAUDI ARABIAN OIL COMPANY


DRAWN BY

EDSD/WED

DATE STARTED

CHECKED BY

02-07-99

NONE

SCALE:

DATE COMPLETED

02-07-99

ENG. DEPT.

OPRG. DEPT.
APPD. FOR CONST.
THIS DRAWING IS NOT TO BE USED FOR

CERTIFIED

CONSTRUCTION OR FOR ORDERING


MATERIAL UNTIL CERTIFIED AND DATED

BY

DATE

BONDING FOR OFFSHORE STRUCTURES


OFFSHORE INSTALLATION DETAILS
METRIC

LIB. DWG.
PLANT NO.

INDEX

M88 X

DRAWING NUMBER

SHT. NO.

REV. NO.