TRANS!
MISSION CONSTRUCTION STANDARD
ATTACHMENT #15 CHECK LIST
SIS Name
Bay No.
2.8
No:
Trip Circuit Supervision
28.1 Trip Circuit Supply Supervision
a, General Mechanical Checks & Visual Inspection
C.
XS) TCS-P-105, Rev. 01
ITEM
DESCRIPTION
DONE
REMARKS,
‘General Visual Inspection
“As per 4.1
‘On Units fitted with hand reset flag indicators, check that the flag
is free to fall before, or just, any contacts closes. Make sure that
the reset mechanism in the cover is correctly located with respect
to the relay element and the flag (or mechanism) can be reset.
‘Check condition of any connectors, contacts alignment and travel
‘Check armature gap.
‘Check for proper operation of LEDs.
b. Electrical tests,
ITEM DESCRIPTION
DONE
REMARKS,
‘General Electrical Tests
As per 4.2
Measure Trip Supply and Alarm Suppl
‘Check Protective fuse ratin,
Ensure correct values of extemal resistors (where applicable)
and wired to the correct relay terminals
‘Check the continuity of the contacts,
‘Check the resistance of all output contacts,
Check pickup Voltage / Drop —off vollage and measure
current,
‘Check power consumption when the relay is energized.
Check Relay Coil Resistance.
Initiate Alarm by removing fuse.
‘Check Nominal contact voltage AC/DC.
‘Check for visual indication for power supply, pickup and reset
2.82 Trip Circuit Supervision, without pre-closing supervisi
a, General Mechanical checks, visual inspection
ITEM
DESCRIPTION
DONE
REMARKS
General Visual Inspection
As per 4.1
‘On Units fitted with hand reset flag indicators, check that the flag
is free to fall before, or just, any contacts closes. Make sure that
2. | the reset mechanism in the cover is correctly located with respect
to the relay clement and the flag (or mechanism) can be reset.
3.__[ Check condition of any connectors, contacts alignment and travel
4.__[ Cheek armature gap
5.__[ Check for proper operation of LEDs.
TESPIOSROWTMA Dato of Approva uly 08,2011
PREENG OOF TTTRANSMISSION CONSTRUCTION STANDARD
ATTACHMENT #15 CHECK LIST
I$ Name / No:
Bay No.
b. Electrical tests
C.
XS) TCS-P-105, Rev. 01
DESCRIPTION
DONE
REMARKS,
General Electrical Tests
‘AS per 4.2
Check that rating of the relay agree with the Auxiliary Supply to
which it is connected,
‘Check that DC Supplies are wired with the correct polarity
Measure Trip Supply and Alarm Supply
Check Protective fuse rating,
Ensure correct values of extemal resistors (where applicable) and
wired to the correct relay terminals.
Check the continuity of the contacts,
Check the resistance of all output contacts
Check pickup / Drop —off for both voltage and current of the
operating coil
‘Check power consumption when the relay is energized.
Check operating Coil Resistance.
Check voltage across relay coil when circuit breaker is open and
closed.
Check voltage across extemal resistors (where applicable) when
circuit breaker is open and closed.
14,
With the circuit breaker closed apply @ temporary Short circuit
across each of the extemal resistors (where applicable) of the trip
circuit. Ensure the C.B. does not trip
5,
Tnitiate Alarm by removing fuse.
16.
voltage ACIDG
17.
cation for power supply, pickup and reset
2.8.3 Trip Circuit Supervision, with pre-closing supervision
a, Mechanical checks & visual inspection
DESCRIPTION
DONE
REMARKS,
General Visual Inspection
‘As per 4.1
‘On Units fitted with hand reset flag indicators, check that the flag is
free to fall before, or just, any contacts closes. Make sure that the
reset mechanism in the cover is correctly located with respect to the
relay clement and the flag (or mechanism) can be reset.
Check condition of any connectors, contacts alignment and travel.
‘Check armature gap.
‘Check for proper operation of LEDs.
b, Electrical tests
DESCRIPTION
DONE
REMARKS,
General Electrical Tests
‘As per 4.2,
Check that rating of the relay agree with the Auxiliary Supply to
which itis connected,
TESPIOSROWTMA Dato of Approva uly 08,2011
PREENG TH OF TTTRANSMISSION CONSTRUCTION STANDARD
C.
XS) TCS-P-105, Rev. 01
ATTACHMENT #15 CHECK LIST
SIS Name / No:
Bay No,
TEM DESCRIPTION DONE | REMARKS
3.__| Check that DC Supplies are wired with the correct polarity,
4, [ Measure Trip Supply and Alarm Supply
3.___| Check Protective fuse rating.
6, _ | Ensure correct values of extemal resistors (where applicable) and
wired to the correct relay terminals.
7___| Check the continuity of the contacts.
8.__| Check the resistance of all output contacts
9,__| With the C.B. Open Check pickup / Drop -off for both voltage and
current of Operating coil-1
10,_ | With the C.B. closed Check pickup / Drop —off for both voltage and
current of Operating coil-2.
11. | Check power consumption when the relay is energized.
12.__| Check operating Coil Resistance.
13,_ | Check voltage actoss relay coil when cireuit breaker is open and
closed.
14, | Check voltage across extemal resistors (where applicable) when
circuit breaker is open and closed.
With the circuit breaker closed apply @ temporary Short circuit
15, | actoss each of the external resistors (where applicable) of the trip
circuit, Ensure the C.B. does not trip
16, | Initiate Alarm by removing fase.
17._| Check Nominal contact voltage AC/DC.
18. | Check for visual indication for power supply, pickup and reset
TESPIOSROWTMA Dato of Approva uly 08,2011
PREENG EOF TT