SM6 MV Switchgear
SM6 MV Switchgear
Catalogue | 2013
SM6
Modular units
Air insulated switchgear up to 36 kV
Medium Voltage
Distribution
SM6
Air insulated
switchgear
1 to 36 kV
Your requirements
Safety
Operating safety through protection against electrical,
mechanical and thermal effects of a fault (insulation of each
compartment)
All operations carried out from the front, door closed
Voltage Presence Indicator System located on the front panel
Position indicator linked to the devices physical position
Protection in the event of internal arcing
Interlocking devices
Anti-reflex handles
Reliability
Type-tested solution which complies with the IEC62271-200
standard
Design by the most accurate three-dimensional computer
techniques
Manufacturing & Testing according to ISO 9001:2000
quality standard
Simplicity
Easy installation - All cubicles with the same engineering
dimensions
On-site information retrieval
Possibility of remote management
Maintenance with power on (LSC2A), very simple
Compartmentalization of MV parts
(insulated partitions)
Medium Voltage
Distribution
SM6
Air insulated
switchgear
1 to 36 kV
Our solutions
Schneider Electric has developed protection, monitoring and control solutions specifically
dedicated to Medium Voltage networks for over 40 years.
SM6 switchgear has been specifically designed on the basis of that extensive experience.
It also incorporates some very new solutions, giving the best in terms of continuity of service
and operators safety.
PE57150
SF1
or/and
Evolis*
630
1250
A comprehensive solution
SM6 switchgear is fully compatible with
PowerMeter metering units.
Sepam multi-function protection relays
- Protection
- Measurements and diagnosis.
VIP protection self powered relay for protection.
SM6 swithchboards can thus be easily integrated into any monitoring
and control system.
- Local & remote indication and operation.
SM6, a truly
professional
solution!
More than
1,300,000
cubicles
installed
world-wide.
SM6
AMTED398078EN
General contents
Presentation
General characteristics
11
Characteristics
of the functional units
49
Connections
83
Installation
91
Appendices
Order form
101
AMTED398078EN
Presentation
AMTED398078EN
Contents
Quality assurance
Presentation
PM103194
The Schneider Electric experiences extends over forty years in factorybuilt cubicles and over thirty years in SF6 breaking technology for Medium
Voltage switchgear.
This experience means that today Schneider Electric can propose
a complementary range: vacuum type circuit breaker cubicles up to 24 kV
and standard or enhanced internal arc withstand cubicles to reinforce
the safety of people according to the IEC standard.
This gives you the advantage of unique experience, that of a world leader,
with over 2,500 000 SF6 Medium Voltage units installed throughout
the world.
Putting this experience at your service and remaining attentive to your
requirements is the spirit of active partnership that we want to develop
in offering you the SM6.
The modular SM6 is a range of harmonised cubicles equipped with SF6 or
vacuum breaking technology switchgear with 30 years life span.
These cubicles allow you to produce all your Medium Voltage substation
requirements up to 36 kV by superposing their various functions.The result
of in-depth analysis of your requirements, both now and in the future, SM6
cubicles mean that you can take advantage of all the features of both a
modern and proven technology.
1975: innovation
Sulphur hexafluoride (SF6) is first used in an MV switch for an MV/LV
transformer substation, with the VM6.
1989: experience
Over 300,000 VM6 cubicles equipped networks throughout the world.
1991: innovation and experience
Cumulated with the second generation of SM6 modular SF6 cubicles.
2013: a leading position
With over 1,300,000 SM6 cubicles installed around the world,
Schneider Electric consolidates its position as uncontested leader
in the Medium Voltage field.
AMTED398078EN
Presentation
Upgradability
SM6, a comprehensive range
Compactness
SM6, an optimised range
Maintenance
SM6, a range with reduced maintenance
bb The active parts (breaking and earthing) are integrated in an SF6-filled, sealed for
life unit
bb The control mechanisms, are intented to function with reduced maintenance
under normal operating conditions
bb Enhanced electrical endurance when breaking.
Ease of installation
SM6, a simple range to incorporate
bb Reduced dimensions and weights
bb Only one civil works layout
bb A solution adapted to cable connection
bb Simplified switchboard busbar design.
With the SM6, Schneider Electric proposes solutions for network management;
the Sepam and VIP or relay ranges protect installations, providing continuity
of electrical supply and reducing downtime.
AMTED398078EN
Presentation
61051N
61016N
24 kV
36 kV
Switch
unit
Circuit breaker
unit
Switch
unit
Circuit breaker
unit
Ferrous metal
84%
65%
74%
82 %
Non-ferrous metal
4%
10.6%
8%
7.8 %
Thermohardening
9.5%
22%
15%
8%
Thermoplastics
2.35%
2.3%
2%
2%
Fluid
0.15%
0.1%
1%
0.2 %
MT55145
01
ISO 140
AMTED398078EN
Presentation
61052N
PE57151
AMTED398078EN
Presentation
PE57234
Asia/Middle East
Africa
South America/Pacific
Europe
AMTED398078EN
Presentation
Quality assurance
A major advantage
MT55055
MT55054
The quality system for the design and manufacture of SM6 units
has been certified in conformity with the requirements of
the ISO 9001: 2000 quality assurance model.
ISO
900 1
ISO
9002
61002N
During manufacture, each SM6 is subject to systematic routine testing which aims to
check the quality and conformity:
bb Sealing testing
bb Filling pressure testing
bb Opening and closing rate testing
bb Switching torque measurement
bb Dielectric testing
bb Conformity with drawings and plans.
61003N
The results obtained are written and reported on the test certificate for each device
by the quality control department.
AMTED398078EN
10
AMTED398078EN
General characteristics
Contents
Field of application
12
14
15
18
19
Operating conditions
20
Standards
21
Main characteristics
22
24
Compartments description
26
Safety of people
28
28
30
31
By switchgear
By operating mechanism safety
By internal arc protection
AMTED398078EN
32
32
33
34
37
Ammeter
39
40
40
43
43
44
45
46
47
11
Field of application
General characteristics
HV/MV substation
MV consumer substation
(MV metering)
IM
CM
DM2
QM
PM
IM
DE59670EN
MT55148
IM
MV consumer substation
(LV metering)
IM
IM
QM DM1-S
Substation
GAM2 QM
MT55147
Other standards
MV consumer substations
(MV metering)
IM
DM1-D
GBC-A
QM
DM1-S
MT55146
IM
12
AMTED398078EN
Field of application
General characteristics
DE59200EN
HV/MV substation
Distribution switchboard
GBC-B
QM QM IM
IM
GBC-B
DM1-A
61004N
DM1-A
Incoming
line
ATS
Incoming
line
Unit definitions
Standby
generator source
Standby
source
Distribution switchboard
QM QM GBC-B
IM
IMB GBM IM
GBC-B
DM1-S
DM1-S
ATS
Incoming
line
Incoming
line
AMTED398078EN
13
General characteristics
IM
Switch unit
SM6-24: 375 or 500 mm
SM6-36: 750 mm
50
DE59673
DE59672
See in
details
on page
DE59671
Switching
IMC
Switch unit
SM6-24: 500 mm
SM6-36: 750 mm
IMB
Switch unit
with earthing disconnector
right or left outgoing line
SM6-24: 375 mm
SM6-36: 750 mm
51
14
DE59693
DE59692
NSM-cables
Cables power supply
for main incoming line
and standby line
SM6-24: 750 mm
NSM-busbars
Busbars power supply
for main incoming line on right or left
and cables for standby line
SM6-24: 750 mm
AMTED398078EN
General characteristics
QM
Fuse-switch combination unit
SM6-24: 375 or 500 mm
SM6-36: 750 mm
QMC
Fuse-switch combination unit
SM6-24: 625 mm
SM6-36: 1000 mm
QMB
Fuse-switch combination unit
right or left outgoing line
SM6-24: 375 mm
SM6-36: 750 mm
DE59677
52
DE59676
DE59675
Fuse-switch
DE59674
See in
details
on page
PM
Fuse-switch unit
SM6-24: 375 mm
SM6-36: 750 mm
53
54
DE59679
DE59678
SF6 circuit-breaker
DM1-A
Single-isolation, disconnectable
circuit breaker unit
SM6-24: 750 mm
SM6-36: 1000 mm
AMTED398078EN
DM1-D
Single-isolation, disconnectable
circuit breaker unit
right or left outgoing line
SM6-24: 750 mm
SM6-36: 1000 mm
15
General characteristics
DM1-W
Withdrawable single-isolation
circuit breaker unit
SM6-24: 750 mm
DM1-S
Single-isolation, disconnectable
circuit breaker unit with
autonomous protection
SM6-24: 750 mm
DM1-Z
Withdrawable single-isolation
circuit breaker unit
right outgoing line
SM6-24: 750 mm
DE59680
55
56
DE53490
DE53487
See in
details
on page
DE59681
SF6 circuit-breaker
DM2
Double-isolation, disconnectable
circuit breaker unit right or left outgoing line
SM6-24: 750 mm
SM6-36: 1500 mm
55
57
16
DMV-A
Single-isolation
circuit breaker unit
SM6-24: 625 mm
DE53493
DE53492
DE53491
Vacuum circuit-breaker
DMV-D
Single-isolation
circuit breaker unit
right outgoing line
SM6-24: 625 mm
DMV-S
Single-isolation
circuit breaker unit with
autonomous protection
SM6-24: 625 mm
AMTED398078EN
General characteristics
DE59694
See in
details
on page
DE53485
Vacuum circuit-breaker
DMVL-A
Single-isolation, disconnectable
circuit breaker unit
SM6-24: 750 mm
58
DMVL-D
Single-isolation, disconnectable
circuit breaker unit right outgoing line
SM6-24: 750 mm
59
DE59232
DE59231
CVM
Fuse-contactor unit
SM6-24: 750 mm
AMTED398078EN
CVM
Contactor unit
SM6-24: 750 mm
17
DE59684
CM
Voltage transformers for mains
with earthed neutral system
SM6-24: 375 mm
SM6-36: 750 mm
DE53496
60
61
18
CM2
Voltage transformers for mains
with insulated neutral system
SM6-24: 500 mm
SM6-36: 750 mm
DE53497
See in
details
on page
DE59863
General characteristics
GBC-A
Current and/or voltage
measurement unit
right or left outgoing line
SM6-24: 750 mm
SM6-36: 750 mm
GBC-B
Current and/or voltage
measurement unit
SM6-24: 750 mm
SM6-36: 750 mm
AMTED398078EN
DE53498
DE59687
GEM
Extension unit VM6/SM6
SM6-24: 125 mm
DE59688
GBM
Connection unit
right or left outgoing line
SM6-24: 375 mm
SM6-36: 750 mm
62
GAM2
Incoming cable-connection unit
SM6-24: 375 mm
SM6-36: 750 mm
GAM
Incoming cable-connection unit
with earthing
SM6-24: 500 mm
SM6-36: 750 mm
GFM
Extension unit
Fluokit M36/SM6-36*
SM6-36: 250 mm
64
DE59690
DE59689
DE53504
62
63
GIM
Intermediate bus unit
SM6-24: 125 mm
SM6-36: 250 mm
DE53498
DE59686
See in
details
on page
DE59685
General characteristics
SM
Disconnector unit
SM6-24: 375 mm or 500(1) mm
SM6-36: 750 mm
TM
MV/LV transformer unit
for auxiliaries
SM6-24: 375 mm
SM6-36: 750 mm
EMB
Busbar earthing compartment
SM6-24: 375 mm
* For other switchboard extension (Modularc 36, Unifluorc or Fluokit M24), please consult us.
AMTED398078EN
19
Operating conditions
PE57152
General characteristics
20
AMTED398078EN
General characteristics
Standards
bb IEC standards
62271-200
High-voltage switchgear and controlgear - Part 200: A.C. metalenclosed switchgear and controlgear for rated voltage above 1 kV
and up to and including 52 kV.
62271-1
62271-103
62271-105
60255
Electrical relays.
62271-100
62271-102
61869-2
61869-3
60044-8
62271-206
High-voltage prefabricated switchgear and controlgear assemblies Voltage presence indicating systems.
62271-304
NFC 13.200
NFC 64.130
High voltage switches for rated voltage above 1 kV and less than 52 kV.
AMTED398078EN
HN 64-S-41
HN 64-S-43
21
General characteristics
Main characteristics
PE57150
The hereunder values are for working temperatures from -5C up to +40C
and for a setting up at an altitude below 1000 m.
Electrical characteristics
Rated voltage
Ur
7.2
kV
12
17.5
24
36
Insulation level
Insulation
Ud
20
28
38
50
70
Isolation
Ud
23
32
45
60
80
Insulation
Up
60
75
95
125
170
Isolation
Up
70
85
110
145
195
16
31.5
50
630-1250
25
630 - 1250
1250
20 (2)
630 - 1250
16
630 - 1250
Breaking capacity
Rated current
Ir
Ik/tk (1)
kA/1 s
Ima
kA
12.5
62.5
630
50
630
40
630
31.25
400 - 630
630
630
630-1250
NA
NSM-cables, NSM-busbars
kA
25
PM
kA
25
CVM
kA
6.3
NA
kA
25
NA
NA
20
20
20
kA
kA
DM1-Z
DM2
kA
25
630-1250
20
630-1250
1250
25
630
NA
25
1250
NA
20
630
25
630
1250
kA
25
630-1250
DMVL-A
kA
20
630
NA
DMVL-D
kA
25
630
NA
NA
22
AMTED398078EN
General characteristics
Main characteristics
PE57150
Endurance
Units
Mechanical endurance
Electrical endurance
IEC 62271-103
1000 operations
class M1
IEC 62271-103
100 breaks at Ir,
p.f. = 0.7, class E3
CVM
IEC 62271-102
1000 operations
Disconnector
IEC 60470
250000 breaks at Ir
Disconnector
IEC 62271-102
1000 operations
IEC 62271-100
30 breaks at 12.5 kA for SM6-24
25 breaks at 25 kA for SM6-24
40 breaks at 16 kA for SM6-36
15 breaks at 25 kA for SM6-36
10000 breaks at Ir,
p.f. = 0.7, class E2
Operating sequence
O - 0.3s - CO - 15s - CO
O - 0.3s - CO - 3mn
O - 3mn - CO - 3mn - CO
Switch
IEC 62271-103
1000 operations
class M1
IEC 62271-103
100 breaks at Ir,
p.f. = 0.7, class E3
Evolis circuit
breaker
IEC 62271-100
10000 operations
class M2
IEC 62271-100
100 breaks at 25kA for SM6-24
10000 breaks at Ir,
p.f. = 0.7, class E2
Disconnector
IEC 62271-102
1000 operations
Evolis circuit
breaker
IEC 62271-100
10000 operations
class M2
DMVL-A
DMVL-D
IEC 62271-100
100 breaks at 16kA for SM6-24
100 breaks at 25kA for SM6-24
10000 breaks at Ir,
p.f. = 0.7, class E2
AMTED398078EN
23
Factory-built cubicles
description
General characteristics
2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.
5 low voltage: installation of a terminal block (if motor option installed), LV fuses
DE58647
2
1
5
4
2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.
5 low voltage: installation of compact relay devices (Statimax) and test terminal
boxes. If more space is required, an additional enclosure may be added on top
of the cubicle.
Options: please, refer to the chapter Characteristics of the functional units.
24
AMTED398078EN
Factory-built cubicles
description
General characteristics
DE58648
1 switchgear: load break switch and earthing switch(es), in enclosure filled with
5
4
SF6 and satisfying and one vacuum circuit breaker, sealed pressure system
requirements.
2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.
If more space is required, an additional enclosure may be added on top of the cubicle.
Options: please, refer to the chapter Characteristics of the functional units.
DE58649
5
4
and satisfying and one vacuum circuit breaker, sealed pressure system
requirements.
2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.
If more space is required, an additional enclosure may be added on top of the cubicle.
Options: please, refer to the chapter Characteristics of the functional units.
Contactor cubicles
DE58650
2
1
2 busbars: all in the same horizontal plane, thus enabling later switchboard
5
the disconnector(s), the contactor and the earthing switch and actuate
the corresponding indications.
5 low voltage: installation of compact relay devices and test terminal boxes.
4
AMTED398078EN
25
61007N
DE53507
General characteristics
Compartments description
Busbar compartment
61006N
DE53508
The three insulated busbars are parallel-mounted. Connection is made to the upper
pads of the enclosure using a field distributor with integrated captive screws.
Ratings 400 (for SM6-24 only) - 630 - 1250 A.
Switch compartment
This compartment is separated from the busbar compartment and the connection
compartment by the enclosure surrounding the switch, the disconnector and
the earthing switch.
DE57172
DE53510
See in fonctional units characteristics chapter for each unit allowable section.
The earthing switch must be closed before the cubicle may be accessed.
The reduced depth of the cubicle makes for easy connection of all phases.
A stud incorporated in the field distributor makes it possible to position and secure
the cable-end lug with a single hand.
26
AMTED398078EN
Compartments description
PE57230
Operating-mechanism cover
These covers contain the various operating functions for the:
bb switch and earthing switch
bb disconnector(s)
bb circuit breaker
bb contactor
and the voltage presence indicator.
The operating-mechanism cover may be accessed with the cables and busbars
energised and without isolating the substation.
It also enables easy installation of padlocks, locks and standard LV accessories
(auxiliary contacts, trip units, motors, etc.).
C - LV control cabinet
h = 2050 mm
450 mm
DE57195
C
B
A
215 mm
AB
AMTED398078EN
1500 mm
1615 mm
27
DE59695
A - LV cover
h = 2250 mm
PE58270
PE57153
DE57173
General characteristics
Safety of people
General characteristics
By switchgear
61010N
PE57226
Switch-disconnector for 24 kV
Switch-disconnector for 36 kV
Closed position
Open position
Earth position
28
AMTED398078EN
Safety of people
General characteristics
By switchgear
61012N
DE53514
bb Operating safety
Accidental over-pressures are eliminated by the opening of the safety membrane.
61058N
Contacts closed
PE50798
Precompression
Arcing period
Contacts open
bb Vacuum tightness
Vacuum contactor comprises three separate poles fixed on a structure supporting
the control mechanism. Each pole encloses all of the active parts in an insulating
enclosure under vacuum and its vacuum tightness is checked in the factory.
AMTED398078EN
29
General characteristics
Safety of people
PE57230
PE57231
Mechanical and electrical controls are side by side on the front fascia, on a panel
including the schematic diagram indicating the devices status (closed, open, earthed):
bb Closed: the drive shaft is operated via a quick acting mechanism, independent of
the operator. No energy is stored in the switch, apart from when switching operations
are taking place.
For combined switch fuses, the opening mechanism is armed at the same time
as the contacts are closed.
bb Opening: the switch is opened using the same quick acting mechanism,
operated in the opposite direction.
For circuit breakers and the combined switch fuses, opening is controlled by:
vv a push-button,
vv a fault.
bb Earthing: a specific control shaft enables the opening or closing of the earthing
contacts. Access to this shaft is blocked by a cover that can be slid back if the switch
is open but which remains locked in place if it is closed.
PE57166
The position of main contacts is clearly visible from the front of the cubicle through
the window.
Despite SM6 switch is sealed pressure system and has open and close capacity
on rated current at 0 bar relative pressure SF6, to insure you about the internal
pressure, we propose on request before sale or on site by after-sales either
a pressure switch or an analog manometer on the switch.
These devices are both fitted without any alteration on the switch, they are
temperature compensated and compatible with visibility of main contacts
if requested.
PE56366
VPIS complies with 62271-206 standard allowing to indicate the voltage presence on
each phase with LEDs. Designed for harsh environments so that to guarantee high
reliability in MV/LV susbstations worldwide.
Exits in Voltage Output version to provide voltage presence information to VD23
voltage presence relay.
30
AMTED398078EN
General characteristics
Safety of people
Consequently:
The SM6 is designed to offer a good level of safety
bb Control of the architecture:
vv compartment type enclosure.
DE59732
bb Technological control:
vv electrotechnical: modelling of electrical fields,
vv mechanical: parts produced using CAD systems.
bb Use of reliable components:
vv choice of materials,
vv earthing switch with closing capacity.
DE59734
In all internal arc versions, the SM6 has successfully passed all of the type testing
relative to standard IEC 62271-200 (5 acceptance criteria).
The materials used meet the constraints for which the SM6 is designed.
The thermal and mechanical forces that an internal arc can produce are perfectly
absorbed by the enclosure.
An operator situated in front of the SM6 switchboard during an internal fault
will not be exposed to the effects of arcing.
AMTED398078EN
bb Choice of exhaust:
(Installation requirements manual to be considered)
vv downwards exhaust
Civil engineering with an adequate volume is necessary.
vv upwards exhaust for SM6-24
A ceiling height greater or equal than 2150 mm is necessary, duct at the right or left
side of the cubicle (not supplied).
31
General characteristics
MV electrical network
management
PE56423
PE56421
PE15078
Control command
32
AMTED398078EN
General characteristics
MV electrical network
management
Easergy T200 I
PE56311
PE56422
PE56421
PE56423
Polarized connectors
PE57787
AMTED398078EN
33
MV electrical network
management
General characteristics
DE40552EN
Automation systems
Current
Execution time
b The automation systems can be switched on and off from the local operator panel
and disabled using the configurator.
b Switches can be controlled manually in the following circumstances:
v automation system switched off
v switch in local mode.
Voltage
drop
Sectionaliser (SEC)
Vn
SW2 voltage
O
Vn
O
T1
O
C
TR
TR
SW1
TR
T1 TR
SW2
O
T1
SW1
TR
C
O
TR
T2
Operating modes
TR
TR
SW2
DE59321EN
SW1 voltage
T1
Tg2
GE voltage
TR
TR
TR
TR
6s
GE Command
Tg1
SW
T2 TR
SWG
T2 TR
SWG
34
SW2
SW1 voltage
SW1
b The automation system counts the number of times a fault current followed
by a voltage loss is detected. It sends an open order if:
v the switch is closed
v the fault has disappeared
v the MV supply is absent.
b The automation system is reset at the end of the execution time delay.
SW1 voltage
The sectionaliser automation system opens the switch after a predefined number of
faults (1 to 4) during the voltage dip in the reclosing cycle of the top circuit breaker.
DE56654
DE59320EN
Time
b Configurable parameters:
v Number of faults: from 1 to 4
v Execution time: from 20 s to 4 mins configurable
in 5 s steps
v Automation system valid/invalid.
Changeover sequences:
Network ATS: in the event of voltage loss on the normal channel, changeover involves
opening the normal channel after time delay T1 and then closing the backup channel.
Note: in Auto mode, the sequence of return to the normal channel depends on
configuration of the Paralleling upon auto return option (see below).
Generator ATS: in the event of voltage loss on the network channel, changeover
involves sending the order for opening the network channel and at the same time
the Generator start-up order, after time delay T1.
The remainder of the changeover sequence depends on the management of
Generator channel closing (configurable option):
bb Case of Generator channel closing after start-up order:
After the Generator start-up order, the closing order is given to the Generator
channel, without waiting until the Generator is actually started.
bb Case of Generator closing after Generator power on:
The Generator channel closing order is sent only when Generator voltage is detected.
AMTED398078EN
General characteristics
MV electrical network
management
Automation systems
1
2
3
4
5
6
7
8
9
10
11
12
DI 1
DI 2
Priority channel
DI 3
DI 4
DI 5
Genset forcing
DI 6
DE56806
DE59175
Configurable parameters:
bb Automatic transfer system ON/OFF
bb Operating mode: Semi-Auto, Auto SW1, Auto SW2,
SW1 > SW2, SW2 > SW1
bb T1: 0 ms to 2 min. in increments of 100 ms
bb T2: 0 s to 30 min. in increments of 5 s
bb Disabling/enabling transfer upon fault detection:
bb Choice of voltage presence detection: DI4 or VD23
bb Channel connected to generator: SW1 or SW2
bb Type of automatic transfer system: Network ATS
or Generator ATS
bb Manual control enabled/disabled if ATS in operation
bb Paralleling enabled/disabled in auto and/or manual mode
bb Choice of type of changeover to Generator: immediately
or after detection of Generator power on
Changeover conditions
Relays are installed in factory in the T200 enclosure to provide interfacing with
the generating set (Generator ATS version only). Connection should be performed
as follows (see diagram opposite):
bb Voltage: contact closed if Generator started, to be wired on the two available
terminals (do not wire if detection of power on is performed by a relay VD23)
bb Start-up: Generator start-up order, to be wired on terminals C and B
bb Stop: Generator stoppage order, to be wired on terminals D and B.
Stop
Start-up
Genset
bb Upon transfer to the Generator, if the latter doesnt start, the automatic transfer
system waits for a period of 60 s at most before stopping changeover, then:
vv in SW > SWG mode: the automatic transfer system is locked and must be reset
(on the Control panel) to restart the device.
vv in SW <> SWG mode or in Auto mode: the automatic transfer system remains
operational.
If voltage returns to the network channel, the automatic transfer system requests
return to the network channel.
Generator Stop
Start
started
generator generator
contact
order
order
Interface with the generating set
DE59173
G
Source transfer locking
DO 1
Stop/start generator order
1
2
3
4
+5
6
bb When the automatic transfer system is configured with auto return on the network
channel, Generator stoppage is requested 6 s after the changeover sequence
is completed.
35
General characteristics
MV electrical network
management
Automation systems
DE56655
SW3
SW2
The BTA (Bus Tie Automatism) is an automation system for switching sources
between two incoming lines (SW1 and SW2) and a busbar coupling switch (SW3).
It must be used in conjunction with VD23 type voltage presence detectors and the fault
current detection function on the busbar incoming lines.
Operating mode
Normal position
SW1
SW3
SW2
Coupling sequence
DE59322EN
Active coupling
SW1
V2
SW2 voltage
SW3
V1
SW1 voltage
SW2
O
C
O
C
O
T1
SW1
T3
SW3
T2
Configurable parameters:
b Operating mode:
Standard/locking upon voltage loss
b Automatic return: SW1/SW2
b Automation system: on/off
b Delay before switching
T1: 100 ms to 60 s in 100 ms steps
b Delay before return
T2: 5 s to 300 s in 1s steps
b Interlock delay on voltage loss
T3: 100 ms to 3 s in 100 ms steps
b Motorisation type: command time
b Manual control: enabled/disabled in local and remote modes
if automation system in operation
b Paralleling: enabled/disabled in auto and (or) manual modes
b Transfer locking upon fault detection.
Coupling interlock
36
AMTED398078EN
General characteristics
PE57783
PE57784
Indication reset
b Automatic reset upon load current recovery (configurable time delay on Flair 22D
and Flair 23DM)
b Manual reset via front panel button
b Reset via external Reset input
b Reset by time delay: fixed (4 hr) for Flair 21D and adjustable using front
panel keypad (2 hr to 16 hr) for Flair 22D and Flair 23DM.
AMTED398078EN
37
General characteristics
Display principle
Sensors
The Flair 21D, 22D, 23DM range uses
an integrated detection system composed
of indicators and dedicated CTs.
Integrated sensors are normally placed
around the bushings. Split CTs can be
placed around cables for retrofit purposes.
Selection table
DE58715
Flair
Flair 21D
Flair 22D
Flair 23DM
Dual-powered
b (1)
Overcurrent
Earth-fault
Ammeter
Maximeter
External lamp
External reset
Test
Reset
L1
L2
L3
Power supply
I max.
Esc
Detection
Easergy
Flair 22D
EMS58352
Display
(4 digit LCD)
Connection diagrams
Self-powered
DM1000048
L2
L1
Description
Reset Indication
L3
Flair 22D
L2
L1
VPIS-VO
option
FLAIR 22D
Reset Indication
L3
L2
L1
SCADA
Reset
Standard applications
VPIS-VO
option +
(1)
FLAIR 23DM
(1) Com RS485
38
Flair 21D
Flair 22D
Fault detector for networks with very low load current (< 2 A) with
possibility of manual adjustments
Flair 23DM
AMTED398078EN
Ammeter
Functions
PE57786
General characteristics
Display principle
bb Load curents are permanently displayed
vv continuous scrolling of L1, then L2, then L3.
bb Maximeter
vv access to maximeter display by pressing a dedicated push button
vv continuous scrolling of M1, then M2, then M3
vv reset of all maximeter by pressing a combination of two push buttons.
Connections, assembly
Small size enclosure
bb DIN format: 93 x 45 mm
bb Secured, extraction-proff mounting
bb Terminal connections.
Current sensors
bb Split core CT for mounting on MV cables.
Technical data
DE58404
Application
Frequency
Load current
Measurement
Range
Reset of maximeter
Power supply
Self power
Battery
Auxiliary supply
Display
Amp 21D
L1
L2
L3
Minimum current
50 Hz and 60 Hz
3A
Phase current
Accuracy (I < 630 A)
Manual from device
3 to 630 A (resolution 1 A)
(2% + 2 digit)
Yes
I load 3 A
No
No
Display
Current per phase
Maximeter per phase
4 digits LCD
Yes (resolution 1A)
Yes
Phase CTs
3 split core CT
Test
Yes
Sensors
PE57233
Miscellaneous
AMTED398078EN
39
General characteristics
Series 10
Series 20
Simplicity
Easy to install
bb Light, compact base unit.
bb Optional modules fitted on a DIN rail, connected
using prefabricated cords.
bb User friendly and powerful PC parameter and
protection setting software to utilize all of Sepams
possibilities.
User-friendly
bb Intuitive User Machine Interface, with direct data
access.
bb Local operating data in the users language.
Protections
Current
Voltage
Frequency
Specifics
Applications
b
b
b
Phase and
earth fault
overcurrent
b
b
Breaker
failure
Disconnection
by rate of
change of
frequency
Substation
Busbar
Transformer
Motor
Generator
Capacitor
10A, 10B
S20
S24
10A, 10B
T20
M20
T24
Logic inputs
Logic outputs
Temperature sensors
Channel
0 to 10
4 to 8
4 to 8
0 to 8
0 to 8
Characteristics
Current
B21
3I + Io
0 to 10
3I + Io
Voltage
3V + Vo
LPCT (1)
Communication ports
IEC61850 Protocol
Control
B22
b
1
Matrix (2)
1 to 2
1 to 2
Other
Backup battery
Front memory
cartridge with settings
(1) LPCT: low-power current transformer complying with standard IEC 60044-8.
(2) Control matrix for simple assignment of information from the protection,
control and monitoring functions.
(3) Logipam ladder language (PC programming environment) to make full use
of Sepam series 80 functions.
(4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.
40
AMTED398078EN
General characteristics
Series 40
Protections
Current
Voltage
Frequency
Specifics
Applications
b
b
b
Series 60
b
b
b
b
b
b
b
b
b
Directional
earth fault
Directional
earth fault
and phase
overcurrent
S41, S43
S42
S60
T42
T60
Substation
Busbar
Transformer
Motor
Generator
Capacitor
S40
G40
G60
C60
Logic inputs
Logic outputs
Temperature sensors
Channel
0 to 10
0 to 28
4 to 8
4 to 16
0 to 16
0 to 16
Characteristics
T40
M41
b
b
b
b
b
b
Directional
earth fault
Directional
earth fault
and phase
overcurrent
S62
T62
M61
Current
3 I + Io
3 I + Io
Voltage
3V, 2U + Vo
3V, 2U + Vo or Vnt
LPCT (1)
Communication ports
IEC61850 Protocol
Control
Matrix (2)
Logic equation editor
1 to 2
1 to 2
b
b
b
b
G62
Logipam (3)
Other
Backup battery
Front memory cartridge
with settings
48 hours
(1) LPCT: low-power current transformer complying with standard IEC 60044-8.
(2) Control matrix for simple assignment of information from the protection, control and monitoring functions.
(3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions.
(4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.
AMTED398078EN
41
General characteristics
Series 80
Protections
Current
Voltage
Frequency
Specifics
Applications
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
Directional
earth fault
Directional
earth fault
and phase
overcurrent
Disconnection
by rate of
change of
frequency
Transformer
Machine
& transformer- differential
machine unit
differential
S82
T81
M81
T82
b
b
b
b
b
b
Capacitor-bank
unbalance
Substation
Busbar
Transformer
Motor
Generator
Capacitor
S80
B80
Logic inputs
Logic outputs
Temperature sensors
Channel
0 to 42
0 to 42
0 to 42
0 to 42
5 to 23
5 to 23
5 to 23
5 to 23
0 to 16
0 to 16
0 to 16
0 to 16
Characteristics
S81
b
b
b
S84
B83
G82
T87
M88
G88
M87
G87
C86
Current
3I + 2 x Io
2 x 3I + 2 x Io
3I + Io
2 x 3I + 2 x Io
Voltage
3V + Vo
3V + Vo
2 x 3V + 2 x Vo
3V + Vo
LPCT (1)
2 to 4
2 to 4
2 to 4
2 to 4
b
b
b
b
b
b
b
b
b
b
b
b
Backup battery
Communication ports
IEC61850 Protocol
Control
Matrix (2)
Logic equation editor
Logipam (3)
Other
(1) LPCT: low-power current transformer complying with standard IEC 60044-8.
(2) Control matrix for simple assignment of information from the protection, control and monitoring functions.
(3) Logipam ladder language (PC programming environment) to make full use of Sepam series 80 functions.
(4) Standard lithium battery 1/2 AA format, 3.6 V, front face exchangeable.
42
AMTED398078EN
General characteristics
PE57159
VIP 35
200
250
315
400
500
630
800
3
3.3
10
15
20
25
36
45
55
68
80
115
140
170
200
10
15
18
22
28
36
45
56
70
90
115
140
200
4.2
12
15
18
22
28
36
45
55
70
90
115
140
200
5.5
8*
12
15
18
22
28
36
45
55
68
90
115
140
170
8*
8*
10
12
18
20
25
36
45
55
68
80
115
140
170
200
6.6
8*
8*
10
12
15
18
22
28
36
45
56
70
90
115
140
200
10
8*
8*
8*
10
12
15
20
25
30
37
55
68
80
115
140
170
200
11
8*
8*
8*
8*
10
12
15
18
22
28
36
45
55
68
90
115
140
170
13.8
8*
8*
8*
8*
10
12
15
18
22
28
36
45
55
68
90
115
140
15
8*
8*
8*
8*
8*
10
15
18
20
25
36
45
55
68
80
115
140
170
200
20
8*
8*
8*
8*
8*
8*
10
12
15
20
25
30
37
55
68
80
115
140
170
200
22
8*
8*
8*
8*
8*
8*
10
12
15
18
22
28
36
45
55
68
90
115
140
170
170
PE57160
VIP 300 LL
Phase protection
bb phase protection is via two independently adjustable thresholds:
vv the lower threshold can be chosen to be inverse definite time or definite time.
The definite time curves are in conformity with IEC standard 60255-3.
They are either of inverse, very inverse or extremely inverse type.
vv the upper threshold is inverse definite time.
Earthing protection
bb protection against phase-to-earth faults uses the residual current measurement,
taken from the sum of the secondary currents in the sensors. This is taken via
a CRa X1 gauge: 10 to 50 A and X4: 40 to 200 A or via a CRb X1 gauge:
63 to 312 A and X4: 250 A to 1250 A.
bb as for phase protection, phase-to-earth protection had two thresholds
that can be independently set.
Signalling
bb two indicators show the origin of the trip operation (phase or earth).
They remain in position after the relay power supply has been cut.
two led indicators (phase and earth) show that the lower threshold
has been exceeded and that its time delay is currently in progress.
AMTED398078EN
43
General characteristics
Sepam series 10
19
24
200
250
315
400
500
630
800
1000
1250
1600
2000
2500
3000
38
48
61
77
96
121
154
192
241
308
385
481
577
3500
28
35
44
55
70
87
110
140
175
219
280
350
437
525
22
27
34
43
55
69
87
110
137
172
220
275
344
412
481
5.5
21
26
33
42
52
66
84
105
131
168
210
262
315
367
19
4.2
6.6
22
160
31
24
30
38
48
61
77
96
120
154
192
241
289
337
22
28
35
44
55
70
87
109
140
175
219
262
306
10
23
29
36
46
58
72
92
115
144
173
202
11
21
26
33
42
52
66
84
105
131
157
184
13.8
21
26
33
42
52
67
84
105
126
146
15
19
24
31
38
48
62
77
96
115
135
20
23
29
36
46
58
72
87
101
22
21
26
33
42
52
66
79
92
44
CRb 1250/1
AMTED398078EN
General characteristics
Code
Protection units
Sepam
series 10
50 - 51
b
50N - 51N b
67N
27
59
49
b
59N
46
51LR
66
37
b
Three-phase overcurrent
Zero-sequence overcurrent
Directional zero-sequence current
Undervoltage
Overvoltage
Thermal image
Zero-sequence overvoltage
Negative sequence overcurrent
Long start-up and rotor blocking
Maximum number of start-ups
Single-phase undercurrent
Communication
series 20
b
b
b
b
b
b
b
b
series 40
b
b
b
b
b
b
b
b
b
b
b
b
series 60
b
b
b
b
b
b
b
b
b
b
b
b
series 80
b
b
b
b
b
b
b
b
b
b
b
b
VIP
35
300
b (2)
b (3)
b (1)
b (1)
Weight
(kg)
Ratio of
Class of precision
transformation
CRa
Dimensions (mm)
External Internal Thickness
(without
fastening)
143.5
81
37.5
2.18
1/200
CRb
143.5
1.26
1/1250
CRc
143.5
81
81
37.5
37.5
S1-S2: 1/200
2% from 10 A to 100 A
On load 5.7 (cal. x 1)
1% from 100 A to 1600 A
1% from 10 A to 10 kA
On load 0.67 (cal. x 4)
1% from 10 A to 11 kA
On load 5.7 (cal. x 1)
1 % from 10 A to 25 kA
On load 0.67 (cal. x 4)
S1-S2:
On load 0.6
5% from 10 A to 80 A
2.5 % from 80 A to 600 A
S1-S3:
2% from 20 A to 2200 A
DE58402
S1-S3: 1/500
VIP 35
AMTED398078EN
45
General characteristics
Standard
applications
PE88012
Sepam series 20
Advantages
bb Consistent protection chain with the same sensor measures phase currents
from 5 A to 630 A
bb Simple to install and implement:
vv installation of LPCT sensors
-- TLP130 and TLP190 are installed around MV cable
-- CLP2 is installed on the MV circuit
vv LPCT connected directly to Sepam series 20, 40, 60 and 80
vv accessories available to test the LPCT protection chain by secondary current
injection.
bb LPCTs range of use
LPCT measuring and protection function guaranteeing the accuracy up to
the short-time current.
Following the range of use of LPCT:
vv from 5 A up to 1250 A respecting the error limits imposed by the accuracy class 0,5
vv from 1250 A up to 50 kA respecting the error limits imposed by the accuracy class 5P.
PE88011
Demanding
applications
PE88010
Custom
applications
DE58405EN
Sepam series 40
5.00
4.75
4.50
4.25
4.00
3.75
3.50
3.25
3.00
2.75
2.50
2.25
2.00
1.75
1.50
1.25
1.00
0.75
0.50
0.25
Ratio error
Protective class 5P
Measuring class 0.5
A
5
20
100
1000
1250
2000
3000
31500
40000
50000
MT11325
Connections
1 LPCT sensor, equipped with a shielded cable fitted with an RJ45 connector
to be connected directly to the card 3
2 Sepam series 20, 40, 60 and 80 protection unit
3 Card interface that adapts the voltage delivered by the LPCT sensors,
with microswitch setting of rated current.
vv CCA671 card for series 60 and 80
vv CCA670 card for series 20 and 40.
46
AMTED398078EN
General characteristics
PM100592
Applications
A battery ensures uninterrupted operation of the whole substation in the event of loss
of the main supply. The backup power supply unit:
bb Includes a regulated and temperature-compensated charger
bb Stops the battery before deep discharge
bb Carries out a battery check every 12 hours
bb Measures battery ageing
bb Forwards monitoring information via a Modbus communication port and
output relays.
PS100 benefits
Only one battery
The PS100 stops supplying power and reserves an additional energy backup
to restart the installation after an extended power interruption.
The additional energy backup can be enabled with a local pushbutton to provide
energy for restarting the protection relays and operating the MV switchgear.
Main features
bb DIN rail mounting for easy integration in any LV cabinet or MV/LV substation
bb 2 power supply outputs:
vv 12 Vdc - 18 W continuous - 100 W 20 s (for modem, radio, RTU, etc.)
vv 48 Vdc or 24 Vdc - 300 W /1 minute (for switchgear operating mechanism motors)
and 90 W / continuous for protection relays, electronic devices, etc.
bb RJ45 Modbus communication port
bb 2 output relays (AC supply ON, Battery ON)
bb Diagnosis with LEDs
bb 1 sealed lead-acid 12 V battery with a 10-year service life (from 7 Ah to 40 Ah)
bb Power supply paralleling available with a 2nd PS100
bb -40C to +70C operating temperature.
Range
bb PS100-48V
bb PS100-24V
bb Bat24AH
bb Bat38AH
AMTED398078EN
47
48
AMTED398078EN
Characteristics of
the functional units
Contents
AMTED398078EN
Switching
Protection
Metering
Other functions
50
50
52
60
62
Operating mechanisms
65
Auxiliaries
68
70
72
73
75
76
Protection of transformers
77
Interlocks
79
49
Characteristics of
the functional units
IM
Switch unit
IMC
Switch unit
DE53519
IMB
Switch unit with earthing switch
Right or left outgoing
DE53518
DE59700
Switching
kA
DE59711
DE59710
Electrical characteristics
Ik/1s
25
kA
Ima
62.5
20
50
Ir = 630 A
Ir = 630 A
16
40
12.5
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
36
31.25
kV
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
36
kV
Basic equipment:
Versions:
Optional accessories:
bb 630 A three-phase upper busbars for severe operating conditions for SM6-24
bb visibility of main contacts
bb pressure indicator device
bb enlarged low-voltage control cabinet for SM6-24
bb 50 W heating element for SM6-24
bb 630A cable connection by the top (no internal arc withstand if selected)
bb fault indicators
bb Connection pads for two dry-type single-core cables for 36 kV
bb digital ammeter
bb surge arresters (for SM6-36 and for SM6-24 in 500
mm width cubicle)
bb 630 A busbars earthing switch cabinet for SM6-24
(not available for internal arc IEC62271-200)
50
AMTED398078EN
Characteristics of
the functional units
Switching
NSM-busbars
Busbars power supply for
main incoming line on left (N) and
cables for standby line (S) on right
DE53561
DE58401
NSM-busbars
Cables power supply for
main incoming line on left (N) and
busbars for standby line (S) on right
DE53559
NSM-cables
Cables power supply for
main incoming line (N)
and standby line (S)
kA
DE59218
DE59212
Electrical characteristics
Ik/1s
25
kA
Ima
62.5
20
50
Ir = 630 A
Ir = 630 A
16
40
12.5
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
kV
31.25
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
kV
Basic equipment:
Optional accessories:
bb auxiliary contacts
bb key-type interlocks
bb 50 W heating element
bb control and monitoring
bb visibility of main contacts
bb pressure indicator device
bb 1250 A three-phase upper busbars
bb 630 A three-phase upper busbars for severe operating conditions
AMTED398078EN
51
Characteristics of
the functional units
Protection
Fuse-switch
DE53524
QMB
Fuse-switch combination unit
Outgoing line right or left
DE53523
QMC
Fuse-switch combination unit
DE59701
QM
Fuse-switch combination unit
kA
DE59713
DE59712
Electrical characteristics
Ik/1s
kA
25
25
20
20
Ir = 200 A
16
Ir =
63 A
12.5
12
17.5
24
36
Ir = 200 A
16
Ur
7.2
Isc
Ir =
63 A
12.5
kV
Ur
7.2
12
17.5
24
36
kV
Basic equipment:
Version:
Optional accessories:
52
AMTED398078EN
Characteristics of
the functional units
Protection
Fuse-switch
DE53526
PM
Fused-switch unit
DE59714
Electrical characteristics
kA
25
20
Ir = 200 A
16
Ir =
63 A
12.5
Ur
7.2
12
17.5
24
36
kV
Basic equipment:
Version:
Optional accessories:
AMTED398078EN
53
Characteristics of
the functional units
Protection
DM1-D
Single-isolation
disconnectable CB unit
Outgoing line on left
DE53533
DE53532
DM1-D
Single-isolation
disconnectable CB unit
Outgoing line on right
DE53531
DM1-A
Single-isolation
disconnectable CB unit
DE59715
Electrical characteristics
kA
25
20
Ir = 630 - 1250 A
16
12.5
12
17.5
24
Ur
36
kV
Basic equipment:
Version:
Optional accessories:
bb cubicle:
vv auxiliary contacts on the disconnector
vv protection using Sepam programmable electronic unit
vv three voltage transformers
vv key-type interlocks
vv 1250 A three-phase upper busbars at Ir 630 A
vv 630A cable connection by the top (no internal arc
withstand if selected)
vv 630 A three-phase upper busbars for severe operating conditions for SM6-24
vv enlarged low-voltage control cabinet for SM6-24
vv 50 W heating element for SM6-24
vv connection pads for two dry-type single-core cables for SM6-36
vv surge arresters
vv 630 A busbars earthing switch cabinet for SM6-24
(not available for internal arc IEC62271-200)
54
AMTED398078EN
Characteristics of
the functional units
Protection
DE53537
DM2
Double-isolation
disconnectable CB unit
Outgoing line on left
DE53536
DM2
Double-isolation
disconnectable CB unit
Outgoing line on right
DE58360
DM1-S
Single-isolation
disconnectable CB unit
with independent protection
kA
DE59721
DE59212-Isc
Electrical characteristics
Ik/1s & Isc
25
kA
25
20
20
Ir = 630 A
Ir = 630
16
16
12.5
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
kV
12.5
Ir = 400 - 630
7.2
12
17.5
Ur
24
36
kV
Basic equipment:
bb VIP relay
bb three CR sensors for VIP relay protection
bb voltage presence indicator
bb connection pads for dry-type cables
bb downstream earthing switch 2 kA rms making capacity
bb three CTs
bb 150 W heating element for SM6-36
Version:
Optional accessories:
bb cubicle:
vv key-type interlocks
bb cubicle:
vv protection using Sepam programmable electronic unit
vv auxiliary contacts on disconnectors
vv 2 voltage transformers phase-to-phase or 3 voltage transformers phase-to-earth
bb 630A cable connection by the top (no internal arc withstand if selected)
vv 50 W heating element for SM6-24
bb circuit breaker:
vv motor for operating mechanism
vv release units (coil)
vv operation counter on manual operating mechanism
AMTED398078EN
55
Characteristics of
the functional units
Protection
DE53539
DM1-Z
Withdrawable single-isolation CB unit
Outgoing line on right
DE53538
DM1-W
Withdrawable single-isolation
circuit breaker unit
kA
DE59226
DE59715
Electrical characteristics
Ik/1s & Isc
25
kA
25
20
20
Ir = 630 - 1250 A
Ir = 1250 A
16
12.5
16
Ir = 400 - 630 - 1250 A
7.2
12
17.5
24
Ur
36
kV
12.5
Ur
7.2
12
17.5
24
kV
Basic equipment:
bb three-phase busbars
Version:
Optional accessories:
bb cubicle:
vv auxiliary contacts on the disconnector
vv protection using Sepam programmable electronic unit
vv key-type interlocks
vv three voltage transformers for SM6-24
vv connection enclosure for cabling from above for
SM6-24
vv 50 W heating element for SM6-24
vv enlarged low-voltage control cabinet for SM6-24
bb circuit breaker:
vv motor for operating mechanism
vv release units (coil)
vv operation counter on manual
operating mechanism
56
AMTED398078EN
Characteristics of
the functional units
Protection
DMV-S
Single-isolation circuit breaker unit
with independent protection
DE53543
DE53542
DMV-D
Single-isolation circuit breaker unit
Outgoing line on right
DE53541
DMV-A
Single-isolation
circuit breaker unit
DE59227
Electrical characteristics
kA
25
20
Ir = 630 - 1250 A
16
12.5
12
17.5
Ur
24
kV
Basic equipment:
bb three CTs
bb Sepam series 20 programmable electronic unit
bb connection pads for dry-type cables
bb downstream earthing switch 25 kA rms making capacity
Optional accessories:
bb cubicle:
bb circuit breaker:
vv auxiliary contacts on the disconnector
vv motor for operating mechanism
vv three voltage transformers
vv release units (coil)
vv key-type interlocks
vv operation counter on manual operating mechanism
vv 50 W heating element
vv 1250 A three-phase upper busbars at Ir 630 A
vv 630 A three-phase upper busbars for severe operating conditions
vv enlarged low-voltage control cabinet
vv 630A cable connection by the top
(no internal arc withstand if selected)
AMTED398078EN
57
Characteristics of
the functional units
Protection
DMVL-D
Single-isolation disconnectable circuit breaker unit
Outgoing line on right
DE59703
DE53535
DMVL-A
Single-isolation disconnectable circuit breaker unit
kA
DE59717
DE59228
Electrical characteristics
Ik/1s & Isc
kA
25
25
20
20
Ir = 630 A
16
16
Ir = 630 A
12.5
Ur
7.2
12
17.5
24
kV
12.5
Ur
7.2
12
17.5
24
kV
Basic equipment:
Optional accessories:
bb cubicle:
bb circuit breaker:
vv auxiliary contacts on the disconnector
vv motor for operating mechanism
vv three voltage transformers
vv release units (coil)
vv key-type interlocks
vv operation counter on manual operating mechanism
vv 50 W heating element
vv 1250 A three-phase upper busbars at Ir 630 A
vv 630 A three-phase upper busbars for severe operating conditions
vv enlarged low-voltage control cabinet
vv Sepam relay protection
vv surge arresters
58
AMTED398078EN
Characteristics of
the functional units
Protection
DE53528
CVM
Disconnectable contactor unit with fuses
DE53527
CVM
Disconnectable contactor unit
kA
DE59221
DE59220
Electrical characteristics
Ik/1s & Isc
kA
Isc
25
10
20
Ir = 250 A
8
6.3
16
Ir = 400 A
Ur
7.2
12
12.5
kV
Ur
7.2
12
kV
Basic equipment:
bb vacuum contactor
bb disconnector and earthing switch
bb three-phase busbars
bb contactor operating mechanism with magnetic holding or contactor with mechanical latching
bb disconnector operating mechanism CS
bb one to three current transformers
bb auxiliary contacts on contactor
bb connection pads for dry-type cables
bb voltage presence indicator
bb downstream earthing switch 2 kA rms making capacity
bb operation counter on contactor
bb enlarged low-voltage control cabinet
bb mechanical interlocking between contactor and disconnector/earthing switch
bb equipment for three DIN striker fuses
bb mechanical indication system for blown fuses
bb auxiliary contact for blown fuses
Version:
Optional accessories:
bb cubicle:
vv auxiliary contacts on the disconnector
vv protection using Sepam programmable electronic unit
vv one to three voltage transformers
vv key-type interlocks
vv 50 W heating element
vv 1250 A three-phase upper busbars
vv 630 A three-phase upper busbars for severe operating conditions
bb contactor:
vv mechanical interlocking
bb DIN striker fuses
AMTED398078EN
59
Characteristics of
the functional units
Metering
CM2
Voltage transformers unit for network
with insulated neutral system
DE53547
DE53546
CM
Voltage transformers unit for network
with earthed neutral system
DE59722
Electrical characteristics
kA
Ik/1s
25
20
Ir = 50 A
16
12.5
Ur
7.2
12
17.5
24
36
kV
Basic equipment:
Optional accessories:
bb auxiliary contacts
bb mechanical signalling for blown fuses
bb auxiliary contact for blown fuses for SM6-24
bb 1250 A three-phase upper busbars
bb 630A cable connection by the top (no internal arc withstand if selected)
bb 50 W heating element for SM6-24
bb 630 A three-phase upper busbars for severe operating conditions for SM6-24
bb enlarged low-voltage control cabinet for SM6-24
60
AMTED398078EN
Characteristics of
the functional units
GBC-A
Current and/or voltage measurements unit
Outgoing line on right
GBC-A
Current and/or voltage measurements unit
Outgoing line on left
GBC-B
Current and/or voltage measurements unit
DE53551
DE53550
DE53549
Metering
DE59709
Electrical characteristics
kA
Ik/1s
Ir =
1250 A
25
20
Ir = 630 - 1250 A
16
12.5
12
17.5
24
Ur
36
kV
Basic equipment:
bb one to three CTs for SM6-24
bb three CTs for SM6-36
bb connection bars
bb three-phase busbars
bb 150 W heating element for SM6-36
Optional accessories:
AMTED398078EN
61
Characteristics of
the functional units
Other functions
GIM
Intermediate bus unit
DE58361
DE53552
GFM
Extension unit
Fluokit M36/SM6-36
DE53552
GEM
Extension unit
VM6/SM6
DE53553
GBM
Connection unit
Outgoing line right or left
Ir =
1250 A
25
kA
Ik/1s
25
20
20
Ir = 630 A
Ir = 630 - 1250 A
16
12.5
16
Ir = 400 - 630 - 1250 A
7.2
12
17.5
24
Ur
36
kV
Basic equipment:
bb connection bars
bb three-phase busbars for outgoing lines
right or left
bb 150 W heating element for SM6-36
Optional accessories:
62
kA
Ir = 400 - 630 A
7.2
12
17.5
bb metallic envelop
bb three-phase busbars
Ur
24
kV
Ik/1s
kA
25
25
20
20
16
12.5
DE59214
Ik/1s
DE59709_2
kA
DE59212
DE59709
Electrical characteristics
Ir =
630 A
12.5
24
Ir = 630 A
16
Ur
36
Ik/1s
kV
bb metallic
envelop
bb three-phase
busbars
12.5
Ir = 400 - 630 A
7.2
12
17.5
24
Ur
36
kV
bb metallic envelop
bb LV-continuity
AMTED398078EN
Characteristics of
the functional units
GAM2
Incoming-cable-connection unit
GAM
Incoming-cable-connection unit
DE53555
DE53554
Other functions
kA
DE59709
DE59719
Electrical characteristics
Ik/1s
Ir =
1250 A
25
20
Ir = 400 - 630 A
12
17.5
Ir =
1250 A
25
Ir =
630 1250 A
16
7.2
Ik/1s
20
Ir = 630 A
12.5
kA
Ir = 630 - 1250 A
16
Ur
24
36
kV
12.5
12
17.5
24
Ur
36
kV
Basic equipment:
bb three-phase busbars
bb voltage presence indicator
bb connection pads for dry-type cables
bb connection bars
bb 150 W heating element for SM6-36
bb downstream earthing switch 25 kA rms making capacity
bb operating mechanism CC for SM6-24
bb operating mechanism CS for SM6-36
Optional accessories:
bb fault indicator
bb digital ammeter
bb 1250 A three-phase upper busbars at Ir 630 A
bb enlarged low-voltage control cabinet for SM6-24
bb 630A cable connection by the top (no internal arc withstand if selected)
bb 50 W heating element for SM6-24
AMTED398078EN
bb auxiliary contacts
bb key-type interlocks
bb surge arresters for SM6-24
63
Characteristics of
the functional units
Other functions
EMB
Busbars earthing switch
cabinet
DE53558_N
DE53557
TM
MV/LV transformer unit
for auxiliaries
DE59704
SM
Disconnector unit
Ik/1s
Ir =
1250 A
25
kA
DE59212
kA
DE59722
DE59709
Electrical characteristics
Ik/1s
20
20
Ir = 630 - 1250 A
16
16
Ir = 400 - 630 - 1250 A
7.2
12
17.5
24
Ur
36
kV
12.5
Ur
7.2
12
17.5
24
36
kV
Basic equipment:
Optional accessories:
bb auxiliary contacts
bb key-type interlocks
bb 1250 A three-phase upper busbars at Ir 630 A
bb 630A cable connection by the top (no internal arc withstand if selected)
bb enlarged low-voltage control cabinet for SM6-24
bb 50 W heating element for SM6-24
bb 630 A three-phase upper busbars for severe operating conditions for SM6-24
bb digital ammeter for SM6-24
bb surge arrester for SM6-36
64
Ir = 630 A
Ir = 50 A
16
12.5
Ik/1s
25
25
20
kA
12.5
Ir = 400 - 630 A
7.2
12
17.5
Ur
24
kV
bb earthing switch
bb connection bars three phase
bb operating mechanism CIT
bb installation on 630 A IM 375 mm or
DM1-A units (not available for internal
arc IEC 62271-200)
bb require a key-type interlocks
adapted to the switchboard network
bb auxiliary contacts
AMTED398078EN
Operating mechanisms
Characteristics of
the functional units
Units
b
b
b
IM, IMB
IMC
PM
QM
QMC, QMB
v
v
v
b
b
Circuit breaker
CC
RI
P2
v
v
v(1)
v
v
b
b
b
b
b
b
NSM-cables, NSM-busbars
GAM 24 kV
EMB
b Provided as standard
v Other possibility
(1) Only SM6-36
(2) 1250 A version
CIT
CI1
CI2
CS
Load-break switch
Fused switch
Closing
Opening
Load-break switch
Fuse switch combination
Closing
Opening
Disconnector
Hand lever
Hand lever
Motor
Motor
1 to 2 s
1 to 2 s
Remote control
network management
Hand lever
Push button
Motor
Coil
4 to 7 s
35 ms
Remote control
transformer protection
Earthing switch
Manual operating mode
Closing
Hand lever
Closing
Hand lever
Load-break switch
Fuse switch combination
Mechanism Closing
Opening
charging
Hand lever
Push button Push button
Motor
Coil
Coil
4 to 7 s
55 ms
35 ms
Remote control
network management, need of quick
reconfiguration (generator source, loop)
N/A
Closing
Opening
Hand lever
Hand lever
Hand lever
Unit applications
Main circuit switch
Opening
Hand lever
Opening
Hand lever
Closing
Opening
Hand lever
N/A
N/A
N/A
Hand lever
N/A
N/A
Closing
Hand lever
Opening
Hand lever
61029N
AMTED398078EN
65
Characteristics of
the functional units
Operating mechanisms
61030N
61031N
61032N
61033N
66
AMTED398078EN
Characteristics of
the functional units
Operating mechanisms
PE57163
61035N
Undervoltage
SFset
Combinations
1
Combinations
4
b
b
b
b
b
AMTED398078EN
67
Characteristics of
the functional units
Auxiliaries
61036N
Un
Power supply
(V)
DC
24
48
110
125
220
AC (50 Hz)*
120
230
Motor option
(W)
(VA)
Operating time for CIT
Charging time for CI1, CI2
200
200
1 to 2 (s)
4 to 7 (s)
1 to 2 (s)
4 to 7 (s)
Opening releases
Shunt trip
Response time
Undervoltage
Pick-up
Hold
Response time
(W)
(VA)
(ms)
200
(W)
(VA)
(W)
(VA)
(ms)
160
250
300
300
300
35
400
35
750
280
550
50
45
40
400
55
750
4
45
Closing release
Shunt trip
Response time
(W)
(VA)
(ms)
200
250
300
300
300
55
PE57164
Un
Power supply
(V)
DC
24
48
110
125
220
AC (50 Hz)*
120
230
Motor option
Charging time
(W)
(VA)
(s)
300
380
15
15
(W)
(ms)
(W)
(VA)
(ms)
3
30
85
30
45
45
(W)
(VA)
(W)
(VA)
(ms)
160
Opening releases
Mitop (low energy)
Response time
Shunt trip
Response time
Undervoltage
Pick-up
Hold
Response time
180
280
550
50
55
40
10
55
Closing release
Shunt trip
Response time
(W)
(VA)
(ms)
85
180
65
65
68
AMTED398078EN
Characteristics of
the functional units
Auxiliaries
61035N
Threshold
Consumption
24/30
48/60
100/130
200/240
48/60
100/125
200/250
0.85 to 1.1 Ur
(VA or W)
180
Motor overcurrent
2 to 3 Ir during 0.1 s
Charging time
6 s max.
Switching rate
CH contact
10 A 240 V
Direct current
Threshold
Response time
to the circuit breaker at Ur
24
48
100/130
200/250
(Vdc)
24/30
48/60
100/130
200/250
Threshold
Consumption
0.7 to 1.1 Ur
(VA or W)
Response time
to the circuit breaker at Ur
50 ms 10
24
48
100/130
200/250
(Vdc)
24/30
48/60
100/130
200/250
Threshold
Consumption
0.85 to 1.1 Ur
(VA or W)
PE57842
Minimum
Maximum
Vdc
Vac
AMTED398078EN
48 V
480 V
10 A
60 W (L/R 150 ms)
700 VA (power factor 0.35)
125
680
20-41
250
640
20-40
69
Current transformers
for SM6-24
Characteristics of
the functional units
CVM
b
(*)
b
b
b
(*)
ARJP1
Transformer ARJP1/N2F
bb characteristics according to IEC standard 61869-2
bb single primary winding
bb double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
Ith (kA)
t (s)
Measurement
and protection
5A
5A
10
20
30
1.2
2.4
3.6
1
15 VA - class 0.5
2.5 VA - 5P20
50
6
75
10
100
10
150
10
200
10
Transformer ARJP1/N2F
bb characteristics according to IEC standard 61869-2
bb single primary winding
bb double secondary winding for measurement and protection.
ARJP1
5A
5A
50
100
6
10
1
15 VA - class 0.5
2.5 VA - 5P20
150
200
Transformer ARM3/N2F
bb characteristics according to IEC standard 61869-2
bb double primary winding
bb single secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
ARM3
I1n (A)
Ith (kA)
t (s)
Measurement and 5 A
protection
1A
5A
* For 5 A protection
10/20
20/40
5
12.5
1
0.8
7.5 VA - class 0.5
1 VA - 10P30
5 VA - 5P10
50/100
12.5/21*
1
100/200
12.5/25*
200/400
12.5/25*
300/600
25
200/400
25
300/600
25
5 VA - 5P15
ARM4
I1n (A)
Ith (kA)
t (s)
Measurement
and protection
(*) Consult us
70
5A
5A
5A
50/100
14.5
1
30 VA - class 0.5
5 VA - 5P15
7.5 VA - 5P10
100/200
25
7.5 VA - 5P15
15 VA - 5P10
Transformer ARM4
bb characteristics according to IEC standard 61869-2
bb single or double primary winding
bb up to 3 secondary windings (for measure and/or for protection)
bb rated highest voltage 7,2 - 12 - 17,5 - 24kV
bb rated primary current up to 630A (for SM6 cubicles)
bb secondary currents 5A or 1A
bb version with one secondary winding: ARM4/N1F
bb version with two secondary windings: ARM4/N2F
bb version with three secondary windings: ARM4/N3F
for further characteristics please consult us.
AMTED398078EN
Characteristics of
the functional units
Characteristics of
the functional units
Current transformers
for SM6-24
ARJP2
Transformer ARJP2/N2F
bb characteristics according to IEC standard 61869-2
bb single primary winding
bb double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
50
Ith (kA)
25
t (s)
ARJP3
Measurement
and protection
100
200
400
600
1
5A
10 VA
class 0.5
15 VA
class 0.5
15 VA
class 0.5
15 VA
class 0.5
20 VA
class 0.5
5A
2.5 VA
5P20
2.5 VA
5P20
5 VA
5P20
5 VA
5P20
7.5 VA
5P20
Transformer ARJP3/N2F
bb characteristics according to IEC standard 61869-2
bb single primary winding
bb double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
1000
Ith (kA)
25
PE55661
t (s)
1250
Measurement
and protection
1A
30 VA - class 0.5
1A
10 VA - 5P20
Measurement
and protection
5A
30 VA - class 0.5
5A
10 VA - 5P20
5A
100 A
1250 A
22.5 mV
0.5
5P
400
40 kA 1s
24 kV
50 kV
PE57162
AMTED398078EN
5A
100 A
1250 A
22.5 mV
0.5
5P
250
25 kA 1s
0.72 kV
3 kV
71
Characteristics of
the functional units
Current transformers
for SM6-36
For units DM1-A, DM1-D, SM6-36, DM2, IMC, GBC-A, GBC-B
PE57222
Transformer ARM6T/N1 or N2
bb characteristics according to IEC standard 61869-2
bb double primary winding
bb double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
50-100
Ith (kA)
16 - 20
25
t (s)
5A
30 VA class 0.5
5A
2.5 VA - 5 VA - 5P20
10 VA 5P20
Measurement
and protection
Current transformer ARM6T
Transformer ARM9T
bb characteristics according to IEC standard 61869-2
bb double primary winding
bb double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
1000/1250
Ith (kA)
40
t (s)
Measurement
and protection
Current transformer ARM9T
1
5A
5A
10 VA - 5P20
PE57162
72
TLP 130
TLP 190
5A
5A
1250 A
2500 A
Secondary output
22.5 mV - 100 A
22.5 mV - 100 A
0.5
0.5
5P
5P
250
400
25 kA 1 s
40 kA 1 s
0.72 kV
0.72 kV
3 kV
3 kV
AMTED398078EN
Characteristics of
the functional units
Voltage transformers
for SM6-24
Synthesis table by unit
VTs
VRQ2-n/S1
VRFR-n/S1
VRC2/S1
VRM3-n/S2
VCT24
VRC1/S1
Units CM
CVM
b
b
b
b
TM
b
b
b
VRQ2
24
10/3
100/3
250
Accuracy class
0.5
30
15/3
15-20/3
30
20/3
30
30-50
VRC2
17.5
10/3
100/3
250
Accuracy class
0.5
30
15/3
24
10
100
500
Accuracy class
0.5
50
15
20
PE55648
First secondary
Second secondary
AMTED398078EN
12
17.5
24
10/3
15/3
20/3
100/3 - 100/3
200
Accuracy class
0.5
30-50
100
Accuracy class
3P
Rated output
50
73
Characteristics of
the functional units
Voltage transformers
for SM6-24
VRC1
7.2
3.3
5.5
6.6
110
100
110
100
110
300
Accuracy class
0.5
100
DE53562
24
10
220
Output (VA)
2500
15
20
2500
2500
4000
4000
DE58408
Surge arresters
For units IM500, DM1-A, DM1-W, GAM, DMV-A*, DMVL-A
In (A)
400/630
Un (kV)
7.2
10
12
17.5
24
Note: the rated voltage of the surge arrester is according to units rated voltage.
(*) limited up to 17.5 kV for DMV-A circuit breaker cubicles.
74
AMTED398078EN
Characteristics of
the functional units
Voltage transformers
for SM6-36
PE57223
36
303
333
1003
1003 or 1103
450
Accuracy class
0.5
3P
30-50
30
PE57224
36
30
33
100
100 or 110
700
Accuracy class
0.5
50-100
For units TM
Transformer VRC3/S1 (phase-to-phase)
bb single primary winding
bb single secondary
bb characteristics according to IEC standard 61869-3
36
30
220
1000
DE58408
Surge arresters
For units IM, DM1-A, SM, GAM2
AMTED398078EN
In (A)
630
Un (kV)
36
75
Characteristics of
the functional units
Example:
Consider a 950 kW motor at 5 kV.
In =
pf
= 130 A
Id = 6 x In = 780 A
Then select the next higher value, i.e. 790 A.
For six 5-second starts per hour, select fuses
rated 200 A.
Note: the same motor could not be protected for 12 starts
per hour since the maximum service voltage for the required
250 A rated fuses is 3.3 kV.
76
Service
voltage (kV)
3.3
6.6
Starting
current (A)
30
Id = 6 x Ie
Ie
1100
183
250
250
250
942
157
250
250
250
250
250
250
785
131
200
200
200
200
200
250
628
105
160
160
160
200
200
200
565
94
160
160
160
160
160
160
502
84
125
160
160
160
160
160
439
73
125
125
125
160
160
160
377
63
100
125
100
125
125
160
314
52
100
100
100
100
100
125
251
42
100
100
100
100
100
100
188
31
80
100
100
100
100
100
126
21
50
50
63
80
80
80
AMTED398078EN
Characteristics of
the functional units
Protection of transformers
PE57161
Fuse ratings for SM6 protection units such as PM, QM, QMB and QMC depend,
among other things, on the following criteria:
bb service voltage
bb transformer rating
bb fuse technology (manufacturer)
Different types of fuses with medium loaded striker may be installed:
vv Solefuse fuses as per standard UTE NCF 64.210
vv Fusarc CF fuses as per IEC 60.282.1 recommendation and dimensions are related
to DIN 43.625 standard.
For fuse-switch combination unit type QM, QMB, QMC, refer only to the selection
table and reference list of fuses. For all other type of fuses, consult us.
Example: for the protection of a 400 kVA transformer at 10 kV, select either Solefuse
fuses rated 43 A or Fusarc CF fuses rated 50 A.
Type of
fuse
Service
Transformer rating (kVA)
Rated
voltage
25
50
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 voltage
(kV)
(kV)
Solefuse (UTE NFC standards 13.100. 64.210)
5.5
6.3 16
31.5 31.5 63
63
63
63
63
7.2
10
6.3 6.3 16
16
31.5 31.5 31.5 63
63
63
63
15
6.3 6.3 16
16
16
16
16
43
43
43
43
43
63
20
6.3 6.3 6.3 6.3 16
16
16
16
43
43
43
43
43
63
24
Solefuse (general case, UTE NFC standard 13.200)
3.3
16
16
31.5 31.5 31.5 63
63
100 100
7.2
5.5
6.3 16
16
31.5 31.5 63
63
63
80
80
100 125
6.6
6.3 16
16
16
31.5 31.5 43
43
63
80
100 125 125
10
6.3 6.3 16
16
16
31.5 31.5 31.5 43
43
63
80
80
100
12
13.8
6.3 6.3 6.3 16
16
16
16
31.5 31.5 31.5 43
63
63
80
17.5
15
6.3 6.3 16
16
16
16
16
31.5 31.5 31.5 43
43
63
80
20
6.3 6.3 6.3 6.3 16
16
16
16
31.5 31.5 31.5 43
43
63
24
22
6.3 6.3 6.3 6.3 16
16
16
16
16
31.5 31.5 31.5 43
43
63
Fusarc CF and SIBA(1) (general case for QM, QMB and QMC cubicle according to IEC 62271-105)
3.3
16
25
40
50
50
80
80
100 125 125 160(1) 200(1)
7.2
5
10
16
31.5 40
40
50
63
80
80
125 125 160(1)
5.5
10
16
31.5 31.5 40
50
50
63
80
100 125 125 160(1) 160(1)
6
10
16
25
31.5 40
50
50
63
80
80
125 125 160(1) 160(1)
6.6
10
16
25
31.5 40
50
50
63
80
80
100 125 125 160(1)
10
6.3 10
16
20
25
31.5 40
50
50
63
80
80
100 100 125(1) 200(1)
12
11
6.3 10
16
20
25
25
31.5 40
50
50
63
80
100 100 125(1) 160(1)
13.8
6.3 10
16
16
20
25
31.5 31.5 40
50
50
63
80
80
100(1) 125(1) 125(1) 17.5
15
6.3 10
10
16
16
20
25
31.5 40
50
50
63
80
80
100(1) 125(1) 125(1)
20
6.3 6.3 10
10
16
16
25
25
31.5 40
40
50
50
63
80
100(1) 125(1) 24
22
6.3 6.3 10
10
10
16
20
25
25
31.5 40
40
50
50
80
80
100(1)
(2)
Fusarc CF for dry type transformers
30
10
10
16
20
25
31.5 31.5 50
50
63
63
36
31.5
10
10
16
20
25
25
31.5 50
50
63
63
33
6.3
10
16
20
25
25
31.5 40
50
50
63
34.5
6.3
10
16
20
25
25
31.5 40
50
50
63
Fusarc CF oil immersed type transformers (2)
30
10
10
16
20
25
31.5 31.5 40
40
50
63
36
31.5
10
10
16
20
25
31.5 31.5 40
40
50
63
33
10
10
16
20
25
25
31.5 31.5 40
40
50
34.5
10
10
16
20
25
25
31.5 31.5 40
40
50
77
Protection of transformers
Characteristics of
the functional units
DE53563
Fuses dimensions
Solefuse (UTE standards)
55
DE57467
35
23
450
Ur
(kV)
Ir
(A)
L
(mm)
(mm)
Weight
(kg)
7.2
6.3 to 125
450
55
12
100
450
55
17.5
80
450
55
24
6.3 to 63
450
55
Ur
(kV)
Ir
(A)
L
(mm)
(mm)
Weight
(kg)
7.2
125
292
86
3.3
12
6.3
292
50.5
1.2
10
292
50.5
1.2
16
292
50.5
1.2
20
292
50.5
1.2
25
292
57
1.5
31.5
292
57
1.5
40
292
57
1.5
50
292
78.5
2.8
63
292
78.5
2.8
80
292
78.5
2.8
100
292
78.5
2.8
6.3
442
50.5
1.6
10
442
50.5
1.6
16
442
50.5
1.6
20
442
50.5
1.6
25
442
57
2.2
31.5
442
57
2.2
40
442
57
2.2
50
442
78.5
4.1
63
442
78.5
4.1
80
442
86
5.3
10
537
50.5
1.8
16
537
50.5
1.8
25
537
57
2.6
31.5
537
78.5
4.7
40
537
78.5
4.7
50
537
86
6.4
63
537
86
6.4
Ur
(kV)
Ir
(A)
L
(mm)
(mm)
Weight
(kg)
7.2
160
292
85
3.8
200
292
85
5.4
125
292
67
160
292
85
3.8
200
292
85
3.8
17.5
125
442
85
5.4
24
100
442
85
5.4
125
442
85
5.4
35
45
33
33
23
24
36
DE57467
SIBA
45
12
33
78
33
23
AMTED398078EN
Characteristics of
the functional units
Interlocks
Switch units
Functional interlocks
These comply with IEC recommendation 62271-200 and EDF specification HN 64-S-41
(for 24 kV).
In addition to the functional interlocks, each disconnector and switch include:
bb built-in padlocking capacities (padlocks not supplied)
bb four knock-outs that may be used for keylocks (supplied on request)
for mechanism locking functions.
Unit interlock
Circuit-breaker units
Units
DE53565
A1
C1 C4 A3
b
A4
b
A5
50
52
P1
b
P2
P3
P5
CVM
NSM
GAM
b
b
SM
DM2
Key-type interlocks
A1 type
O
Outgoing units
Aim:
bb to prevent the closing of the earthing switch on a transformer protection unit
unless the LV circuit breaker is locked in open or disconnected position.
DE53566
Interlock
C1 type
bb to prevent the access to the transformer if the earthing switch for transformer
protection has not first been closed.
S
C4 type
S
O
MT20240EN
DE53567
AMTED398078EN
free key
captive key
panel or door
79
DE53568
Characteristics of
the functional units
Interlocks
A3 type
Ring units
Aim:
bb to prevent the closing of the earthing switch of a load-side cubicle
unless the line-side switch is locked open.
A4 type
A5 type
bb to prevent the closing of the earthing switch of the casing unit unless
the downstream and the upstream switches are locked in the open position.
O
S
MT20240EN
DE53570
DE53569
80
free key
captive key
panel or door
AMTED398078EN
Interlocks
DE53572
Characteristics of
the functional units
P1 type
O
DE53573
bb to prevent the closing of an earthing switch if the switch of the other unit
has not been locked in the open position.
P2 type
X
bb to prevent on-load operation of the disconnector unless the switch is locked open
bb to prevent the closing of the earthing switches unless the disconnector and
the switch are locked open.
DE53574
P3 type
AX
DE53575
bb to prevent on-load operation of the disconnector unless the switch is locked open
bb to prevent the closing of the earthing switches with the unit energised, unless
the disconnector and the switch are locked open
bb to allow off-load operation of the switch.
P5 type
bb to prevent the closing of the earthing switch of the incoming unit unless
the disconnector and the switch is locked open.
DE53571
Functional interlocks
50 type
O O
Prevents
bb on-load switching of the disconnectors.
Type 52
Prevents
bb on-load switching of the disconnectors.
O O
Allows
bb off-load operation of the contactor with the disconnectors open (double isolation).
bb off-load operation of the contactor with the disconnector open (single isolation).
MT20240EN
DE59203
Allows
bb off-load operation of the circuit breaker with the disconnectors open (double isolation).
bb off-load operation of the circuit breaker with the disconnector open (single isolation).
AMTED398078EN
free key
captive key
panel or door
81
82
AMTED398078EN
Connections
Contents
AMTED398078EN
84
84
85
85
86
87
88
89
89
90
90
83
Connections
Selection table
PE57840
PE50775
PE50776
Round connector
Square connector
X-section mm2
Supplier
Number of cables
Comments
3 to 24 kV
400 A - 630 A
Round connector
50 to 240 mm2
1 or 2 per phase
3 to 24 kV
1250 A
Round connector
50 to 630 mm2
1 or 2 per phase
y 400 mm2
Square connector
X-section mm2
Supplier
Number of cables
Comments
3 to 24 kV
400 A - 630 A
Round connector
50 to 240 mm2
1 per phase
3 to 24 kV
1250 A
Round connector
50 to 630 mm2
1 per phase
Note:
b The cable end terminals, covered by a field distributor, can be square,
b PM/QM type cubicle, round end connections 30 mm max.
84
AMTED398078EN
Connections
Cable positions
945
SM
945
IMC
400
PM, QM
400
QMC
400
CVM
430
DM1-A
430
DMVL-A
430
DMV-S
320
DM1-W
370
GAM2
760
GAM
470
620
DMV-A
320
313
DM1-S
543
CVM
DE58677
1250 A
DE58676
630 A
IM, NSM-cables,
NSM-busbars, SM
DE58678
Cable-connection height H
measured from floor (mm)
945
320
320
200
200 200
420
200 200
420
200
420
DE53581
DE58679
GAM, GAM2
H
H
200
275
165 165
313
DMV-A (1250 A)
DE58656
DE58417
DE58655
200
420
333
200 200
420
510,5
330
789
200 200
420
145 145
445
X
313
X = 330
X = 268
X = 299
AMTED398078EN
371,5
: 1 single-core cable
: 2 single-core cables
: Three core cable
85
Connections
Trenches depth
DE53585
625
b Through trenches: the trench depth P is given in the following table for usual dry
single-core cables type (for tri-core cables consult us).
b With stands: to reduce depth P or avoid trenches, by placing the units on 400 mm
concrete footings.
b With floor void: the trench depth is given in the following table for usual types of
cables.
500
375
630 A
Cable
section
(mm2)
1250 A
All cubicles
expect ...
Other cubicles
DMVA
CVM
12.5
kA/1s
12-16
kA/1s
12.5
kA/1s
16
kA/1s
12.5 kA/1s
16
kA/1s
SM,
GAM
DM1A, DMV-A,
DM1-W
12-16
kA/1s
12-16 kA/1s
Depth P (mm)
S < 120
187.5
330
550
550
330
550
330
550
550
800
Opposite to
Under the
550
circuit breaker: circuit breaker:
330
450
S > 400
1000
1400
100
DMV-A, DMV-S
For single cables
DE57179
100
630 A units
DM1-A, DM1-W
For single-core cables
DE57178
DE57177
DE57176
100
100
100
445
P
480
600
740
86
600
50
740
600
840
50
740
50
740
50
AMTED398078EN
Connections
630 A units
Rear entry or exit
with conduits
DE57181
100
630 A units
Front entry or exit
with conduits
100
100
P2
P3
P1
600
25
IM
25
25
IM
QMC
IM
IM
IM
DM1
DM1
DE57182
DE57180
IM
PE50797
On each 630 A unit of the range, except those including a low-voltage control cabinet
and EMB compartment, the connection is made with dry-type and single-core cables.
Remarks:
bb Not available for internal arc IEC 62271-200.
bb Not available in 1250 A.
AMTED398078EN
87
Connections
Cubicles
XG (mm) X (mm)
XD (mm)
375
All
57.5
260
57.5
500
GAM
Other
57.5
182.5
260
260
182.5
57.5
625
QMC
Other
307.5
57.5
260
510
57.5
57.5
750
All
432.5
260
57.5
XG
X
XD
5
minimu50
m
70
50
740
70
50
110 min
.
930
90 min
.
120
DE57196
b (mm)
125
95
375
345
500
470
625
595
750
720
21
minimu50
m
4 x M8
3
minimu30
m
100
50
740
600
88
AMTED398078EN
Connections
Selection table
Single-core cables
CableBending
section
radius
(mm2)
(mm)
Units 630 A
IM, IMC, QM, CM, CM2,
PM, DM1-A, GAM, GAM2,
SM, TM
Depth P (mm)
P1
P2
1 x 35
525
350
550
1 x 50
555
380
580
1 x 70
585
410
610
1 x 95
600
425
625
1 x 120
630
455
655
1 x 150
645
470
670
1 x 185
675
500
700
1 x 240
705
530
730
Note: the unit and the cables requiring the greatest depth
must be taken into account when determining the depth P
for single-trench installations. In double-trench installations
must be taken into account to each type of unit and cable
orientations.
100
100
P2
300
IM
100
AMTED398078EN
100
QM
100
200
200
P2
300
1000
1000
IM
100
P1 P2
200
QM
DE59724
DE59723
Trench diagrams
100
100
200
1000
QM
IM
IM
IM
IM
100
100
100
200
100
89
Connections
Cable positions
Side view
DE59730
GAM2 unit
DE57184
DM1-A units
DE57183
QM, PM units
DE59727
IM, SM units
1210
540
400
350
350
700
350
380
700
700
350
632
456
700
380
350
350
DE57185
Front view
IM, SM
QMC
GAM
GAM2
QM, PM
DM1-A
1200
620
490
375
375
750
90
1000
620
540
470
750
375
750
455
375
510
750
1000
AMTED398078EN
Installation
AMTED398078EN
Contents
92
93
95
96
97
98
99
91
DE57186
Installation
Unit type
90
Exhaust
channelling
840
Base
footprint
IM,IMB
Height
H (mm)
1600 (1)
Width
(mm)
375/500
Depth
D (mm)
1030
Weight
(kg)
130/140
IMC
1600 (1)
500
1030
210
1600 (1)
375/500
1030
140/160
QMC
1600 (1)
625
1030
190
CVM
2050
750
1030
400
1600 (1)
750
1230
410
DM1-S
1600 (1)
750
1230
350
DMV-A, DMV-D
1695 (1)
625
1115
350
DMV-S
1600 (1)
625
1115
270
CM
1600 (1)
375
1030
200
CM2
1600 (1)
500
1030
220
GBC-A, GBC-B
1600 (1)
750
1030
300
NSM-cables, NSM-busbars
2050
750
1030
270
GIM
1600
125
930
40
GEM (2)
1600
125
930/1060 (2)
40/45
GBM
1600
375
1030
130
GAM2
1600
375
1030
130
GAM
1600
500
1030
SM
1600 (1)
TM
1600
170
130/160
375
1030
210
750
1230
430
(1) Add to height 450 mm for low-voltage enclosures for control/monitoring and protection functions.
To ensure uniform presentation, all units (except GIM and GEM) may be equipped with
low-voltage enclosures.
(2) Depending on the busbar configuration in the VM6 unit, two types of extension units may be
used:
b to extend a VM6 DM12 or DM23 unit, use an extension unit with a depth of 1060 mm
b for all other VM6 units, a depth of 930 mm is required.
(3) For the 1250 A unit.
92
AMTED398078EN
IM, IMB, PM, QM, QMB, SM, IMC, QMC, CM, CM2
1600
840
1600
840
90
30
70
30
70
DE58665
840
1600
1600
30
70
930
1060
930
450
DE58668
DE58667
GBC-A, GBC-B
503
1600
90
840
AMTED398078EN
30
70
GEM
1600
90
840
90
GIM
DE58664
GAM
1600
DE58666
90
GBM, GAM2
DE58663
450
DE58662
DE58661
Installation
100
1600
90
840
30
70
93
503
840
450
1600
1600
90
450
DE58670
DE58669
Installation
200
100
90
840
1600
200
100
330
90
200
100
DE58673
DMV-A 1250 A
DE58672
DMV-A 630 A
832
840
1680
1680
100
150
90
840
85 445
85
74
100
90
100
DE58675
DMV-S
DE58674
DMV-D
840
1600
1680
100
90
150
85
840
94
100
90
840
85
100
AMTED398078EN
Civil engineering
for SM6-24
Installation
Ground preparation
DE100520
To obtain the internal arc performance, ground implementation must comply with
the following requirements:
bb Straightness: 2 mm / 3 m (Rep.1)
bb Flatness: 3 mm maximum (Rep.2)
All the elements allowing the evacuation of the gas (duct, casing, etc.) must be able
to bear a load of 250 kg/m2.
1
Cubicle
front face
2
Fixing of units
AMTED398078EN
95
Installation
DE58657
PE57168
930
300
(minimum)
25 (minimum)
DE58658EN
930
300
(minimum)
25 (minimum)
or 50 (evacuation by the top)
Evacuation duct
PE57235
569
400
400
1600
Duct
(not supplied)
Coupling flange
(supplied)
96
AMTED398078EN
Installation
Height
(mm)
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
2250
IM, SM
IMC, IMB
QM, PM, QMB
QMC
DM1-A
DM1-D
GIM
DM2
CM, CM2
GBC-A, GBC-B
GBM
GAM2
GAM
GFM
Depth (1)
(mm)
1400 (3)
1400 (2)
1400 (3)
1400 (3)
1400 (2)
1400 (2)
1400
1400 (2)
1400 (2)
1400 (3)
1400 (3)
1400 (3)
1400 (3)
1400
Width
(mm)
750
750
750
1000
1000
1000
250
1500
750
750
750
750
750
250
Weight
(kg)
310
420
330
420
600
560
90
900
460
420
260
250
295
100
(1) The depth measures are given for the floor surface.
(2) The depth in these units are 1615 mm with the enlarged low voltage compartment.
(3) The depth in these units are 1500 mm with the standard low voltage compartment.
Dimensions
DM1-A, DM1-D, DM2 units
215
AMTED398078EN
32
2250
2250
2250
1400
215
DE59664
DE59662
100
DE59663
1400
32
1400
32
230
97
Civil engineering
for SM6-36
Installation
Ground preparation
Fixing of units
A
B
50
DE5961
150
1100
1400
150
14.2 x 25
98
B (mm)
Unit type
750
650
1000
900
DM2
1500
1400
GIM
250
150
AMTED398078EN
Installation
Side view
DE59665
Top view
100
100
5200 min.
(2)
min.
1770 min.
100
100
100
DE59667
Top view
3430 min.
100
1715 min.
100
AMTED398078EN
99
100
AMTED398078EN
Appendices
Order form
Contents
Appendices
Trip curves for VIP 300 LL or LH relays
102
103
Fusarc CF fuses
104
Solefuse fuses
105
Order form
SM6 - Switching
Switching
Automatic Transfer System
SM6 - Protection
AMTED398078EN
106
106
107
Circuit breaker
Fuse switch
Vacuum contactor (Direct Motor Starter) for 24 kV
108
108
110
111
SM6 - Metering
112
113
114
115
116
117
101
Appendices
t>
t>
t >>
t >>
Is 1.2 Is
10 Is
I >>
Is 1.2 Is 10 Is
I >>
VI curve
t (s)
DE53615
t (s)
100
100
10
10
1
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
0.1
0.1
I/Is
0.01
1 1.2
10
I/Is
0.01
1 1.2
100
EI curve
10
100
RI curve
t (s)
DE53616
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
t (s)
1000
10
100
1
10
0.6
0.4
0.3
0.2
0.15
1
0.1
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
0.1
0.01
1 1.2
102
10
I/Is
100
0.1
0.07
0.05
I/Is
0.01
1
10
100
AMTED398078EN
Appendices
DE53617EN
10
0.1
Type
0.01
I/Is
0 1.2
AMTED398078EN
10
15
20
25
30
103
Fusarc CF fuses
Appendices
250 A
160 A
125 A
100 A
31.5 A
40 A
50 A
63 A
80 A
10 A
16 A
20 A
25 A
4A
1000
8
6
4
6.3 A
DE53618
Time (s)
8
1000
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
10
100
8
10000
Current (A)
8
6
4
Ia
8
1.
Ik
Is
Ik
250 A
200 A
160 A
125 A
100 A
80 A
63 A
50 A
40 A
10
8
31.5 A
25 A
20 A
16 A
6
4
10 A
6.3 A
1
8
4A
6
4
0.1
0.1
10
100
104
AMTED398078EN
Solefuse fuses
Appendices
1000
8
6
4
16 A
20 A
25 A
31.5 A
43 A
63 A
80 A
6.3 A
10 A
DE53620
Time (s)
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
10
100
8
1000
8
10000
Current (A)
100
8
6
4
Ia
8
1.
Ik
Is
Ik
2
125 A
100 A
80 A
63 A
10
43 A
31.5 A
25 A
20 A
16 A
10 A
8
6
4
6.3 A
2
1
8
6
4
0.1
0.1
10
100
AMTED398078EN
105
Order form
SM6
Switching
Basic cubicle
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
16 kA 1s for SM6-36
Type of cubicle
24 kV
SM 375
IM 375
SM 500 (for1250 A)
IM 500
36 kV
SM 750
Position in the switchboard
IMC 500
IMB 375
IM 750
IMC 750
IMB 750
First on left
Direction of lower busbars for IMB
Middle
Last on right
Right
36 kV
Options
Common options
Replacement of CIT by
CI1
Signalling contact
CI2
24 Vdc
110 Vdc
32 Vdc
120-125 Vdc
48 Vdc
137 Vdc
60 Vdc
220 Vdc
Interlocking
A3 SM6-SM6
P1 SM6-SM6
On switch
On earthing switch
Cubicle no.
SM cubicle only
P3 SM6-SM6
P2 SM6-SM6
Replacement of 630 A upper busbar by 1250 A (not possible for IMB)
Digital ammeter or
fault current indicator
AMP 21D
Flair 21D
Flair 22D
Flair 23DM
SM6-24 options
Remote control signalling
2 lights
2 lights and 2 PB
Voltage of the lights (must be the same than electrical driving mechanism)
24 V
48 V
110/125 V
Roof configuration (A, B or C only one choice possible)
220 V
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core
B - Low voltage control cabinet (h = 450 mm)
2 x single core
With unpunched door
C - Wiring duct
Cable connection by the bottom (not applicable on IMB, cable maxi 240 mm2)
Three core
Single core
2 x single core
12 kV
17.5 kV
24 kV
50 W heating element
Surge arresters for IM 500
7.2 kV
10 kV
Operation counter
CTs for IMC (quantity)
2
1
Busbar field distributors for severe conditions (only for 630 A)
Internal arc version (not possible with top incomer option) 16 kA 1s
Gaz exhaust direction
Downwards (only for 16 kA 1s)
3
20 kA 1s
Upwards
SM6-36 options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Cable connection by the bottom (2 x single core, cable maxi 240 mm2, not applicable on IMC)
Surge arresters (not applicable on IMB, IMC cubicles)
36 kV
106
AMTED398078EN
Order form
SM6
Switching
Basic cubicle
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
NSM busbar
NSM busbar
NSM cable
NSM cable
NSM cable
First on left
Incoming bottom busbar for NSM busbar
Middle
Last on right
Left
Cable connection by the bottom (cable maxi 240 mm2) for NSM cable
Three core on both
Stand by source
Right
English
Spanish
Chinese
Options
Common options
Signalling contact
1C on SW and 1O & 1C on ES
Operation counter
Interlocking SM6-SM6
Right cubicle
2 x P1
1 x A3
Right cubicle
Left cubicle
On switch
On earthing switch
2 x A3 Right cubicle
On switch
On earthing switch
Left cubicle
On switch
On earthing switch
DNP3
IEC 101/204
FFSK
RS485
PSTN
GSM
FSK
SM6-24 options
2 heating elements
Busbar field distributors for severe conditions (only for 630 A)
Internal arc version (not possible with top incomer option)
16 kA 1s
Gaz exhaust direction
Downwards (only for 16 kA 1s)
AMTED398078EN
20 kA 1s
Upwards
107
Order form
SM6
Protection
Circuit breaker
Basic cubicle
Quantity
Common 24/36 kV
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
16 kA 1s for SM6-36
DM1-A 750
DM1-S 750
DM1-Z 750
DM1-W 750
DMV-S
DMV-D right
DMVL-A
DMVL-D
DMV-A
DM1-A 1000
First on left
Circuit breaker
Middle
Last on right
See specific order form
Cable connection by the bottom (1x single core, cable maxi 240 mm2)
36 kV
Basic SM6-24
Busbar (Ir u Ir cubicle)
For DM1-A, DM1-S, DM1-W, DMVL-A, DMVL-D ,DM1-D, DM2
630 A
1250 A
630 A
1250 A
For DMV-S
630 A
400 A
For DM1-A, DM1-D, DM1-W, DM1-Z
1250 A
Protection
For DM1-S, DMV-S
48/60 Vdc
Voltage of signalling
48/60 Vdc
110/125 Vdc
220/250 Vdc
220/240 Vac (50 Hz)
Basic SM6-36
Current sensors
Options
108
CT
AMTED398078EN
Order form
SM6
Protection
Circuit breaker
Options
Common options
Interlocking
C1
C4
SM6-24 options
Roof configuration (not applicable on DMV-A, DMV-S, DMV-D)
(A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core
2 x single core
1 set
2 sets
DM2
B - Low voltage control cabinet
DM2
C - Wiring duct
1 cabinet
2 cabinets
DM2
1 set
Other cubicles
1 set
2 sets
Surge arrester
50 W heating element
Replacement of 630 A upper busbars 400-630 A by 1250 A
Busbar field distributors for severe conditions (only for 630 A)
Internal arc version (not possible with top incomer option)
16 kA 1s
Gaz exhaust direction
Downwards (only for 16 kA 1s)
20 kA 1s
Upwards
SM6-36 options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Cable connection by the bottom (for DM1-A only)
3 x 2 x single core cable maxi 240 mm2
Surge arrester
Sepam relay protection
AMTED398078EN
36 kV
See specific order form
109
Order form
SM6
Protection
Fuse switch
Basic cubicle
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
16 kA 1s for SM6-36
Type of cubicle
SM6-24
QM 375
QMB 375
QMC 625
PM 375
QMB 750
QMC 1000
PM 750
Middle
First on left
Current transformers for QMC 24 kV (to see price structure)
Last on right
QM 500
SM6-36
QM 750
Position in the switchboard
Quantity of CTs
Right
36 kV
Options
Common options
Fuses (see fuse price structure)
Service voltage y 12 kV
Replacement of mechanism
Shunt trip
24 Vdc
110 Vdc
32 Vdc
120-125 Vdc
48 Vdc
137 Vdc
60 Vdc
220 Vdc
24 Vdc
110 Vdc
32 Vdc
120-125 Vdc
48 Vdc
137 Vdc
60 Vdc
220 Vdc
1C on SW and 1O & 1C on ES
2 O & 2 C on SW
Interlocking
A1
C4
C1
SM6-24 options
Replacement of mechanism
48 V
110/125 V
220 V
Blown fuse signalling contact (mechanical indication PM, electrical for the other cubicles)
Roof configuration (A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core
B - Low voltage control cabinet (h = 450 mm)
2 x single core
With unpunched door
C - Wiring duct
50 W heating element
Operation counter
Digital ammeter (not applicable for QMB)
AMP21D
20 kA 1s
Upwards
SM6-36 options
Replacement of mechanism
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
110
AMTED398078EN
Order form
SM6
Protection
Basic cubicle
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
7.2
(A)
12.5 kA 1s
First on left
Middle
Last on right
400 A
630 A
1250 A
1 CT
2 CT
Busbar Ir
Phase current sensors
3 CT
3 LPCT ring type
Options
MV fuses
25 A
31.5 A
40 A
80 A
100 A
125 A
160 A
Busbar field distributors for severe conditions (only for 630 A)
Key interlockings for C1 type
63 A
250 A
1
Internal arc version (not possible with top incomer option)
Gaz exhaust direction
50 A
200 A
16 kA 1s
20 kA 1s
Upwards
Contactor
Vacuum contactor
Open release
Closing coil
AMTED398078EN
Magnetic hold
Mechanical latching
48 Vdc
125 Vdc
250 Vdc
110 Vac/dc
120 Vac/dc
125 Vac/dc
220 Vac/dc
240 Vac/dc
250 Vac/dc
111
Order form
SM6
Metering
Basic cubicle
Quantity
Common SM6-24/SM6-36
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
16 kA 1s for SM6-36
CM
CM2
TM
GBC-A
GBC-B
CM
CM2
TM
GBC-A
GBC-B
CM
CM2
TM
GBC-A
GBC-B
GBC-A
GBC-B
CM 750
CM2 750
GBC-A 750
TM 750
GBC-B 750
Middle
Last on right
First on left
Direction of lower busbars for GBC-A
Left
Right
1 O and 1 C on SW
See fuse price structure
SM6-36
Basic SM6-24
VTs for GBC (to see price structure)
CTs for GBC (to see price structure)
Phase/phase
Quantity
Phase/earth
2
1 secondary
1 high secondary
2 secondaries
1 low secondary
Basic SM6-36
Voltage transformers
Options
SM6-24 options
Roof configuration (A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core
B - Low voltage control cabinet (h = 450 mm)
C - Wiring duct
2 x single core
With unpunched door
1 O and 1 C
20 kA 1s
Upwards
SM6-36 options
Current transformers and voltage transformers for GBC
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Replacement of 630 A busbar by 1250 A (for CM, CM2 and TM only)
112
AMTED398078EN
Order form
SM6
Other functions
Basic cubicle
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
(kA)
Rated current Ir
(A)
16 kA 1s for SM6-36
GAM 500
GAM2 375
GBM 375
GAM 500
GAM2 375
GBM 375
GAM 500
GBM 375
GAM 750
GAM2 750
GBM 750
First on left
Direction of lower busbars for GBM
Middle
Last on right
Right
SM6-36
Options
SM6-24 options
Roof configuration (A, B or C only one choice possible)
A - Cable connection by the top (cable maxi 240 mm2 with VPIS)
Single core
B - Low voltage control cabinet (h = 450 mm)
2 x single core
With unpunched door
C - Wiring duct
Wiring duct for GBM
ES auxiliary contact (only on GAM 500)
1 O and 1 C
10 kV
12 kV
17.5 kV
SM6-24
A3 SM6-SM6
P5 SM6-SM6
Cubicle no.
Flair 22D
Flair 23DV
20 kA 1s
Upwards
SM6-36 options
Cable connection by the top (single core cable maxi 240 mm2 with VPIS)
Replacement of 630 A busbar by 1250 A (for GAM2 only)
Surge arresters for GAM2
AMTED398078EN
113
Order form
SF1
by
Only one of the boxes (ticked X or filled
the needed value) have to be considered between each
horizontal line.
Green box X corresponds to none priced functions.
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
Impulse voltage Up
(kVbil)
(kA)
Rated current Ir
(A)
Frequency
Mechanism position
60 Hz
50 Hz
A1
B1
Disconnectable
Withdrawable
B1
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
125 Vdc
Undervoltage release YM
24 Vdc
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
Mitop
125 Vdc
Without contact
With contact
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
125 Vdc
Undervoltage release YM
24 Vdc
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
Mitop
125 Vdc
Without contact
With contact
Remote control
Electrical motor M
2432 Vdc
110127 Vdc/ac
4860 Vdc/ac
220250 Vdc/ac
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
125 Vdc
French
English
Leaflets language
114
2
1
1
1
1
1
1
1
1
AMTED398078EN
Order form
SFset
Lateral disconnectable
for SM6-24
by
Only one of the boxes (ticked X or filled
the needed value) have to be considered between each
horizontal line.
Green box X corresponds to none priced functions.
Quantity
Rated voltage Ur
(kV)
Service voltage
(kV)
Impulse voltage Up
(kVbil)
(kA)
Rated current Ir
630 A maximum
Frequency
60 Hz
50 Hz
A1
B1
Mechanism position
Colour for push buttons and indicators
Push buttons open/close: Red/black
Indicator open/close: Black/white
Operating mechanism charged/discharged: White/yellow
CSa 200/1
Is = 10 to 50 A
Is = 40 to 200 A
electrical characteristics)
CSb 1250/1
Is = 63 to 312 A
Is = 250 to 1250 A
VIP 300LL
CSa 200/1
Is = 10 to 50 A
Is = 40 to 200 A
CSb 1250/1
Is = 63 to 312 A
Is = 250 to 1250 A
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
125 Vdc
Undervoltage release YM
24 Vdc
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
125 Vdc
Remote control
Electrical motor M
2432 Vdc
110127 Vdc/ac
4860 Vdc/ac
220250 Vdc/ac
60 Vdc
220 Vdc
30 Vdc
110 Vdc
48 Vdc
125 Vdc
French
English
1
1
1
1
115
Order form
Evolis
Quantity
12
Service voltage
17.5
(kV)
25 kA
630
1250
Phase distance
185 mm
2430 Vdc
100130 Vdc/ac
48 Vac
Low energy release Mitop
4860 Vdc
200250 Vdc/ac
100125 Vdc
200250 Vdc
4860 Vdc/ac
Shunt closing release XF
100130 Vac
200240 Vac
24 Vac
2430 Vdc
100130 Vdc/ac
48 Vac
4860 Vdc
200250 Vdc/ac
If locks
2 identical locks
1 lock
Disabling of O/C circuit breaker push buttons
116
1
1
2 different locks
1
1
AMTED398078EN
Order form
Evolis
Quantity
24 (kV)
Rated voltage Ur
Service voltage
(kV)
Impulse voltage Up
(kVbil)
630 A maximum
Phase distance
250 mm
Mechanism position
B1
110 Vdc
48 Vdc
125-127 Vdc
220 Vdc
Undervoltage release YM
24 Vdc
110 Vdc
48 Vdc
125-127 Vdc
220 Vdc
110 Vdc
48 Vdc
125-127 Vdc
220 Vdc
Undervoltage release YM
24 Vdc
110 Vdc
48 Vdc
125-127 Vdc
220 Vdc
2432 Vdc
110127 Vdc/ac
4860 Vdc/ac
220250 Vdc/ac
110 Vdc
48 Vdc
125-127 Vdc
220 Vdc
1
1
1
1
1
1
1
117
Notes
118
AMTED398078EN