Professional Documents
Culture Documents
I.
This work has been supported by the Polish State Committee for
Scientific Research under Contracts No. 11239/T10/2003/25.
0,4 kV
Rk = 0,12 om/km
Xk = 0,4 om/km
110 kV
X0/X1=3, l = 10 km
20 kV
Rk = 0,164 om/km
Xk = 0,17 om/km
X0/X1=3, l = 0,2 km
20 kV
Al 4x25 mm2
Load 5
100 m
110 kV
l = 1 km
Rk = 0,12 om/km
Xk = 0,4 om/km
X0/X1=3, l = 20 km
110/20 kV
10 MVA
10 %
P = 3 MW
tg = 0,4
l = 1 km
P = 3 MW
tg = 0,4
20/0,4 kV
63 kVA
4,5 %
100 m
Load 4
100 m
Load 3
Load 2
300 m
Load 1
WT
PV
III.
Prime mover
Permanent magnet alternator
Three-phase 6D rectifier
Three-phase 6T PWM inverter
flat
voltage-current
Figure 4. RMS phase voltages and voltage unbalance factor at the PCC after
DERs connection
Figure 3. RMS phase voltages and voltage unbalance factor at the PCC
before DERs connection
Figure 5. RMS phase voltages and voltage unbalance factor at the PCC after
DERs connection and with DSTATCOM in operation
IV.
1 ,2
b
0 ,8
a
0 ,6
0 ,4
0 ,2
0 ,0
0
B. Simulation studies
It has been assumed that voltage dips occurring in the LV
grid result from short-circuits in the HV supplying network.
The studies focused on the assessment of DSTACOM
capabilities in reducing the depth of dips. Simulation studies
were performed for different types of short-circuits. To obtain
voltage dips of variable depth short-circuits were modeled in
various location along the AC line of 20 km length. Fault
duration time was assumed to be 0,2 s which resulted from
protection operation. As an example, the compensation effect is
illustrated in Fig. 6 for the three-phase voltage dip of 0,5 Un.
Summary results of simulation studies have been gathered
in Fig. 7 and 8 which show voltage dips observed on the LV
busbars during three- and single phase faults as the function of
short-circuit location in the 110 kV line. Distance 0 km in the
figures indicates a fault in A station, distance 20 km indicates
a short-circuit in C station, which in case of symmetrical fault
causes short interruption in supply (voltage dip of value equal
to 0). The influence of leakage reactance of the distribution
transformer has also been investigated.
Voltageia
Napiec
compensation
Uf with
z kompens
ac ja
1.20
without
compensation
Uf bez
kompensac
ji
V o l ta g(p.u
e ).
1.00
0.80
0.60
0.40
0.00
0.40
0.50
0.60
Time (s)
0.70
0.80
0.90
1.00
1 ,0
U [jw]
U [p.u.]
0 ,8
a
0 ,6
0 ,4
0 ,2
0 ,0
0
10
12
14
16
18
10
12
14
16
18
20
l [k m ]
CONCLUSIONS
0.20
0.30
1 ,0
[jw]
UU[p.u.]
20
l [k m ]
REFERENCES
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]