Introduction...............................................................................2
Residential Power Distribution...................................................4
Load Centers.............................................................................6
Load Center Construction..........................................................8
Residential Circuit Breakers..................................................... 16
Ground Fault Protection...........................................................23
Arc Fault Protection.................................................................25
Surge Protection......................................................................30
Load Center Mains..................................................................35
Load Center Interrupting Ratings.............................................38
Service Entrance Equipment Load Centers.............................41
Power Supply Systems............................................................42
Load Center Grounding............................................................45
Siemens Ultimate Load Centers..............................................48
Siemens EQ Load Centers......................................................50
Special Application Load Centers............................................52
Load Center Catalog Numbers................................................54
Sizing The Load Center............................................................56
AC Disconnects.......................................................................65
Residential Metering...............................................................66
Review Answers...................................................................... 71
Final Exam...............................................................................72
Introduction
Load Center
Additional
Load Center
A/C Disconnect
Conductors
NEC Article 310
Lighting
NEC Article 410
Services
NEC Article 230
Load Center
NEC Article 408
Overcurrent Protection
NEC Article 240
Switches
NEC Article 404
Branch Circuits
NEC Article 210, 220
Grounding
NEC Article 250
Load Centers
Definition
Accesible Only
From the Front
Mounted in or
Against a Wall
Placed in a
Cabinet or
Cutout Box
Used to Control
Light, Heat, or
Power Circuits
Review 1
1.
a. true
b. false
Knockout
NEMA Enclosures
Removing Knockouts
Interior
Interior
Bus Bars
Bus Bars
Power Source
10
Split Neutral
Neutral
Connections
Insta-Wire
Neutral
Connections
11
Label
12
Trim Assembly
Trim
Door
Twistouts
Integral,
Adjustable,
Upper Pan
13
Circuit Directory
Ground
(If Req'd)
1
240V 3
5
7
9
240V11
13
GFCI 15
17
19
21
23
25
27
29
31
33
35
37
39
14
Review 2
1.
15
16
Circuit Breaker
17
Mechanical
Link
From
Power
Source
To Load
From
Power
Source
2-Pole Circuit Breaker
To Load
18
Branch
Circuit
Breakers
19
Circui
t Break
er and
TVS
GFCI Breaker
er an
d
TYPE QPF
TEST
AFCI Breaker
TYPE
40 C
QAFH
ARC
FAULT
GND
HACR
SWD
Circuit Breaker
Combination Ty
AFC
AFCI
15
Interrupting Rating
22kA 120V
Max. RMS Sym.
50/60 Hz
TEST
10707150001
1-Pole QP
2-Pole QP
QP Circut Breakers
QT Duplex
QT Triplex
Type QP circuit breakers are full-size breakers available as 1pole, 2-pole, or 3-pole breakers. Full size means that each circuit
breaker has a width of 1 inch per pole.
1-pole QP breakers are rated for 120 VAC and have continuous
current ratings from 10 to 70 amps.
2-pole QP breakers are available with a 120/240 VAC rating
or a 240 VAC rating. 2-pole 120/240 VAC QP breakers have
continuous current ratings from 10 to 125 amps and 2-pole 240
VAC QP breakers have continuous current ratings from 15 to
100 amps.
3-pole QP breakers are rated for 240 VAC and have continuous
current ratings from 10 to 100 amps.
All type QP circuit breakers have a 10 kA interrupting rating;
however, Siemens also offers type QPH circuit breakers with a
22 kA interrupting rating and type HQP circuit breakers with a
65 kA interrupting rating.
20
QT Circuit Breakers
Type QT Duplex circuit breakers combine two independent halfinch width breaker poles in a common unit. This unit plugs into
one load center stab and requires one panel space.
QT Duplex
Two Independent 1-Pole Breakers
Requires One Space
21
Review 3
1.
22
TYPE QPF
TEST
Trip Coil
Sensing and
Test Circuit
23
24
Arc Faults
Line-to-Ground Arc
Load
Load
Neutral
Neutral
Load
Neutral
26
ON
Last Known
Trip Condition
Overcurrent
Arc Fault
Arc Fault to
Ground
LED 1
LED 2
TYPE
40 C
QAFH
ARC
FAULT
GND
HACR
SWD
Circuit Breaker
Combination Ty
AFC
AFCI
15
Interrupting Rating
22kA 120V
Max. RMS Sym.
50/60 Hz
Test
Button
TEST
10707150001
3
OFF
OFF
ON
ON
LED 1
LED 2
LED 3
AFCI
ARC
FAULT
TEST
GND
TEST
ARC
FAULT
HACR SWD
Test
Buttons
LISTED
27
Intelli-ArcTM
20+A
30+mA
COMM
PWR
5A
AMPS
PWR
GF
AF
DANGER
Hazardous voltage.
Will cause death or serious injury.
This device necesitates working or near
equipment with exposed electrical hazards
Turn off and lock out power supplying
equipment before connecting this tool.
Ensure a safe work zone before energizing
equipment for testing purposes.
COMM
CLEAR
SAFETY INSTRUCTIONS
This tool must be installed and operated
only by a qualified electrician
This tool is intended for temporary
installation only. Never leave the work site
with this tool connected.
Always replace all doors and covers before
departing from the work site.
120V, 60HZ, 20A Max.
(Power consumption: 50mA)
Intelli-ArcTM
Wire: 60/75o C
AWG: CU#14-8 /AL#12-8
Termination torque: 25 lb-in
STRIP
GAGE
Wire Terminals
(to Breaker)
HOT
NEUTRAL
HOT
LOAD
Hand-held Unit
CIRCUIT
BREAKER
NEUTRAL
Base Unit
28
Wire Terminals
(to Load)
Intelli-ArcTM
COMM
PWR
DANGER
Hazardous voltage.
Will cause death or serious injury.
This device necesitates working or near
equipment with exposed electrical hazards
Turn off and lock out power supplying
equipment before connecting this tool.
Ensure a safe work zone before energizing
equipment for testing purposes.
SAFETY INSTRUCTIONS
This tool must be installed and operated
only by a qualified electrician
This tool is intended for temporary
installation only. Never leave the work site
with this tool connected.
Always replace all doors and covers before
departing from the work site.
Pigtail
GAGE
HOT
Load-side Neutral
(4 ft. min.)
Branch Circuit
Wire: 60/75o C
AWG: CU#14-8 /AL#12-8
Termination torque: 25 lb-in
STRIP
HOT
LOAD
AFCI or GFCI
Breaker
CIRCUIT
BREAKER
Line-side Hot
Load-side Hot
(4 ft. min.)
NEUTRAL
NEUTRAL
Load
Base Unit
Neutral Bar
Intelli-ArcTM
COMM
PWR
DANGER
Hazardous voltage.
Will cause death or serious injury.
This device necesitates working or near
equipment with exposed electrical hazards
Turn off and lock out power supplying
equipment before connecting this tool.
Ensure a safe work zone before energizing
equipment for testing purposes.
SAFETY INSTRUCTIONS
This tool must be installed and operated
only by a qualified electrician
This tool is intended for temporary
installation only. Never leave the work site
with this tool connected.
Always replace all doors and covers before
departing from the work site.
Wire: 60/75o C
AWG: CU#14-8 /AL#12-8
Termination torque: 25 lb-in
STRIP
GAGE
HOT
Panel Neutral
(4 ft. min.)
Neutral Bar
29
NEUTRAL
HOT
LOAD
Conventional
Breaker
Branch Circuit
CIRCUIT
BREAKER
Line-side Hot
Load-side Hot
(4 ft. min.)
NEUTRAL
Base Unit
Load
Surge Protection
30
Thunderstorms
20
<10
30
50
30
20
10
20
30
60
40
30
40
70
50
50
<10
40
60
40
70
80
30
100
60
90
80
70
Circ
uit
Break
er a
nd TV
SS
31
The Circuit Breaker and SPD incorporates two red LED indicator
lights that illuminate to show that surge protection is provided
for all circuits connected to the load center. The Circuit Breaker
and SPD notifies the owner of loss of surge protection by
tripping one or both of the circuit breakers. The value of this
feature is enhanced by using one of these breakers for circuit
protection of frequently used household circuits so that the
circuits controlled by the breaker indicate the status of the
surge protection capability.
Phase Indicators
CAUTION
L2
On-Full Protection
Off-No Proection
L1
DANGER
HAZARDOUS VOLTAGE
Disconnect all power supplying this equipment before replacing.
Failure to do so will result in death or serious injury.
32
Load Center/Panelboard
Black
2-Pole
20 Amp
Black
Circuit Breaker
Neutral Bus
For a service entrance
panel, the neutral and
ground bus are both
grounded.
Ground Bus
33
White
Green
HAZARDOUS VOLTAGE
DANGER
CAUTION
Off-No Proection
On-Full Protection
L2
TPS3 A9040
Point-of-Entry SPD
Phase Indicators
L1
Review 4
1.
a. bathroom
b. living room
c. outdoors
d. near sinks
a. line-to-ground arcs
b. high energy parallel arcs equal to or greater than 75 A
c. series arcs greater than or equal to 5 A
d. all the above
34
Main Breaker
Individual Protection
200 Amp
Circuit Breaker
200 Amp
Circuit Breaker
35
36
Main Breaker
Load Center
Main Lug Only
Load Center
There are two ways to supply power to a main lug only load
center from the main breaker load center. One way is to
connect power from a branch circuit breaker in the main breaker
load center. The other way is to install a lug kit in the main
breaker load center and route power from the installed lugs to
the downstream load center.
37
There are two ways to meet this requirement. The full rating
method requires selection of circuit protection devices with
individual ratings equal to or greater than the available fault
current. In single family homes, the available fault current
normally does not exceed 10,000 amperes. This makes it
inexpensive to use the full rating method,
In some instances the available fault current may exceed 10,000
amperes. For example, in the case of a building with 22,000
amperes of fault current available at the service entrance,
every circuit breaker must have an interrupting rating of at least
22,000 amperes as shown in the following example.
38
Series Rated
The series rated method also requires that the main upstream
circuit protection device must have an interrupting rating equal
to or greater than the available fault current of the system, but
subsequent downstream circuit protection devices connected
in series can be rated at lower values. For example, a building
with 22,000 amperes of available fault current might have the
breaker at the service entrance rated at 22 kA IR and additional
downstream branch breakers rated at a lower value. In this
example, the downstream branch circuit breaker is rated at
10kAIR.
22,000 Amps
Available Fault Current
O
N
O
N
O
F
F
O
F
F
22 kA IR
10 kA IR
39
Main Breaker
65,000 amps IR
Tenant
Main Breakers
22,000 Amps IR
Branch Breakers
10,000 Amps IR
in Tenant Load Center
Modular Metering
40
Service
Entrance
Maximum Number of
Disconnects for Service
Entrance Equipment
Load Center
Homes built prior to 1936, especially in rural areas, used a twowire supply system. This system provided 120 volts between
a hot conductor and a grounded conductor. A 2-wire system is
usually inadequate for todays residential electrical demands and
is not allowed for new construction.
Hot
120 Volts
Ground
Branch Circuits
42
Neutral
240 Volts
120 Volts
Branch Circuits
43
44
45
Service Entrance Grounding When installing a load center, it is important to ground the
neutral bus only at the service entrance as shown in the
following illustration. This is accomplished by connecting a
grounding electrode to the neutral bus. The neutral bus is
bonded to the enclosure at the service equipment so that
the enclosure is also connected to ground. In addition, the
grounded neutral connection from the power source is also
connected to the load center neutral bus.
Service Entrance
Load Center
Transformer Secondary
Neutral
Grounding Electrode
Bonding
46
Grounding Downstream
Load Centers
Downstream
Load Center
Neutral
Neutral
Main
Lugs 1-Pole
Branch
Breaker
Neutral Grounded
At Service Entrance
120 V Load
120 V Load
Review 5
1.
47
49
50
51
Non-critical
Circuits
Main
Breaker
Automatic
Transfer Switch
Generator Backed Up
Critical Circuits
Main Breaker
Load Center
Riser Panels
Extra Space
for Riser Cables
Riser Panel
Renovation Panels
Trailer Panels
Spa Panels
53
Part 1
=
=
=
=
=
Part 2
Part 3
Part 4
Part 5
=
=
=
Part 6
Part 7
=
=
=
=
=
Combination
Surface
Flush
Feed Through Lugs
Ground Bar Factory Installed
54
Part 8
Part 9
Review 6
1.
a. They are convertible from main breaker to main lug
and vice versa.
b. They incorporate a number of innovative features to
save installation time.
c. They are only available with an indoor enclosure.
2. Siemens Ultimate load centers are available for 12 to
_____ circuits and 100 to _____ A.
3. Which of the following types of load centers are
included in the Siemens EQ load center line? List all
that apply.
55
56
Air Conditioner
Bathroom
Living Room
Dining Room
Master
Bedroom
Bathroom
Kitchen
Closet
Range
Linen Closet
Dishwasher
Utility Room
Bedroom
Refrigerator
Bedroom
Entry
Closet
Load Center
Garage
This sample floor plan is for a 2000 square foot home that has
a 9600 VA (240 volts x 40 amps) air conditioner, a 9600 VA (240
volts x 40 amps) electric range, 12,000 VA (240 volts x 50 amps)
of electric heating, a 5000 VA (240 volts x 20.8 amps) clothes
dryer, a 1500 VA (120 volts x 12.5 amps) dishwasher, and a
1176 VA (120 volts x 9.8 amps) garbage disposal. Three small
appliance circuits will be used in the kitchen area.
Note: A thorough knowledge of the National Electrical Code
is required to properly size load centers and conductors. If you
will be performing these task, you are encouraged to become
familiar with this code.
General Lighting Load
57
Laundry Circuit
Demand Factors
6000 VA
4500 VA
1500 VA
Total
12,000 VA
3000 VA
3150 VA
58
9600 VA
5000 VA
12,000 VA
9600 VA
Air conditioner and electric heat will not be used at the same
time. Only the larger of the heater load or air conditioner load
is used (NEC Article 220.82(C)). In this case, the heater load
(12,000 VA) is greater than the air conditioner load (9600 VA).
All other large appliance loads must be calculated at 100%
except for the electric range. NEC Table 220.55 allows a
demand factor for electric ranges. Not all burners will normally
be on high at the same time. According to Table 220.55, an
electric range with a rating not greater than 12,000 watts can
have a demand factor of 8000 watts. For the purpose of this
calculation, assume that the power factor is 0.9, this results
in an apparent power rating for the electric range of 8889 VA
(8000watts divided by 0.9).
Electric heat
Electric clothes dryer
Electric range
12,000 VA
5000 VA
8889 VA
Required Service
1500 VA
1176 VA
Total miscellaneous
appliance load
2676 VA
6150 VA
25,889 VA
2676 VA
Total load
34,715 VA
Determining the Number of Calculating the number of circuits required in a load center
Circuits
involves an understanding of how circuits are configured. In the
following example, a 120/240 volt power supply is connected to
a 16-space/circuit load center.
120 Volts
240 Volts
120 Volts
A
Connected to A Phase
Circuit Breaker
Positions
1
3
5
7
9
11
13
15
B
N
2
4
6
8
10
12
14
16
Circuit Breaker
Positions
Connected to B Phase
60
120 Volts
240 Volts
120 Volts
B
N
5
7
6
8
9
11
10
12
13
14
15
16
61
120 Volts
240 Volts
120 Volts
B
N
5
7
9
11
6
8
10
12
13
14
15
16
Air Conditioner
62
There are three 120 volt, 20 amp small appliance loads. Three
20 amp circuit breakers are required.
Laundry Circuit
Dishwasher Circuit
The dishwasher and garbage disposal are 120 volt loads. The
dishwasher is a 120 volt, 12.5 amp (1500 VA 120 volts) device.
12.5 A x 1.25 = 15.6 A
20 amp wiring and a 20 amp circuit breaker should be used.
64
AC Disconnects
Disconnect Enclosure
Fused Disconnect
GND
GND
Fused
Disconnect
Non-Fused
Disconnect
65
GND
Residential Metering
66
Meter Combos
Meter Main
EUSERC Meter Main
EUSERC
Meter Load Center
Combination
67
Meter Mains
Group Metering
SERVICE
DISCONNECT
SERVICE
DISCONNECT
SERVICE
DISCONNECT
SERVICE
DISCONNECT
SERVICE
DISCONNECT
68
69
Review 7
1.
70
Review Answers
71
Final Exam
You can test your knowledge by taking the final exam for this course online at
http://www.usa.siemens.com/step/. This web page provides links to a variety of our quickSTEP
online courses. To complete the final exam for this course, click on the Basics of Load Centers
link.
Next, move your mouse over to the left so that the navigation bar pops out, and select the Final
Exam link. The final exam page will appear. Before taking the final exam, it is recommended that
you delete the temporary files on your computer. For most versions of Internet Explorer, you
can do this by selecting Internet Options from the Tools menu and then clicking on the Delete
Files button. If you do not perform this step, you may see a score of 0% after you submit your
exam for grading.
After you complete the final exam, click on the Grade the Exam button at the bottom of the
page. Your score on the exam will be displayed along with the questions that you missed.
If you score 70% or better on the exam, you will be given two options for displaying and printing
a certificate of completion. The Print Certificate option allows you to display and print the
certificate without saving your score in our database and the Save Score option allows you to
save your score and display and print your certificate.