Project: WHA Warehouse Wangnoi

Building: E (Mars)
Subject: Ventilation for Battery Charger Room

room

width
length
ceiling height
area
volume

=
=
=
=
=

12
24
6
288
1728

battery

48V/620AH/24 cells
24V/310AH/12 cells
80V/500AH/40 cells

=
=
=

10
10
2

Item No

Code

Calculation

1 ASHRAE 62
1 cfm/Amp

= (620x10)/4+(310x10)/4+(500x2)/4
=
2575

6 ACH

= 6x1728
=

10368

2 EN 50272-2

Q = 0.05xnxIgxAH/1000
= 0.05x((620x24x10)+(310x12x10)+(500x40x2))x20/1000
=
226

3 Hydrogen Produce

= (CxAxOxG)/R/100
C
O
G
A
R

=
=
=
=
=

No of cells in battery
Percentage of overcharge, use 20%

Volume of hydrogen produced by one ampere hour of charge. U


6-hour rated capacity of the battery in ampere hours
Assume gas is released during the last (4) hours of an 8-hour ch

= ((620x24x5)+(310x12x6)+(500x40x2))x20x0.01474/4/100
=
100.76264

1% Hydrogen Concentrate Ventilation


167.9377333

m
m
m
sq.m
cu.m
sets
sets
sets

Exhaust Air Volume

Remarks

cfm

1215 l/s

cu.m/h
cu.m/h

2880 l/s Maximum Value

cu.m/h
10x12x10)+(500x40x2))x20/1000
cu.m/h

63 l/s

cfh

roduced by one ampere hour of charge. Use .01474 to get cubic feet
of the battery in ampere hours
ed during the last (4) hours of an 8-hour charge

x6)+(500x40x2))x20x0.01474/4/100

cfh

cfm

79.25329558 l/s