You are on page 1of 2

VLT Soft Starter MCD 3000

VLT Soft Starter MCD 3000 is a total motor starting solution.


Current transformers measure the motor current and provide
feedback for controlled motor voltage ramp up, but also for
numerous motor protection functions.
A numeric display and logic keypad
buttons makes programming easy
and operational status such as motor
current is shown via the display.

The perfect solution, also for more


severe applications:
Pumps
Conveyors
Fans
Mixers
Compressors
Centrifuge
Mill
Saw
And many more
Power range
7.5 800 kW
Versions for 200690 VAC

The VLT Soft Starter MCD 3000 is


wall mountable, however a Remote
Operator module allows for remote
control and motor performance
monitoring, making it ideal for panel
installation.

Features

Benets

Current ratings for normal and


heavy starting

Fits the most severe applications

Current limit soft start with initial


current ramp up

Limiting the current the motor can


draw during start

DC brake function

Fast stop of heavy inertia applications

Internal delta wiring kit

The soft starter carries only phase current,


and can therefore control a motor with
greater full load current

Reliable

Maximum up-time

Numerous motor protection features

Maintenance free

Password protection of parameters

Prevents unauthorized changes

Max. ambient temperature 50C


without derating

No external cooling or oversizing necessary

User-friendly

Save commissioning
and operating cost

Four dierent auto-adjustable


ramp down proles

Reduced assembly time


Less installation cost

Built-in local control panel with display

Easy to operate

Specications
CURRENT (% Motor Full Load Current)

700%

Full Voltage Stator Current

Mains supply (L1, L2, L3)

600%
500%

Supply frequency (at start)


Supply frequency (during start)
Supply frequency (during run)
Electronics control voltage

3x200 VAC ~ 525 VAC


3x200 VAC ~ 440 VAC (Inside Delta Connection)
3x200 VAC ~ 690VAC
3x200 VAC ~ 440 VAC (Inside Delta Connection)
50HZ ( 2Hz) / 60 Hz ( 2Hz)
>45Hz (50Hz supply) or >55Hz (60 Hz supply)
>48Hz (50Hz supply) or >58Hz (60 Hz supply)
230 VAC (+10%/-15%) or 400 VAC (+10%/-15%)

Control inputs
Start (Terminals 15 & 16)
Stop (Terminals 17 & 18)
Reset (Terminals 25 & 26)
Parameter Set (Terminals 27 & 28)

Normally Open, Active 24 VDC, 8mA approx.


Normally Closed, Active 24 VDC, 8mA approx.
Normally Closed, Active 24 VDC, 8mA approx.
Normally Open, Active 24 VDC, 8mA approx.

Supply voltage MCD3000-TS

Ramp time
(e.g. Par. 4 = 10 secs.)
Current Limit (e.g. Par. 2 = 400% x FLC)

400%

Supply voltage MCD3000-T7

300%
200%
100%

Initial Current (e.g. Par. 3 = 250% x FLC)

10% 20%

30% 40% 50% 60% 70% 80% 90% 100%


ROTOR SPEED (% Full Speed)

Current ramp

Fully featured Soft Starter for


motors up to 800 kW
Total motor starting solution
Advanced start, stop and
protection features
Local programming keypad and
display

Relay outputs
Programmable Output A1)
(Terminals 13 & 14)
Programmable Output B2)
(Terminals 21, 22 & 24)

Normally Open, 5 A @ 250 VAC/360 VA,


5 A @ 30 VDC resistive
Changeover, 5 A @ 250 VAC/360 VA,
5 A @ 30 VDC resistive
Normally Open , 5 A@250 VAC/360 VA,
5 A@30 VDC resistive
Line contactor, Run, High current ag,
Low current ag
Tripped, Output on, High current ag,
Low current ag, Line contactor
Run, D.C.Brake Contactor Control, O

Output C3) (Terminals 33 & 34)

Optional:
Modules for serial communication
Remote operator kit
PC software

1) Programmable functions
2) Programmable functions
3) Programmable functions
Environmental
Degree of protection MCD3007 to MCD3132
Degree of protection MCD3185 to MCD3800
Operating Temperatures
Rated short-circuit current
(with semi-conductor fuses)
Rated insulation voltage (Surges)
Rated impulse withstand voltage
(Fast transients)
Pollution Degree
Electro static discharge
Equipment class (EMC)
Radio-frequency electromagnetic eld

Remote operation kit


Start/stop, reset
LED for start, run, trip
Trip codes
Current display
Motor temperature display
420 mA output

IP 21
IP 20
-5C / +60C
100kA
2 kV line to earth, 1kV line to line
2 kV
Pollution Degree 3
4 kV contact discharge, 8 kV air discharge
Class A
0.15 MHz 80 MHz: 140dBV
80 MHz 1 GHz: 10 V/m

This product has been designed for Class A equipment. Use of the product in domestic environments may cause radio interference, in which
case the user may be required to employ additional mitigation methods.

Standards Approvals
C
UL1
C-UL1
CE

CISPR-11
UL508
CSA 22.2 No. 14
IEC 60947-4-2

1) Requires use of semi-conductor fuses. Excludes models MCD3600~MCD3800

Cabinet sizes
Power range
(400V)
Series

MP005A02

7.555 kW

75110 kW

132 kW

185500 kW

600800 kW

3007 - 3055

3075 - 3110

3132

3185 - 3500

3600 - 3800

Height [mm]

530

530

530

850

1000

Width [mm]

132

264

396

430

560

Depth [mm]

270

270

270

280

315

VLT is a trademark of Danfoss A/S