High Voltage Test of 8D-GIS


with Power VT
Inductive voltage transformers (VT) are usually used in
high voltage substations to provide measuring signals
forcontrol, protection and metering systems.
With an improved design of the windings the VT becomes
a Power VT which then allows for a High Voltage test of
the primary system without special high voltage test
equipment.
Measuring VT function

Test cycle
Cooling time 8 h
Test section up to 2 bays

voltage/[kV]

250

200

Type-tested according to IEC 61869-1 and IEC 60044-2


Rated voltage up to 145 kV

150

Voltage factor 1.9 for 8 h


Accuracy: class 0.2 at 100 VA class 0.5 at 200 VA
Measuring frequency 50/60 Hz
Test VT function
HV-test according to IEC standard and the proposed
testlevels at site (IEC 62271-203 table 107)
Test frequency 100 HZ 20%

100

50

0
0

10 11 12
time/[min]

Typical load cycle

Answers for energy.

CPC 100: signal source


CP TR1: isolating transformer
CP CR1 & CP CR2: resonance reactors

CPC 100
80 Hz 120 Hz

Power VT

CP TR1
CP CR1

CP CR1

AC

Control- & Feeding Unit

GIS

Comprehensive testing capability

Easy re-test over the whole life cycle

after test the GIS can be put into operation without


mechanical work on the primary circuit, i.e. normally
thehigh voltage test set must be removed

test-preparation within minutes e.g. after S/S-extension,


re-assembling or extensive service activities

easy support by neutral testing


companies (e.g. OMICRON) or testing institutes
Easy handling
with a Power VT the high voltage test becomes like
testing a protection relay
light weight units allow handling at site without
liftingfacilities or cranes

low investment in site based testing facilities


possibility for investigation into sporadic effects at
PD-test voltage levels
Space saving
Power VTs are of the same dimension as standard VTs
no extra space needed for temporary installation of
huge high voltage testing facilities

power supply via a standard socket outlet


(e.g. 3-phase, 400 V, 20 A)

Environmental friendly

Easy transport

reduced transport and packages requirements

no SF6-gas handling at site needed for test preparation

test facilities available with transport cases allowing


transport as carry-on luggage during travelling to site
orthe use of standard parcel services