ASLI Circular Variable Air Volume (STR) terminal units are volume flow rate
controller for supply air on variable air volume system. These units are designed
to control the airflow rate of conditioned air into an occupied space in response to
a control signal from thermostat or Building Automation System (BAS). They
could be used in stand alone system or interfaced with LONWORKS.
ASLI RVAV terminal units also incorporate control components, (VAV controller
actuator, and transformer) which are factory fitted. ASLI in-house testing facility
ensured that all boxes that come out from the factory are calibrated and tested to
match the controller of individual size. This allow the terminals to monitor the
desired flow rate, as dictated by the thermostat or BAS, and compensate instantly
for any changes in supply air pressure that might tend to alter the supply air
volume. Hence, the net result is a pressure independent variable air volume
system.
Two models are available, STR (basic unit) and STRC (basic unit with external
cladding to reduce case radiated noise).
Materials
Features
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
STR 1 of 7
A
G
H -Unit Size
100
150
200
250
300
350
400
D
95
145
195
245
295
345
395
E
120
120
120
120
120
120
120
F
220
220
220
220
220
220
220
G
310
310
310
310
310
310
310
L
494
494
494
494
494
596
596
B
195
245
295
345
395
445
495
A
344
344
344
344
344
446
446
H
50
50
50
50
50
50
50
C
100
100
100
100
100
100
100
General notes:
Galvanized steel housing
Mechanically seal leak resistant construction
Right hand control location standard, as shown above
Turbulence flow approaching the terminal will create additional noise, pressure drop and greater air flow variation. It is therefore recommended for optimum
performance, there should be a minimum of 4 duct diameters of straight duct, same size as inlet, between the inlet and any transition, take off or lifting.
STR
C=with cladding
4 = 4 dia.
6 = 6 dia.
8 = 8 dia.
10 = 10 dia.
12 = 12 dia.
14 = 14 dia.
16 = 16 dia.
24X16 = 24X16 inlet
Example: STR-512.
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
STR 2 of 7
liter/s
31 - 106
50 - 212
99 - 378
160 - 637
245 - 991
363 - 1510
472 - 1888
100 (4)
150 (6)
200 (8)
250 (10)
300 (12)
350 (14)
400 (16)
CFM
65 - 225
105 - 450
210 - 800
340 - 1350
520 - 2100
770 - 3200
1000 - 4000
Unit Size
4
10
12
14
16
Air Flow
CFM L/s
79
37
128
60
176
83
225 106
158
74
255 120
353 166
450 213
280 132
453 214
627 296
800 378
473 223
765 361
1058 499
1350 638
735 347
1076 508
1418 669
1759 831
2100 992
1120 529
1640 774
2160 1020
2680 1266
3200 1511
1400 661
1920 907
2440 1152
2960 1398
3480 1643
4000 1889
W.G
0.01
0.01
0.02
0.04
0.01
0.03
0.10
0.21
0.01
0.01
0.02
0.06
0.01
0.01
0.02
0.06
0.01
0.01
0.01
0.02
0.04
0.01
0.01
0.01
0.02
0.06
0.01
0.01
0.01
0.01
0.02
0.05
Pa
14
35
67
112
11
31
71
128
10
24
47
83
11
26
53
92
13
25
41
65
96
16
32
53
85
128
14
25
39
57
81
112
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
STR 3 of 7
Unit Size
4
10
12
14
16
Air Flow
CFM L/s
79
37
128
60
176
83
225 106
158
74
255 120
353 166
450 213
280 132
453 214
627 296
800 378
473 223
765 361
1058 499
1350 638
735 347
1076 508
1418 669
1759 831
2100 992
1120 529
1640 774
2160 1020
2680 1266
3200 1511
1400 661
1920 907
2440 1152
2960 1398
3480 1643
4000 1889
2
45
49
53
57
49
53
57
61
54
57
60
64
60
61
63
67
60
62
63
65
69
62
64
65
67
71
64
66
67
68
69
73
7
33
37
44
51
34
38
45
52
39
42
46
53
45
48
49
56
44
46
49
50
57
46
47
50
51
58
47
48
51
52
52
59
2
48
52
57
61
52
56
61
65
57
60
64
68
63
65
67
71
64
66
67
69
73
66
68
69
71
75
67
69
70
72
73
77
7
46
50
57
60
49
53
59
62
54
57
61
64
60
62
63
66
57
59
61
62
66
61
62
65
66
69
63
65
67
64
65
69
2
55
59
65
69
59
63
69
73
64
67
72
76
70
72
75
79
71
73
75
78
82
73
75
77
80
84
72
75
77
79
82
86
7
53
57
63
64
56
60
66
67
61
64
69
70
67
69
70
71
67
69
71
72
73
68
70
72
73
74
71
74
75
70
72
74
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
STR 4 of 7
Unit Size
4
10
12
14
16
Air Flow
CFM L/s
79
37
128
60
176
83
225 106
158
74
255 120
353 166
450 213
280 132
453 214
627 296
800 378
473 223
765 361
1058 499
1350 638
735 347
1076 508
1418 669
1759 831
2100 992
1120 529
1640 774
2160 1020
2680 1266
3200 1511
1400 661
1920 907
2440 1152
2960 1398
3480 1643
4000 1889
2
46
49
53
56
47
50
54
57
50
53
57
60
56
60
63
64
54
57
61
64
65
55
59
63
66
67
53
56
60
64
67
68
7
15
18
28
33
16
19
29
34
19
22
32
37
25
35
40
46
23
26
36
41
47
24
28
36
43
49
24
27
31
39
46
52
2
47
50
55
58
49
52
56
59
52
55
59
62
58
62
65
67
56
59
63
66
68
57
61
65
68
70
55
58
62
66
69
71
7
26
29
34
37
28
31
36
39
31
34
39
42
37
42
45
49
35
38
43
46
50
36
40
44
48
52
36
39
43
47
51
55
2
50
53
58
61
53
56
61
64
56
59
64
67
62
67
70
72
60
63
68
71
73
61
65
69
73
75
59
62
66
70
74
76
7
31
34
37
39
34
37
40
42
37
40
43
45
43
46
48
50
41
44
47
49
51
42
46
49
51
53
42
45
49
52
54
56
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
STR 5 of 7
Unit Size
4
10
12
14
16
Air Flow
CFM L/s
79
37
128
60
176
83
225 106
158
74
255 120
353 166
450 213
280 132
453 214
627 296
800 378
473 223
765 361
1058 499
1350 638
735 347
1076 508
1418 669
1759 831
2100 992
1120 529
1640 774
2160 1020
2680 1266
3200 1511
1400 661
1920 907
2440 1152
2960 1398
3480 1643
400 1889
2
44
47
51
54
45
48
52
55
48
51
55
58
54
58
61
62
52
55
59
62
63
53
57
61
64
65
51
54
58
62
65
66
7
6
9
19
24
7
10
20
25
10
13
23
28
16
26
31
37
14
17
27
32
38
15
19
27
34
40
15
18
22
30
37
43
2
45
48
53
56
47
50
54
57
50
53
57
60
56
60
63
65
54
57
61
64
66
55
59
63
66
68
53
56
60
64
67
69
7
17
20
25
28
19
22
27
30
22
25
30
33
28
33
36
40
26
29
34
37
41
27
31
35
39
43
27
30
34
38
42
46
2
48
51
56
59
51
54
59
62
54
57
62
65
60
65
68
70
58
61
66
69
71
59
63
67
71
73
57
60
64
68
72
74
7
22
25
28
30
25
28
31
33
28
31
34
36
34
37
39
41
32
35
38
40
42
33
37
40
42
44
33
36
40
43
45
47
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
STR 6 of 7
125
68
73
250
66
71
500
66
69
1000
65
67
2000
57
64
4000
52
59
Controls
- The VAV controller shall be Lon based microprocessor based direct digital control (DDC) with open system concept to ensure ease of
interfacing on site with others.
- Each VAV unit shall have its own dedicated, stand-alone microprocessor-based, truly independent LonMark open system controller.
- Each VAV controller shall accept standard thermistor input for temperature sensing.
All the VAV units shall be capable of stand-alone or networking operation. In networking mode, the DDC controller shall be truly open to be freely integrated to
existing LonWork BAS without any additional hardware or software.
As a minimum, the user shall have the capability of monitoring the following dynamics up-dated information through each of the operator interface devices : zone temperature
actual live airflow
desired set-point airflow
cooling set-point etc
operating mode
The room thermostat shall have a LCD display for room temperature and set point adjustment capability.
The controller shall have an overriding function to occupied/unoccupied mode.
As a minimum the user shall have the ability to monitor and control the following set-points through each of the operator interface devices : cooling set-point
minimum and maximum air flows
neutral zone
occupied/unoccupied time schedule
room temperature
live actual air flow
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.