Usefull Equations
Usefull Equations
K=Material Factor, K for Cu=159, K for Alu=105, K for steel=58 , K for GI=80
Spacing of Conductor in Transmission Line (mm) = 500 + 18x (P-P Volt) + (2x (Span
in Length)/50).
Size of Lighting Arrestor= 1.5x Phase to Earth Voltage or 1.5x (System Voltage/1.732).
If Load Factor is 1 or 100% = This is best situation for System and Consumer both.
If Load Factor is Low (0 or 25%) =you are paying maximum amount of KWH
consumption. Load Factor may be increased by switching or use of your Electrical
Application.
Demand Factor= Maximum Demand / Total Connected Load (Demand Factor <1)