400/220kV GIS Substation Contract No.

COMMENT SHEET
Owner
Drawing Number

Comment Sheet No.1

Contractor

Date of Comment
By Owner: 09/01/2015

Drawing Title
Rev.

Status

Drawing Number

Rev.

Type

0
Com.

400kV Girder Structural Design-Type 4G1

Owners Comments

No.
1

There is no figure of the overall structure giving the dimensions and sections
used.

Reference drawings mentioned on Page No. 3 of 37 is not available.

The STAAD model with the nodes and members displayed is not available in
the document, so the manually calculated loads cannot be co-related with
the input given in the STAAD file.

The load calculations given in the document conform to the code provisions
referred to IS 802 code of practice for use of structural steel in transmission
towers.

Wind load calculations conform to the code provisions including the


reduction in load applicable as per IS 802 (part 1) section 1 Clause no. 8.

The loading diagram given in the document correctly shows the loading
calculated from the codes.