COMMENT SHEET
Owner
Drawing Number
Contractor
Date of Comment
By Owner: 09/01/2015
Drawing Title
Rev.
Status
Drawing Number
Rev.
Type
0
Com.
Owners Comments
No.
1
There is no figure of the overall structure giving the dimensions and sections
used.
The STAAD model with the nodes and members displayed is not available in
the document, so the manually calculated loads cannot be co-related with
the input given in the STAAD file.
The load calculations given in the document conform to the code provisions
referred to IS 802 code of practice for use of structural steel in transmission
towers.
The loading diagram given in the document correctly shows the loading
calculated from the codes.