PRESSURE DROP CALCULATIONS :

SR. ITEM
NO.

PIPE

SIZE
NB
mm

ID

SERVICE OF DMF, ACF, SAC, AND DGT


L
Q
V
C
PRESSURE DROP

mm

mtrs.

m3/hr

m/sec

150
SIZE
NB
150
150
150

147
ID
MM
147
147
147

85.00
K

120.00
Q
M3/HR
120.00
120.00
120.00

1.96
V
M/S
1.96
1.96
1.96

MTRS/MTRS

TOTAL
PRESS.LOSS
MWC

P1-A/B/C/D DISCH TO DMF-POTABLE INLET :


1
PIPE(MS MAIN HEADER)(APPROX)
SR. ITEM
NO.
2
BEND 90DEG(MS)
3
VALVE(B/F)
4
NRV
FROM DMF-POTABLE OUTLET TO FWST INLET:
5
DMF FILL
6
DMF INTERNALS
7
BEND 90DEG(MS)
8
Flow Element
9
VALVE(B/F)
10 PIPE(MS)
11

0.75
0.30
2.50

150

147

0.75

150
150

147
147

0.30
102.00

120.00
120.00
120.00
120.00

1.96
1.96
1.96

100
QTY
4
2
1

5
1
2
100

0.04
PRESSURE DROP
M/QTY
0.15
0.06
0.49

0.15
0.06
0.04

3.74

0.59
0.12
0.49
3.00
1.00
0.74
1.50
0.12
4.49

SUMP DEPTH FROM FGL

8.05

PUMP DISCHARGE OUTLET HEIGHT FROM FGL


PUMP HEAD SELECTED ( MWC ) =
Margin 5%
PUMP HEAD PROVIDED ( MWC ) =

7.50
31.34
1.57
32.91

RECOMMENDED HEAD AT 120 M3/H

HEAD SELECTED AT 120 M3/H

NOMENCLATURE
1) ID = INSIDE DIAMETER OF PIPE IN MM
2) C = COEFFICIENT OF FRICTION
3) Q = FLOW IN M3/HR
4) K = RESISTANCE COEFFICIENT FOR VALVE OR FITTING
5) V = VELOCITY IN (M/S) = Q*4/(3.142*ID*ID/1000000))/3600

33

MWC

HENCE OK