‘This drawing and the design it covers are the property of ENGINEERS INDIA LIMITED, They are merely loaned and on the borrower's express agreement thet they ‘Tl not be feproduced, copied, loaned, exhibited nor toed exoept in the limited way and private ure permitted by any written consent give NO. | DATE REVISIONS BY [CHKD.| APPROVALS JOB NO.6936 (0. [190809] ISSUED _AS JOB STANDARD ski | va [PP 0 = 2.0mm UPTO 12” = 30mm FROM 14” TO 24” COAL TAR EXPOXY PAINT CEMENT LINING "COROLAC RESIN’ 50% COROLAC-1 x ~ 5 + 50% COROLAC-2 T TK CARBON STEEL PIPE (FOR INSIDE OF COLLAR q & OUTSIDE OF PIPE Z “COLLAR L.y PIPE JOINT WITH COLLAR (FOR SIZES UPTO 24”) SECTION X-X 2MM THK CAF GASKET- S.0. FLANGE CEMENT LINING CEMENT LINING SELLE L FIELD CEMENT LINING BUTT WELD PIPE JOINT FLANGED JOINT(NOTE-1) (FOR SIZES > 24’ NOTE 1: FLANGED JOINT TO BE PROVIDED AT CRITICAL LOCATIONS FOR EASE OF FABRICATION, INSPECTION AND MAINTENANCE DETAILS OF COLLAR & THICKNESS OF CEMENT MORTAR LINING 2 PIPE PIPE OD |COLLER ID| COLLAR COLLAR THICKNESS OF NB (Do) (Oi) LENGTH THICK MORTAR LINING REMARKS (ch) | (mm) | (mm) | L (mm) | te (mm) tL (mm) Re 88.97 92.7 110 10 60 + 08 LUNING THICKNESS a" 114.300 118.1 120 10 6.0 + 08 FOR PIPE NB >= 26" . = 120 + 16 | 6" | 168.275 | 172.7 130 10 80 + 08 | er | 2e075 | 2235 140 10 | 100 + 08 =| 10" | 273.050 | 278.2 150 12 12.0 4 08 S| 12” | 323.850 | 329.0 200 12 12.0 + 1.6 3 14° 355.600 (361.2 200 12 12.0 + 1.6 | 16" | 408.400 | 412.4 200 12 12.0 + 1.6 18" | 457.200 | 463.8 250 12 12.0 + 1.6 20" 508.000 515.1 (250 12 12.0 + 1.6 24" 609.600 617.9 (250 12 12.0 + 1.6 SHT. 10. OF 15 CEMENT LINED PIPES: JOINTS & STANDARD NO. REV. Z-BNGINEERS INDIA LIMITED ‘NEW DELI LINING, THICKNESS 6936-6-44-74 | 0