You are on page 1of 6

Reduce to 390 ppm TDS CW from 400 ppm

Evap =
TDS =

CW =
TDS =

75 L/s
0 mg/L

5000 L/s
400 mg/L
2,000,000 mg/s

RCW =
TDS =

Maintain 400 ppm TDS CW


Evap =
TDS =

CW =
TDS =

5000 L/s
400 mg/L
2,000,000 mg/s

75 L/s
0 mg/L

RCW =
TDS =

BD =
TDS =

125 L/s
406 mg/L
50,761 mg/s

With blowdown :
CW =
TDS =

4925 L/s
406 mg/L
2,000,000 mg/s

Without blowdown :
CW =
TDS =
MU =
TDS =

4925 L/s
406 mg/L
2,000,000 mg/s

MU =
TDS =

200 L/s
10 mg/L
2000 mg/s

BD =
TDS =

11 L/s
406 mg/L
4,277 mg/s

TDS =

With blowdown :
CW =
TDS =

Without blowdown :
CW =

TDS =
MU =
TDS =
MU =
TDS =

86 L/s
50 mg/L
4277 mg/s

TDS =

With blowdown :
5000 L/s
1,951,239 mg/s
390

Without blowdown :
4925
2,000,000
75
2000

L/s
mg/s
L/s
mg/s

400.4

With blowdown :
5000 L/s
2,000,000 mg/s
400

Without blowdown :
4925 L/s

2,000,000 mg/s
75 L/s
4277 mg/s
400.86