Professional Documents
Culture Documents
Two Man Ip Control
Two Man Ip Control
Manipulated Parameters
Introduction
Split-Range Control
Example
Summary
Process Control
Introduction Historic Perspective
Controller
SP
Most common
techniques are: split
range, valve position
control.
Combination of these
techniques offer new
capability to address this
class of problems
Two(2) Manipulated
Parameters
Process
Unmeasured
Disturbance
Process Control
Introduction Historic Perspective
TIC
101
Temperature Example
IP
101
4-20ma
3-15PSI
A/C
Cooling
A/O
Heating
100
Valve
Position
(% of Span)
0
Process
TT
101
Cooling
Heating
3
IP Output ( PSI )
15
Process Control
Introduction Historic Perspective
4-20ma
IP
102
3-15PSI
PS
102
100
Valve
Position
(% of Span)
0
3
pH
A/O
A/O
Coarse Valve
AT
102
Fine Valve
Coarse Valve
PID
SPLT
When using
traditional valves,
split range control
may implemented in
DeltaV Controller
using two(2) current
outputs
AO
AO
AI
PID
SPLT
AO
AO
Process Control
Introduction Historic Perspective
Process Control
Introduction Historic Perspective
Process Control
Introduction Historic Perspective
IN_ARRAY Parameter
SP range
associated
with OUT1
The SP range
associated with
each output is
defined by
IN_ARRAY.
SP range of
outputs may be
defined to overlap
SP range
associated
with OUT2
Process Control
Introduction Historic Perspective
OUT_ARRAY Parameter
When SP is outside
defined range, then
the value at the end
of range is used to
determine the
output.
LOCKVAL
determines if OUT1
value is held if SP is
greater that the
upper end of range
defined for OUT1.
No restrictions are
placed on the output
range.
Process Control
Introduction Historic Perspective
Splitter Block
OUT_1
100
OUT_2
OUT_ARRAY
0 100 0 100
IN_ARRAY
0 100 0 100
0
0
100
OUT_ARRAY
100 0 0 100
IN_ARRAY
0 40 35 100
100
0
100
0
100
LOCK_VAL holds
HYSTVAL
LOCK_VAL is zero
0
0
OUT_ARRAY
0 100 0 100
IN_ARRAY
0 40 35 100
100
SP
2006Fisher-Rosemount Systems, Inc.
Slide 1- 11
Process Control
Introduction Historic Perspective
PID
TT103
TIC103
SPLT
AO
IP103A
FY103
AO
IP103B
TIC
103
FY
103
IP
103A
HEATER
2006Fisher-Rosemount Systems, Inc.
Slide 1- 12
IP
103B
TT
103
COOLER
Process Control
Introduction Historic Perspective
100
Valve
Position
(% of Span)
Cooling (IP103B)
Heating (IP103A)
0
0
TIC103 Output (% of Span)
2006Fisher-Rosemount Systems, Inc.
Slide 1- 13
100
Process Control
Introduction Historic Perspective
PID
PT104
PIC104
SPLT
FY104
AO
IP104A
AO
IP104B
1475# Header
Boiler
IP
104A
FY
104
IP
104B
400# Header
PIC
104
PT
104
Turbo
Generator
Process Control
Introduction Historic Perspective
100
Valve
Position
(% of Span)
Valve 104A
Valve 104B
0
0
PIC104 Output (% of Span)
2006Fisher-Rosemount Systems, Inc.
Slide 1- 15
100
Process Control
Introduction Historic Perspective
A 1% change in controller
output to the splitter should
have the same impact on
control parameter when
operating with either valve.
Process Control
Introduction Historic Perspective
Heating
1.1degF
Calculate the
splitter SP span
and range for
each output
based on the
observed
response
2.2degF
1%
Cooling
1%
Time
Process Control
Introduction Historic Perspective
Process Control
Introduction Historic Perspective
SP
Small
Valve
PID OUT
PV
Large
Valve
Process Control
Introduction Historic Perspective
Process Control
Introduction Historic Perspective
AIC
106
Mode
Target
Valve
Position
IP
106A
ZC
106
Fine Valve
IP
106B
I-Only
Controller
A/O
Coarse
Valve
PID control is
implemented using the
actuator with finer
resolution or fastest
impact on controlled
parameter
AT
106
Process
pH
Fine Valve
Coarse Valve
Time
2006Fisher-Rosemount Systems,
Inc.
Slide 1- 21
Target Valve
Position
PID
PID
Slide 1- 22
It is possible to
implement valve
position control in the
DeltaV controller or for
this function to be
distributed to fieldbus
devices.
AO
Traditional
field devices
AO
I-Only
Fieldbus
devices
2006Fisher-Rosemount Systems, Inc.
I-Only control is
achieved by
configuration of the PID
Block STRUCTURE,
GAIN and RESET
parameters.
AO
I-Only
AI
AO
Process Control
Introduction Historic Perspective
Process Control
Introduction Historic Perspective
The STRUCTURE
parameter should be
configured for I action
on Error, D action on
PV
PID
FT107
FIC107
AO
IP107A
I-Only
ZC107
AO
IP107B
IP
107A
FIC
107
FT
107
ZC
107
IP
107B
Process Control
Introduction Historic Perspective
Example --Boiler
Boiler BTU Demand
AI
FT109B
SUM
PID
FY109
FIC109
AI
AO
IP109A
I-Only
FT109A
ZC109
AO
IP109B
BTU Demand
FY
109
FIC
109
IP
109A
FT
109B
HI BTU Fuel
ZC
109
Boiler
IP
109B
FT
109A
2006Fisher-Rosemount Systems, Inc.
Slide 1- 26
Process Control
Introduction Historic Perspective
Example Reformer
Reformer Air Demand
AI
PID
FT110
FIC110
AO
IP110
ZC
110
SC
110
Air
Machine
I-Only
AO
ZC110
SC110
FIC
110
Total Air
Demand
IP
110
FT
110
Secondary
Reformer
Process Control
Introduction Historic Perspective
Process Control
Introduction Historic Perspective
Target
position for
fine valve is
30%.
When the
fine valve
saturates,
then
response is
limited to be
reset of the
I-Only
control
PV
SP
Coarse Valve
Limited
Fine Valve
Process Control
Introduction Historic Perspective
The features of split range control and valve position control may be
combined to provide immediate response to large changes in
demand while retaining the features of valve position control for
normal changes.
Process Control
Introduction Historic Perspective
A composite
Block can be
created that
combines the
features of split
range and valve
position control
Support for
BKCAL_IN and
BKCAL_OUT
can be
implemented to
provide
bumpless
transfer
Process Control
Introduction Historic Perspective
Composite Algorithm
NORMAL
SP
FILTER_TC
CAS_IN
OUT_1
Filter
x
x
MODE
RANGE
SPAN
OUT_2
Scaling
BKCAL_IN1
Balance Calculation
BKCAL_OUT
BKCAL_IN2
Process Control
Introduction Historic Perspective
Composite Implementation
Parameters that
must be configure
are: FILTER_TC,
SPAN (of SP),
RANGE (of
OUT1), and
NORMAL
(desired position )
The FILTER_TC
should be
configured similar
to the reset time
of the I-Only
Controller that
would be used for
valve position
control.
Process Control
Introduction Historic Perspective
Process Control
Introduction Historic Perspective
Small change
For small
changes in SP or
load disturbance,
the response is
similar to that
provided by
valve position
control
For large
changes in SP or
load disturbance,
the immediate
response is
similar to split
range control
Large change
SP, PV
OUT of
PID
Fine
Valve
Coarse
Valve
Process Control
Introduction Historic Perspective
Summary
Process Control
Introduction Historic Perspective