The design of the switchgear should be based on safety to personnel and equipment
during operation and maintenance, reliability of service, ease of maintenance,
mechanical protection of equipment, interchangeability of equipment and ready
addition of future loads.
capacity
- Live Cable LED Indicators thru Capacitor Voltage Dividers mounted on the bushings.
- Mechanical ON/OFF/EARTH Indication
- Anti-reflex operating handle
- Cable Testing facility without disconnecting the cable terminations, cable joints
and terminal protectors on the bushings.
Cable terminations
- Cable boxes suitable for 1 X 3C x 300 sq mm XLPE Cable with right angle Cable
Termination Protectors.
Signature of Tenderer
Date:
Place:
Page 2 of 14
MGVCL/PP/D2/4013/RMU/
INDOOR RMU
1. MODULAR DESIGN, PANEL TYPE WITH FRONT CABLE ACCESS.
2. RMU MUST BE MADE OF ROBOTICALLY WELDED STAINLESS STEEL.
3. Offered RMU must be extensible.
Signature of Tenderer
Date:
Place:
Page 3 of 14
MGVCL/PP/D2/4013/RMU/
2.2.1 Fixed type SF-6 gas insulated / Vacuum circuit breakers. It should be maintenance
free, having stainless steel robotically welded enclosure for IN DOOR RMU &
hermatically sealed metallised Epoxy Enclosure / Stainless steel enclosure for OUT
DOOR RMU application.
2.2.2 Low gas pressure devices- 1.2 Bar pressure. RMU should have full rating with 0.0
Bar gas pressure.
2.2.3 Live cable indicators- High operator safety.
2.2.4 Fully Rated integral ear thing switch on each device.
2.2.5 Self powered Microprocessor Based relay- Does not require any external source
of power.
2.2.6 Units fully SCADA Compatible. Retrofitting at site possible at a later date. Line
switches ( Load break switches) as well as T- OFF circuit Breaker can be operated by
remote.
2.2.7 For indoor Cable boxes should be front access and interlocked with earth switch.
No rear access required. For outdoor RMUs cable boxes shall be on sides/rear/front.
2.2.8 Cable testing possible without disconnection of cables.
2.2.9 Compact in dimension.
2.2.10Circuit Breaker with self powered O/C & E/F RELAY.
2.2.11 Low pressure, sealed for life equipment, can operate at 0 bar pressure.
2.2.12Cable ear thing switch on all switching device-standard, for operator safety.
2.2.13Enclosure with IP 54 standard protection for OUTDOOR RMUs and IP2X for
INDOOR RMUs
2.2.14All live parts should be inside a hermetically sealed metalised Epoxy enclosure /
stainless steel enclosure for out door type RMU & 3mm stainless steel robotically
welded enclosure for indoor RMU.
Signature of Tenderer
Date:
Place:
Page 4 of 14
MGVCL/PP/D2/4013/RMU/
3 DESIGN CRITERIA
3.1 Service conditions
The offered switchgear and control gear should be suitable for continuous operation under
the basic service conditions indicated below. Installation should be in normal indoor
conditions in accordance with IEC 60694.
Ambient temperature -1 oC to +45 oC
Relative humidity up to 95%
Altitude of installation up to 1000m, IEC 60120
3.2 General structural and mechanical construction
The offered RMU should be of the fully arc proof metal enclosed, free standing, floor
mounting, flush fronted type, consisting of modules assembled into one or more units. Each
unit is made of a cubicle sealed-for life with SF6 / VCB and contains all high voltage
components sealed off from the environment.
The overall design of the indoor switchgear should be such that front access only is
required. It should be possible to erect the switchboard against a substation wall, with HV
and LV cables being terminated and accessible from the front.
The units should be constructed from 3 mm thick stainless steel sheets. The design of the
units should be such that no permanent or harmful distortion occurs either when being lifted
by eyebolts or when moved into position by rollers.
. For outdoor RMUs a weather proofing process shall be carried out. SHEET METAL MUST BE GRIT
BLASED / THERMALLY SPRAYED AND POLYURETHANE PAINTED WITH ABOUT 70 MICRON
THICKNESS, TO ACHIVE OUTDOOR WORTHINESS AND CORROSION PROOF NESS .
- RMU ENCLOSURE MUST BE SHIELDED AGAINST SOLAR IRRADIATION AND TESTED FOR A
AMBIENT OF 45 / 50 DEGREE C WITHOUT DERATING OF THE EQUIPMENT.
The cubicle should be have a pressure relief device. In the rare case of an internal arc, the
high pressure caused by the arc will release it, and the hot gases is allowed to be
exhausted out at the bottom / top / rear of the cubicle. A controlled direction of flow of the
hot gas should be achieved.
Signature of Tenderer
Date:
Place:
Page 5 of 14
MGVCL/PP/D2/4013/RMU/
KV
KV
KV
Hz
A
A
A
12/15.5KV
28 / 35
75 / 95
50/
630
630
200 / 630
7
8
9
10
11
Rated voltage
Power frequency withstand voltage
Impulse withstand voltage
Rated frequency
Rated current busbars
Rated current (cable switch)
Rated current (T-off)
Breaking capacities:
active load
closed loop (cable switch)
off load cable charging (cable switch)
earth fault (cable switch)
earth fault cable charging (cable switch)
A
A
A
A
630
630
135
200
115
12
kA
20 / 21
13
kA
52
14
kA
20 / 21
15
16
17
18
Maximum value
Maximum value of 24 hour mean
Minimum value
Altitude for erection above sea level4
C
C
C
m
+ 50
+ 35
0
...1000
19
Relative humidity
Signature of Tenderer
Max 95%
Date:
Place:
Page 6 of 14
MGVCL/PP/D2/4013/RMU/
3
4
5
Number of phases
Whether RMU is type tested
Whether facility is provided with pressure relief
6
7
8
9
10
Insulating gas
Nominal operating gas pressure
Gas leakage rate / annum
Expected operating lifetime
Whether facilities are provided
monitoring
11
No
1
2
separate handle
separate
handle
and push buttons
O 3min-CO-3minCO
approx. 45ms
5
6
7
CO
approx. 40ms
1000
1000
CO
2000
Signature of Tenderer
IEC
Metal
Enclosed
,Panel
type,
Compact Module.
3
Yes
Yes
%
for
gas
SF6
1.4 bar abs. 20 C
0,075
30 years
Yes, temperature
compensated
manometer can be
delivered
Stainless
steel
sheet, 3 mm /
metallised
cast
resin
3position combined
switch
/
earth
switch
Date:
Place:
Page 7 of 14
MGVCL/PP/D2/4013/RMU/
10
Degree of protection:
High Voltage live parts, SF6 / VCB tank
IP 67
11
12
13
IP 2X
IP 3X
IP 54
14
15
Colours:
Front cover
Side and cable cover
5 .0 PANEL(MODULE) DESCRIPTION
5.1.1 Incoming cable module
It should be consist of an SF6 cubicle housing a switch disconnector and an ear thing
switch. Bus bars and all electrical connections are located inside the tank. The operating
shafts for the switches should be have rotary seals where they enter the SF6 cubicle. The
operating mechanisms should be located outside on the front of the SF6 tank. Cable
bushings should be located on the front of the SF6 cubicle in a separate cable
compartment. Front covers containing the mimic diagram and having a degree of protection
IP2XC close the fronts.
5.1.2 The T-off circuit breaker module (200 A)
The T-off circuit breaker module should be consist of an SF6 cubicle housing a circuit
breaker unit and a disconnector- ear thing switch. An integrated relay and related CTs is
used for tripping of the circuit breaker. Bus bars and all electrical connections should be
located inside the tank. The operating shafts for the switches should be have rotary
seals where they enter the SF6 cubicle. The operating mechanisms are located outside on
the front of the SF6 B tank. Cable bushings should be located on the front of the SF6
cubicle in a separate cable compartment. Front covers containing the mimic diagram having
a degree of protection IP2XC seal off the fronts.
6 CIRCUIT BREAKERS
SF-6 / Vacuum bottles should be use as interrupters of the currents. The circuit breaker
main circuit should be connected in series with a three-position disconnector ear thing
switch. The operation between circuit breaker and disconnector
ear thing must be
interlocked.
1. SF6 / VCB BREAKER must Self -TRIPPING AND HAS A SELF POWERED RELAY
Switch on to fault condition relay does not specify operation of O/C or Fault, so it should be
visible indication.
2. THE RMU MUST BE EXTENSIBLE TYPE
Signature of Tenderer
Date:
Place:
Page 8 of 14
MGVCL/PP/D2/4013/RMU/
The mechanism for the T-off switch and ear thing switch is operating both switches via one
common shaft. The mechanism has stored spring energy and provide independent manual
operation for closing and opening of the switch, independent closing of the ear thing switch
and dependent opening of the ear thing switch. The mechanism has fuse- tripping device.
The mechanism for the vacuum circuit breaker (VCB) and disconnector- earthing switch is
operating the VCB and the disconnector earthing switch via to separate shafts. The
mechanism for the VCB has stored spring energy and provides independent manual
operation for closing and opening of the VCB. The mechanism has a relay with related CTs
and/or remote tripping device. The mechanism for the disconnector earthing switch provide
independent manual operation for closing and opening of the disconnector, independent
closing of the earthing switch and dependent opening of the earthing switch.
Signature of Tenderer
Date:
Place:
Page 9 of 14
MGVCL/PP/D2/4013/RMU/
7.9.Power connection.
The cables are installed in the dedicated compartment below the mimic front cover. At the
bottom of the cable compartment, an earthing bar system made of copper with a minimum
cross section of 120 mm2 should be fitted. In each compartment the earthing bar should be
fitted with 4 screws M10. The earthing system is connected to the tank by a copper bar,
which rises up to the connecting point of the tank behind the rear partition wall on the
middle of the switchgear.
Signature of Tenderer
Date:
Place:
Page 10 of 14
MGVCL/PP/D2/4013/RMU/
7.10 INTERLOCKING.
The mechanism for the cable switch should be provide a built in interlocking system to
prevent operation of the switch when the earthing switch is closed, and to prevent operation
of the earthing switch when the switch is in the closed position.
The mechanism for the T-off switch should be provide a built in interlocking system to
prevent operation of the switch when the earthing switch is closed, and to prevent operation
of the earthing switch when the switch is in the closed position. In addition an interlocking
device
allows access to the fuses only when the earthing switch is in the earthed position and
opening of the earthing switch is only possible when the fuse cover is closed and secured.
The mechanism for the VCB and the disconnector-earthing switch should be have a built in
interlocking system to prevent operation of the disconnector-earthing switch when the VCB
is in the closed position.
7.12.2 Auxiliaries.
The switchgear should be prepared for options like motor operation, auxiliary contacts and
short-circuit indicators. Necessary terminal blocks and wiring etc. should be placed behind
the front cover of each module.
Signature of Tenderer
Date:
Place:
Page 11 of 14
MGVCL/PP/D2/4013/RMU/
Signature of Tenderer
Date:
Place:
Page 12 of 14
MGVCL/PP/D2/4013/RMU/
10.0 DOCUMENTATION.
An instruction manual should be provided with necessary information for receiving,
handling, storage, installation, operation and maintenance.
Routine test certificate should be follow each unit, and standard schematic drawings should
be delivered for Ring Main Units. Compact Switchgear should be have drawings that
consist of system single line drawings, general arrangement and schematic drawings for
order specific units.
All drawings shall confirm to International Standards Organization (ISO) A series of
drawing sheets/Indian Standards Specification IS : 11065. All dimensions and data shall be
in ink and suitable for microfilming. All dimensions and data shall be in S.I. Units.
NAME PLATE:
Each RMU and its associated equipment s shall be provided with following
information.
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
Name of manufacturer.
Type, design and serial number
Rated voltage and current
Rated frequency
Rated symmetrical breaking capacity
Rated making capacity
Rated short time current and its duration
Purchase Order number and date
Month and year of supply
Rated lighting impulse withstand voltage
Signature of Tenderer
Date:
Place:
Page 13 of 14
MGVCL/PP/D2/4013/RMU/
Note:
i) The word rated need not appear on the name plate.
Recognized abbreviations may be used to express the above particulars.
ii)
12.0
TRAINING:
Installation of the switchgear should be require no special tools. Optional product training