For
YORK Refrigeration
Antiscale Equipment
Model Water Manager
Produced by
Aqua-Perl Danmark ApS.
Ultrasound by Elma GmbH
Version 1.10 Sept. 2005
1.
2.
3.
4.
5.
6.
7.
8.
9.
Control Box:
Pipe make-up water:
Pipe cooling water:
Ultrasound:
Conductivity sensor:
Pump Recirculation:
Motorvalve bleed-off:
Flow Meters:
Ready-made Stand:
From left is shown: Conductivity sensor, the Min-max water level sensor and a motor valve.
The Water Manager manages the water flows to and from the condenser. It
reduces the scale in the condenser. The Water Manager is environmentally
friendly, no chemicals are applied.
For use in evaporative condensers and cooling towers is developed a special series
named Water Manager. It manages the water on both the input and output side.
The Bleed-off is managed simultaneously with the help of a microprocessor.
Conductivity measurements are made.
The Water Manager is specially designed for use in condensers. Here is the make-up
water treated as well as the tank water being circulated for repeated treatment. The
system is build with an coil pulse treatment pipe for the make-up water, and a
second pipe for the cooling water with coil and electrode pulses as well as 2
ultrasound heads.
Dimensioning
The Water Manager system is dimensioned to treat the water from all commonly
available condensers.
A total Water Manager system consist of the following components:
1.
2.
3.
4.
5.
6.
7.
8.
9.
1
2
1
2
1
1
1
1
3
Control Box
Water Treatment Pipes
Ultrasound head
Conductivity Sensors
Pump for recirculation
Motor valve for make-up water
Flow Meter for make-up water
Motor valve for bleed-off water
Flow Meters for water flow control
The method of placing two treatment pipes, one for make-up water and one for
recirculation, can be recommended for more reasons. Easier installation and
better treatment. By the floating ball valve type of water inlet is the twotreatment-pipe model the only feasible method of installation.
The treatment device consist of an inner pipe of PVC, around which an cobber coil
is laid. The electrode pair is inserted in the top end of the pipe. In the middle is
the ultrasound head placed. The outer pipe consist of PVC. The length of 950 mm
refers to the mid hole to mid hole distance. The total length is approx 1200 mm.
The straight through pipe is 650 mm long.
Item list
1 - Control box (Water Manager)
2 - Treatment pipe
3 - Conductivity sensor
4 - Pump for recirculation
5 - Valve sparge water
6 - Water meter - sparge water
7 - Motorvalve - bleed off
8 - Water Meter - bleed off
9 - Float valve
10 - Non return valve
To Receiver
Strainer
kch
6
2
9
10
2
10
7
8
3
1
The stand with the Water Manager mounted on it is normally placed in a room close
to the condenser or beside the tank where the cooling water is stored for pumping to
the condenser.
If the condenser only stores cooling water in its bottom reservoir the make-up water
is send through the make-up treatment pipe on the stand. The cooling water is lead
from the condenser reservoir through the cooling water treatment pipe by means of
the pump, and then back to the condenser reservoir. Bleed-off water is discharged
during the process when the bleed-off motorvalve is open.
When a separate tank for one or more condensers is employed, then is the Water
Manager stand placed close to the tank. Make-up water is fed through the make-up
treatment pipe. Cooling water is recirculated through the recirculation treatment pipe
and drained as explained before.
Practical steps for installation:
1. Connect the water pipes. (40 mm PVC)
Upper left: Make-up water. Middle left: Drain water. Lower left:
Recirculation Pump. Top left: Make-up water to reservoir. Top right:
Recirculation water to reservoir. By use of toilet swimmer water level control
the make-up motorvalve will be open constantly. Factory standard. Select in
System Mode: Level Sensor Configuration.
2. Connect the Water Level Sensor. (Optional)
The common in pin 10 low voltage, Low water level pin 11 and high water
level pin 12.
3. Connect the PC or network connection. Install the program. (Optional)
4. Connect the Power supply.
Power 110-240 Volt AC 50/60 Hz. Standard 220 Volt for pump and
motorvalves. If using 110 Volt supply make sure that the pump and
motorvalves are 110 Volt appliances. Pump standard 50 hz. Install 60 hz
pumps in some countries. Be sure that the ultrasound head is connected.
5. Start the Application.
Make sure that recirculation water is available. Select drain mode: 1)EC and
drain% as backup or 2)drain % only. In System Mode of the Menu. Adjust the
EC Factor and Drain %.
Display
The top line of the display indicates the OK status or alarms. The number two line shows if makeup or drain takes place. The third line shows the heading for the values. The bottom line shows the
actual values.
By scrolling the arrows pushbuttons the four main headings are shown:
1. Drain conditions, EC (Conductivity) Factor and Drain%.
2. Actual Bleed-off flow and total.
3. Actual Make-up Flow, total and EC for make-up water.
4. Actual Recirculation flow and EC for cooling water.
Pushbuttons
1. Drain Mode: To select actual drain level. EC Factor is the conductivity bleed-off level, For
example 2,0 means that bleed-off will start when the conductivity of the cooling water has
reached the double of the make-up waters conductivity. Example: Make-up water has EC
0,5 mS, with EC Factor 2,0 drain will start by EC 1,0. (0,5 x 2,0 = 1,0). The Drain % is
overruling the EC Factor, it will secure a minimum draining level. (Standard 25%)
2. Make-up: Manual check of the Make-up valve.
3. Bleed-off: Manual check of the Bleed-off valve.
4. Arrow up: For scrolling upwards for menu selection or values.
5. Arrow down: For scrolling downwards for menu selection or values.
Model water
Size
m3/h
5000
10000
Pipe Material:
Water conditions:
Cord type Coil:
Cord type Electrode:
Cord type Ultrasound:
Control Box:
Size:
Material:
Power Supply:
Internal Voltage:
Programming:
Wiring diagram:
Conductivity sensor:
Material:
63
75
5.4
18.0
l/min
Pipe
mm long
Pump
Model
166
300
950
950
CH-4-20
CH-8-20
Mounting:
Wiring:
Signal:
Water Level
Sensor:
Type:
Material:
Weight:
Wiring:
Signal:
Motor valve:
Type:
Material:
Specifications:
Power supply:
Working time:
Water Flow Meter:
Signal:
VNI 3 rods
Pump:
Type:
Power supply:
Output:
Fuses:
F4: Ultrasound 1,0 A F
F5: Intern Power 3,15 A F
F1: Make-up Valve 1,0 AF F2: Bleed- Off Valve 1,0 A F, F3: Circulation Pump 6,3 A F
2: Phase
5: Common Blue
3: Ground
14: NO
16: IN Signal
19: 2 IN Signal
22: 2 IN Signal
25: N1 Low
26: N2 High
40: E2 cable 2
The Water Manager PC program is installed on an ordinary PC. It is connected to a COM or USB
port from the RS-485 on the right side of the board. An RS-485 converter must be used.
Connection from the top pin: 1: RX-A, 2: RX-B (1 and 2 RS485 receive input) 3: Ground,
4: TX-B 5: TX-A (4 and 5 RS485 Transmit output).
When running all relevant data will be displayed on the screen. Alarms are shown in flashing red.
The settings may be changed from the PC screen.
10
Pair
RX-B
RX-A
GND
RS-485
TX-B
TX-A
Y/G
BRN
1
BLK
2
BLU
3
Level sensor
BRN
BLK
BLU
Make-up
valve
EC-sensor
Make-up
E1 E2
ST5 ST6
41 42
BRN
39 40
2 x 2 x 0,22 mm
Shielded
BLU
BRN
2
38
BRN
1
37
USB
UltraSonic.
BLU
WHT
35 36
YEL
GRN
33 34
BRN
WHT
BLU
31 32
YEL
GRN
29 30
BRN
2
BLU
BRN
BLK
BLU
BRN
BLK
BLU
BRN
BLK
BLU
BLK
27 28
D
43
PC
2 x 0,75mm
Flow-sensor
Recirc.
N1 N2
Make-up
Mag. S Electrode
2 x 0,75mm
BRN
1
BLK
2
BLU
3
24 25 26
Make-up
Mag. N
C
44
BRN
WHT
UltraSonic Head
BLU BLK
4 x 0,22 mm
Flow-sensor
Bleed-off
IN GND
Main
Mag. S
45
Electrode
4 x 0,22 mm
BLU
21 22 23
Main
Mag. N
46
Make-up
Magnet valve
2 x 0,75mm
Bleed-off
valve
BRN
IN GND
EC
Recirc.
47
2 x 0,75mm
L2
18 19 20
EC
Make-up
Level
3 x 0,75mm
L1
Circ.
pump
1 BRN
2 BLK
3 BLU
17
Flow
Recirc.
3 x 0,75mm
PE
3 x 0,75mm
Mains P
Flow-sensor
Make-up
3 x 0,75mm
3 x 0,75mm
L3 L2 L1
IN GND
15 16
BRN
14
Flow
Bleed-off
3 x 0,75mm
CO NC NO
12 13
BLU
11
BRN
10
3 x 0,75mm
L1 L2
9
BLU
C
8
WHT
Flow
Make-up
Alarm
Y/G
T3 T2 T1
Main
Switch
L1 L2
6
BLU
C
5
Make-up
BRN
L1
4
BRN
PE
3
WHT
F
2
Bleed-off
BLU
N
1
Pump
BRN
Mains
A
1 1
B
2 2
C
3 3
D
4 4
5 5
6 6
7 7
8 8
9 9
Main
Magnet valve
EC-sensor
Recirc.
STR.
FSCM-NR.
TEGNINGSNR.
REV.
1:10
PAPIR
A
1 AF 1