CALCULO DE CAIDA DE TENSION : INSTALACIONES ELECTRICAS "I.E.

DANIEL HERNANDEZ" - PAMPAS TAYACAJA - HUANCAVELICA


TRAMO CRITICO ALIMENTADOR: TG-TD6;
TRAMOS CRITICOS ALIMENTADORES: TG-TD9. - T
PTOS.
P (KW)
SUM P
L (MT)
K(FCT )
S( mm )
AV (%)
SUM AV (%)
I (A)

B
C
D
E
31.11
27.34
8.75
5.65
2.44
75.29
44.18
16.84
8.09
2.44
38
65
45
60
23
0.000173 0.00024 0.00035 0.00048 0.000758
70
50
35
25
16
0.494956 0.6961 0.26243 0.2353 0.042511
0.494956 1.19106 1.45348 1.68879 1.731296 OK
127.2521 74.6713 28.4623 13.6734 4.12399

G
H
4.38
10.06
3.2
17.64
13.26
3.2
71
20
25
0.000758 0.0012119 0.00202
16
10
6
0.948723 0.3213959 0.16159
0.948723 1.2701192 1.43171 OK
29.81442 22.41152 5.40851

I
J
13.26
2.43
1.95
17.64
4.38
1.95
71
33
24
0.00076 0.00121 0.00202
16
10
6
0.94872 0.17517 0.094529
0.94872 1.12389 1.21842 OK
29.8144 7.4029 3.295812

CALCULO DE CAIDA DE TENSION : INSTALACIONES ELECTRICAS "I.E. DANIEL HERNANDEZ" - PAMPAS TAYACAJA - HUANCAVELICA
TRAMO CRITICO ALIMENTADOR: TG-TD3A;
TRAMOS CRITICOS ALIMENTADORES: TG-TD3B.
PTOS.
P (KW)
SUM P
L (MT)
K(FCT )
S( mm )
AV (%)
SUM AV (%)
I (A)

A
31.11
75.44
38
0.000173
70
0.495943
0.495943
127.5057

B
31.96
44.33
65
0.00024
50
0.69846
1.19441
74.9248

C
12.37
12.37
10
0.00121
10
0.14991
1.34432 OK
20.9073

B
C
31.11
41.48
2.85
75.44
44.33
2.85
38
65
10
0.000173 0.0002424 0.00121
70
50
10
0.495943 0.6984635 0.03454
0.495943 1.194406 1.22895 OK
127.5057 74.924788 4.81696