You are on page 1of 11

CALCULATION SUMMARY

Project Name : Job Name

Project Location:

Drawing No. :

City:

Design Areas
Design Area
Name

Tercer piso p2

Calc. Mode
(Model)

Demand (HW)

Occupancy

Area of
Total Water Pressure @
Application
Source

Min.
Density

Min.
Pressure

Min.
Flow

Calculated
Heads

Hose
Streams

Margin To
Source

(ft)

(gpm)

(psi)

(gpm/ft)

(psi)

(gpm)

(gpm)

(psi)

2000

325,5

165,4

0,09

10,3

36

100

32,5

File: C:\Users\Hidraulico\appdata\local\temp\HTMC 3P_1_1_2360.sv$


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 1

HYDRAULIC CALCULATIONS
for
Job Information
Project Name : Job Name
Contract No. :

City:

Project Location:

Date: 26/09/2014

Contractor Information
Name of Contractor:
Address:

City:

Phone Number:

E-mail:

Name of Designer:
Authority Having Jurisdiction:

Design
Remote Area Name

Tercer piso p2

Remote Area Location

HTMC

Occupancy Classification
Density (gpm/ft)

0,09

Area of Application (ft)

2000

Coverage per Sprinkler (ft)

400

Number of Calculated Sprinklers

In-Rack Demand (gpm)

Special Heads
Hose Streams (gpm)

100

Total Water Required (incl. Hose Streams) (gpm)

325,5

Required Pressure at Source (psi)

128,4

Type of System

Wet

Volume - Entire System (gal)

147,7 gal

Water Supply Information


Date

26/09/2014

Location

HTMC

Source

W2

Notes

File: C:\Users\Hidraulico\appdata\local\temp\HTMC 3P_1_1_2360.sv$


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 2

Job : Job Name

Node Labels:
Pipe Labels:

Off
Off

Diagram for Design Area : Tercer piso p2


(Optimized Hydraulic Simplified)

File: C:\Users\Hidraulico\appdata\local\temp\HTMC 3P_1_1_2360.sv$


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 3

Job : Job Name

Hydraulic Analysis for : Tercer piso p2


Calculation Info
Calculation Mode
Hydraulic Model
Fluid Name
Fluid Weight, (lb/ft)
Fluid Dynamic Viscosity, (lbs/ft)

Demand
Hazen-Williams
Water @ 60F (15.6C)
N/A for Hazen-Williams calculation.
N/A for Hazen-Williams calculation.

Water Supply Parameters


Flow (gpm)
0
500

Supply 1 : W2

Pressure (psi)
170
150

Hoses
Inside Hose Flow / Standpipe Demand (gpm)
Outside Hose Flow (gpm)
Additional Outside Hose Flow (gpm)

100

Other (custom defined) Hose Flow (gpm)


Total Hose Flow (gpm)

100

Sprinklers
Ovehead Sprinkler Flow (gpm)

225,5

InRack Sprinkler Flow (gpm)

Other (custom defined) Sprinkler Flow (gpm)

Total Sprinkler Flow (gpm)

225,5

Required Margin of Safety (psi)

W2 - Pressure (psi)

128,4

W2 - Flow (gpm)

225,5

Demand w/o System Pump(s)

N/A

Other

File: C:\Users\Hidraulico\appdata\local\temp\HTMC 3P_1_1_2360.sv$


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 4

Job : Job Name

Hydraulic Analysis for : Tercer piso p2

File: C:\Users\Hidraulico\appdata\local\temp\HTMC 3P_1_1_2360.sv$


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 5

Job : Job Name

Hydraulic Analysis for : Tercer piso p2


Graph Labels
Label

Values

Description

S1

Supply point #1 - Static

S2

Supply point #2 - Residual

D1

Elevation Pressure

D2
D3

Flow (gpm)

Pressure (psi)

170

500

150

4,3

System Demand

225,5

128,4

System Demand + Add.Out.Hose

325,5

128,4

Curve Intersections & Safety Margins


Intersection

Curve Name
Supply

Safety Margin

Pressure (psi)

Flow (gpm)

Pressure (psi)

@ Flow (gpm)

164,1

258,6

32,5

325,5

Open Heads
Head Ref.

Head Type

Required
Coverage

Calculated

K-Factor
Density

Flow

Pressure

Density

Flow

Pressure

(ft)

(gpm/psi)

(gpm/ft)

(gpm)

(psi)

(gpm/ft)

(gpm)

(psi)

S62

Overhead
Sprinkler

400

11,2

0,09

36

10,3

0,129

51,7

21,3

S63

Overhead
Sprinkler

400

11,2

0,09

36

10,3

0,136

54,6

23,7

S64

Overhead
Sprinkler

400

11,2

0,09

36

10,3

0,092

36,8

10,8

S65

Overhead
Sprinkler

400

11,2

0,09

36

10,3

0,116

46,5

17,2

S66

Overhead
Sprinkler

400

11,2

0,09

36

10,3

0,09

36

10,3

File: C:\Users\Hidraulico\appdata\local\temp\HTMC 3P_1_1_2360.sv$


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 6

Job : Job Name

Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data
Node#
Elev

Type
Hgroup

K-Fact.
Discharge
Coverage Tot. Pres.
Req. Pres.
Open/Closed Overdischarge Density Elev. Pres. Req. Discharge
gpm
gpm

gpm/psi

ft

ft
gpm/ft

psi
psi

psi
gpm

S62
50

Overhead Sprinkler 11,2


HEAD
Open

51,7
15,7

400
0,129

21,3
-4,3

10,3
36

S63
50

Overhead Sprinkler 11,2


HEAD
Open

54,6
18,6

400
0,136

23,7
-4,3

10,3
36

S64
50

Overhead Sprinkler 11,2


HEAD
Open

36,8
0,8

400
0,092

10,8
-4,3

10,3
36

S65
50

Overhead Sprinkler 11,2


HEAD
Open

46,5
10,5

400
0,116

17,2
-4,3

10,3
36

S66
50

Overhead Sprinkler 11,2


HEAD
Open

36
0

400
0,09

10,3
-4,3

10,3
36

001
50

Node
NODE

14,2
-4,3

002
50

Node
NODE

20,6
-4,3

005
49

Node
NODE

27,6
-3,9

039
49

Node
NODE

124,1
-3,9

264
49

Node
NODE

27,2
-3,9

265
49

Node
NODE

27,1
-3,9

W2
40

Supply
SUPPLY

-225,5

128,4
0

File: C:\Users\Hidraulico\appdata\local\temp\HTMC 3P_1_1_2360.sv$


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 7

Job name: Job Name

Sheet number:___________________

PIPE INFORMATION
Node 1
Node 2

Elev 1
Elev 2

(ft)

S66
001

50
50

001
002

K-Factor 1 Flow added(q)* Nominal ID


Fittings
K-Factor 2 Total flow (Q) Actual ID
quantity x (name) = length

(gpm/psi)

(gpm)

11,2

(in)

(ft)

L
F
T

C Factor total (Pt)


Pf per ft elev (Pe)
frict (Pf)

(ft)

(psi)

(psi)

36
36

1 1x(us.Tee-Br)=5
1,049

5,07
5
10,07

120
0,3851

10,3
0
3,9

50
50

36,8
72,8

1.25 1x(us.Tee-Br)=6
1,38

11,22
6
17,22

120
0,3736

14,2
0
6,4

002
005

50
49

46,5
119,3

1.25 1x(us.Tee-Br)=6
1,38

1
6
7

120
0,9317

20,6
0,4
6,5

005
039

49
49

106,2
225,5

2.5 3x(us.90)=18
2,469

523,47
18
541,47

120
0,1783

27,6
0
96,5

039
W2

49
40

0
225,5

4 1x(us.90)=10
4,026

13,39
10
23,39

120
0,0165

124,1
3,9
0,4

S64
001

50
50

11,2

36,8
36,8

1 1x(us.Tee-Br)=5
1,049

3,42
5
8,42

120
0,402

10,8
0
3,4

S65
002

50
50

11,2

46,5
46,5

1.25 1x(us.Tee-Br)=6
1,38

15,13
6
21,13

120
0,1625

17,2
0
3,4

S62
265

50
49

11,2

51,7
51,7

1.25 2x(us.Tee-Br)=12
1,38

15,23
12
27,23

120
0,1979

21,3
0,4
5,4

265
264

49
49

0
51,7

2.5
2,469

9,84
0
9,84

120
0,0116

27,1
0
0,1

264
005

49
49

54,6
106,2

2.5
2,469

8,33
0
8,33

120
0,0442

27,2
0
0,4

S63
264

50
49

5,09
9
14,09

120
0,2187

23,7
0,4
3,1

11,2

54,6
54,6

1.25 1x(us.Tee-Br)=6
1,38 1x(us.90)=3

NOTES

Discharge shown for flowing nodes only

2006 National Fire Protection Association

Page 8

Job : Job Name

Hydraulic Calculations

PIPE INFORMATION
Node 1
Node 2

Elev 1
Elev 2

(ft)

K-Factor 1 Flow added (q) Nominal ID


Fittings
K-Factor 2 Total flow (Q) Actual ID
quantity x (name) = length

(gpm/psi)

(gpm)

(in)

(ft)

L
F
T

C Factor total (Pt)


Pf per ft elev (Pe)
frict (Pf)

(ft)

(psi)

NOTES

(psi)

Path No: 1
S66
001

50
50

001
002

11,2

36
36

1 1x(us.Tee-Br)=5
1,049

5,07
5
10,07

120
0,3851

10,3
0
3,9

50
50

36,8
72,8

1.25 1x(us.Tee-Br)=6
1,38

11,22
6
17,22

120
0,3736

14,2
0
6,4

002
005

50
49

46,5
119,3

1.25 1x(us.Tee-Br)=6
1,38

1
6
7

120
0,9317

20,6
0,4
6,5

005
039

49
49

106,2
225,5

2.5 3x(us.90)=18
2,469

523,47
18
541,47

120
0,1783

27,6
0
96,5

039
W2

49
40

0
225,5

4 1x(us.90)=10
4,026

13,39
10
23,39

120
0,0165

124,1
3,9
0,4

W2

128,4

Path No: 2
S64
001

50
50

11,2

36,8
36,8

1 1x(us.Tee-Br)=5
1,049

3,42
5
8,42

120
0,402

001

10,8
0
3,4
14,2

Path No: 3
S65
002

50
50

11,2

46,5
46,5

1.25 1x(us.Tee-Br)=6
1,38

15,13
6
21,13

120
0,1625

002

17,2
0
3,4
20,6

Path No: 4
11,2

S62
265

50
49

51,7
51,7

265
264

49
49

0
51,7

264
005

49
49

54,6
106,2

1.25 2x(us.Tee-Br)=12
1,38

15,23
12
27,23

120
0,1979

21,3
0,4
5,4

2.5
2,469

9,84
0
9,84

120
0,0116

27,1
0
0,1

2.5
2,469

8,33
0
8,33

120
0,0442

27,2
0
0,4

005

27,6

Path No: 5
S63
264

50
49

11,2

54,6
54,6

1.25 1x(us.Tee-Br)=6
1,38 1x(us.90)=3

5,09
9
14,09

264

120
0,2187

23,7
0,4
3,1
27,2

File: C:\Users\Hidraulico\appdata\local\temp\HTMC 3P_1_1_2360.sv$


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 9

Job : Job Name

Hydraulic Calculations

PIPE INFORMATION
Node 1
Node 2

Elev 1
Elev 2

(ft)

K-Factor 1 Flow added (q) Nominal ID


Fittings
K-Factor 2 Total flow (Q) Actual ID
quantity x (name) = length

(gpm/psi)

(gpm)

(in)

(ft)

L
F
T
(ft)

C Factor total (Pt)


Pf per ft elev (Pe)
frict (Pf)
(psi)

Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.

Maximum Velocity of 25,59 ft/s occurs in the following pipe(s):

NOTES

(psi)

(005-002)

File: C:\Users\Hidraulico\appdata\local\temp\HTMC 3P_1_1_2360.sv$


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 10

Job : Job Name

Device Graphs

File: C:\Users\Hidraulico\appdata\local\temp\HTMC 3P_1_1_2360.sv$


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 11